Skip to main content

ECC or Buildings Branch | Flame Safeguard part 2

Flame Detectors
C7012 Solid State Purple Peeper® Ultraviolet Flame Detector
Solid state electronic flame detectors for use with Honeywell
Flame Safeguard controls and amplifiers. Sense ultraviolet
radiation produced by combustion of gas, oil, coal or other fuels.
• Mount horizontally, vertically or at any angle in between.
• Provide quick electrical hookup with threaded conduit fitting and
color-coded leadwires.
• Reduced nuisance shutdowns by wiring two in parallel.
• C7012E1278 5 pin Brad Harrison type (formally 41307N) mating
connector not supplied nor available through Honeywell.
• C7012A, E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7012C, F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper
Application: Gas, Oil or Coal fired burners
Lead Length: 96 in. (2438 mm)
Power Consumption: 2.5 W
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 14740.01
Material
Number
Frequency Weight NEMA
Rating
Electrical
Connections
Mounting Electrical
Ratings
Ambient
Temperature
Range
Approvals,
Underwriters
Laboratories Inc.
Approvals,
Others
Includes Used With
C7012A1145/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, R7847A,
R7257; Flame
Amplifiers: R7247A,
B; R7847A, B; R7257
C7012A1152/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
1 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1160/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
1 in. NPT 120 Vac -40°F to
+175°F
(-40°C to
+79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1186/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 208 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1194/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 240 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1202/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 100 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, R7847A,
R7257
C7012A1210/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, R7847A,
R7257
C7012C1042/U 50 Hz;
60 Hz
14.5 lb
(6.6 kg)
Explosion
Proof
4 NEC Class
1 Colorcoded
lead
wires.
1 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
E34649, Guide
No. ZTSZ
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012G1019/U 50 Hz 4.25 lb
(1.9 kg)
NEMA 4 5 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 220 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Meets DIN
Standards
Cast
case and
cover
Flame Amplifiers:
R7247C, R7847C
70-6910 799
Commercial/Industrial
Combustion Controls
Flame Detectors
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
800 70-6910
Flame Detectors
C7012 Solid State Purple Peeper® Ultraviolet Flame Detector
(Self-Checking)
Solid state electronic flame detectors for use with Honeywell
Flame Safeguard controls and amplifiers. Sense ultraviolet
radiation produced by combustion of gas, oil, coal or other fuels.
• Mount horizontally, vertically or at any angle in between.
• Provide quick electrical hookup with threaded conduit fitting and
color-coded leadwires.
• Reduced nuisance shutdowns by wiring two in parallel.
• C7012E1278 5 pin Brad Harrison type (formally 41307N) mating
connector not supplied nor available through Honeywell.
• C7012A, E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7012C, F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper, Self-Checking
Application: Gas, Oil or Coal fired burners
Lead Length: 96 in. (2438 mm)
Power Consumption: 7.0 W
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 14740.01
Used With: Flame Amplifiers: R7247C, R7847C
Material
Number
Frequency Weight NEMA
Rating
Electrical
Connections
Mounting Electrical
Ratings
Ambient
Temperature
Range
Approvals,
Underwriters
Laboratories Inc.
Approvals,
Others
Includes
C7012E1104/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1112/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
1 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1120/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
1 in. NPT 120 Vac -40°F to +175°F
(-40°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1146/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 208 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover,
with Hot refractory
tube
C7012E1153/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 240 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1187/U 50 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 220 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
DIN (Europe) Cast case and cover
C7012E1195/U 50 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 110 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
BGC (Europe) Cast case and cover
C7012E1203/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 240 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
BGC (Europe) Cast case and cover
C7012E1278/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 Brad Harrison
type number
41310
connector
1 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012F1052/U 50 Hz; 60 Hz 14.5 lb
(6.6 kg)
Explosion
Proof
6 NEC Class 1
Color-coded
lead wires.
1 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
E34649, Guide
No. ZTSZ
Explosion-proof, two
piece, violet, cast
aluminum enclosure
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
70-6910 801
Commercial/Industrial
Combustion Controls
Flame Detectors
C7024 Solid State Purple Peeper® Ultraviolet Flame Detector
24 Vdc solid state electronic flame detectors for sensing the
ultraviolet radiation emitted by the combustion of most carbon
containing fuels, such as natural gas, LP gases, and oil.
• Use with R7824C Dynamic Self-Check Flame Signal Amplifier.
• Circuitry provides low power consumption and high reliability.
• Mount horizontally, vertically or at any angle in between.
• Field-replaceable UV radiation sensing tube and quartz viewing
window.
• Quick electrical installation with threaded conduit fitting and colorcoded
leadwires.
• Reduce nuisance shutdowns by wiring two in parallel.
• Oscillating shutter interrupts UV radiation using the R7824C
amplifier.
• C7024E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7024F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper, Self-Checking
Application: Coal fired burners; Gas fired burners; Oil fired burners
Lead Length: 96 in. (2438 mm)
Electrical Connections: Six NEC CLASS 1 color-coded leaders
Electrical Ratings: 24 Vdc
Power Consumption: 7.8 W maximum.
Ambient Temperature Range: -20°F to +175°F (-20°C to +79°C)
Approvals, CSA: Certified: Master Report LR95329-3
Used With: Flame Amplifiers: R7824C
Accessories:
190971G/U – 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
Material Number NEMA Rating Mounting Approximate, Dimensions Weight Approvals, Underwriters
Laboratories Inc.
Includes Comments
C7024E1001/U NEMA 4 3/4 in. NPT 5 1/4 in. diameter (includes
mounting flange) x 7 7/32 in.
long (133 mm diameter (includes
mounting flange) x 183 mm long)
4.25 lb (1.9 kg) Component Recognized: File
No. MP268
Cast case and
cover
Flame Amplifiers:
R7824C
C7024F1009/U Explosion
Proof
1 in. NPT 8 in. diameter x 12 in. long (203 mm
diameter x 305 mm long)
14.5 lb (6.6 kg) Component Recognized: For
use in hazardous locations;
Class 1 Groups C and D; Class
2, Groups E, F and G; File no.
E34649
Flame Amplifiers:
R7824C
802 70-6910
Flame Detectors
C7027; C7044 Minipeeper Ultraviolet Flame Detector
Compact Flame Detector for use with flame safeguard controls
with ultraviolet amplifiers.
• Use with Honeywell Flame Safeguard primary safety controls and
burners requiring ultraviolet flame detection.
• C7027 mounts on a 1/2 in. sighting pipe by using an integral collar.
• Detectors can be wired in parallel for difficult sighting applications.
• C7027 seals against pressures up to 5 psi (34.5 kPa) when correctly
installed.
• Allows for blast tube mounting due to compact size.
• C7044 mounts with a two screw bracket.
• The C7044 UV sensor tube is enclosed in a stainless steel housing.
• C7044 has the capability of side or end viewing in flame monitoring
applications.
Type: Ultraviolet, Minipeeper
Electrical Connections: 2 NEC Class 1 leadwires
Vibration: 0.5 G max
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259,
R7290
Material Number Application Lead Length Mounting Ambient
Temperature Range
Approvals,
Others
Includes Comments
C7027A1023/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
Detects ultraviolet
radiation in flames
C7027A1031/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
Detects ultraviolet
radiation in flames
C7027A1049/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1056/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
DIN (Europe) Detects ultraviolet
radiation in flames
C7027A1064/U Coal fired burners; Gas fired
burners; Oil fired burners
288 in. (7315
mm)
Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1072/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1080/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
136733 Heat Block
and 390427B bushing
Detects ultraviolet
radiation in flames
C7027A1114/U Coal fired burners; Gas fired
burners; Oil fired burners
44 in. (1118 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
installed 22" flexible
conduit
Detects ultraviolet
radiation in flames
C7027A1122/U Oil fired burners; Gas fired
burners; Coal fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1130/U Gas fired burners; Oil fired
burners; Coal fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to +215°F
(-40°C to +102°C)
Detects ultraviolet
radiation in flames
C7044A1006/U Coal fired burners; Gas fired
burners; Oil fired burners
72 in. (1829 mm) Mounting Bracket
provided
0°F to 215°F
(-18°C to +102°C)
Mounting bracket Detects ultraviolet
radiation in flames
- Side Viewing
Dimensiions in inches (millimeters)
COLLAR WITH 1/2-14 NPSM
INTERNAL THREADS
4 (102) 8 FOOT (2.44 METER)
LEADWIRES (2)
M1943G
C7027A1064 HAS 24 FOOT (7.32 METER) LEADWIRES. C7027A1114 HAS
44 IN. (1.118 M) LEADWIRES WITH 22 IN. (558 MM) FLEXIBLE CONDUIT.
1
2
2
3-1/2 (89)
1-1/16
(27)
1
MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL
THREADS) INSTEAD OF CLAMP TYPE CONNECTOR.
6 FOOT
[1.83 METER]
LEAD
WIRES (2)
3-5/8 (92)
1/2
(13)
1-27/64
(36)
3/8
(10)
7/8
(22)
9/16
(14)
M1944D
MOUNTING
BRACKET
70-6910 803
Commercial/Industrial
Combustion Controls
Flame Detectors
C7035 Minipeeper Ultraviolet Flame Detector
Dimensiions in inches (millimeters)
1/2-14 NPSM
INTERNAL THREADS
COLLAR WITH 2 (51) 2
1 - 11-1/2 NPSM
INTERNAL
THREADS
1
1 DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL MOUNTING THREADS.
DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL MOUNTING THREADS.
C7035A1056 HAS 12 FOOT (3.66 METER) LEADWIRES.
2
3
INSERTION DEPTH
6 FOOT
[1.83 METER]
LEADWIRES (2) 3
M1945E
2-5/8 (67)
1-1/2
(38)
31/32
(25)
4-1/8 (105)
1-3/16
(30)
Compact flame detector for use with flame safeguard controls
with ultraviolet amplifiers.
• Use with Honeywell Flame Safeguard primary safety controls and
burners requiring ultraviolet flame detection.
• Mounts on a 1 in. sighting pipe by using an integral collar.
• Protects the sensing tube with a shield.
• Meets outdoor rain tight requirements of Underwriters Laboratories
Inc., NEMA 4 and NEMA 4X.
• Wires in parallel for difficult sighting applications.
• Seals against pressures as high as 5 psi (34.5 kPa) when correctly
installed.
• Field-replaceable ultraviolet sensing tube.
Type: Ultraviolet, Minipeeper
NEMA Ratings: NEMA 3 and NEMA 4
Electrical Connections: 2 NEC Class 1 leadwires
Vibration: 0.5 G max
Mounting: Integral nut for 1 in. sighting pipe.
Approximate, Dimensions: 1 1/2 in. diameter x 4 1/8 in. long (38 mm
diameter x 105 mm long)
Weight: 6 oz (0.17 kg)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Comments: Detects ultraviolet radiation in flames
Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259,
R7290
Material Number Application Lead Length Ambient Temperature Range Approvals, Others Includes
C7035A1023/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C)
C7035A1031/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C)
C7035A1049/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) DIN (Europe)
C7035A1056/U Coal fired burners; Gas fired burners; Oil fired burners 144 in. (3658 mm) -40°F to +250°F (-40°C to +121°C)
C7035A1064/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C)
C7035A1080/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) 600F leads
C7035A1098/U Oil fired burners; Gas fired burners; Coal fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C)
804 70-6910
Flame Detectors
C7061 Dynamic Self-Check Ultraviolet Flame Detector
Dynamic self-checking flame detector used with R7861 Dynamic
Self-check Amplifiers for sensing the ultraviolet radiation
generated by the combustion of gas, oil, or other fuels.
• Oscillating shutter interrupts ultraviolet radiation reaching the UV
sensor to provide the UV sensor tube checking function.
• Can be mounted horizontally, vertically or at any angle in between.
• The detector requires faceplate alignment and has integral
locating reference points to assure proper operation of the shutter
mechanism.
• Field replaceable ultraviolet sensing tube and quartz viewing window.
• Models with threaded conduit fitting and color-coded leadwires allow
rapid electrical installation.
• C7061A1038 or A1046 5 pin Brad Harrison type (formally 41307N)
mating connector not supplied nor available through Honeywell.
• Two detectors can be wired in parallel to reduce nuisance shutdowns
in difficult flame sighting applications.
• Protective heat block built into mounting flange.
• -40°F (-40°C) rated ultraviolet sensing tube is supplied.
• C7061E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7061F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper, Self-Checking
Application: Gas fired burners; Oil fired burners
Comments: Dynamic self-checking flame detector
Used With: Flame Amplifiers: R7861
Approvals, Underwriters Laboratories Inc.: C7061A, M-Listed:
File No. MP268, Guide No. MCCZ; C7061F-Recognized: For use in
hazardous locations, Class 1 Groups C and D; class 2, Groups E, F
and G; File no. E34649
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 14740.01
Material
Number
NEMA Rating Lead Length Electrical Connections Mounting Electrical Ratings Frequency Ambient
Temperature Range
Approvals,
Others
C7061A1004/U NEMA 4 77 in.
(1981 mm)
PVC jacketed cable 3/4 in. NPT 120 Vac 50 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1012/U NEMA 4 96 in.
(2438 mm)
Color-coded leadwires 3/4 in. NPT 120 Vac 51 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1020/U NEMA 4 Terminal block 3/4 in. NPT 120 or 230 Vac 52 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1038/U NEMA 4 Brad Harrison type
number 41310 connector
3/4 in. NPT 120 Vac 53 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1046/U NEMA 4 Brad Harrison type
number 41310 connector
1 in. NPT 120 Vac 54 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1053/U NEMA 4 96 in.
(2438 mm)
Color-coded leadwires 1 in. NPT 120 Vac 55 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061F1003 Explosion Proof Terminal block 1 in. NPT 120 or 230 Vac 56 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
CE and conforms
to EEXD IIc
C7061F2001/U Explosion Proof 96 in.
(2438 mm)
Color-coded leadwires 1 in. NPT 120 Vac 57 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061M1008/U NEMA 4 96 in.
(2438 mm)
Color-coded leadwires 1 in. NPT 120 Vac 58 Hz; 60 Hz -4°F to +175°F
(-20°C to +79°C)
C7061M1016/U NEMA 4 Brad Harrison type
number 41310 connector
1 in. NPT 120 Vac 59 Hz; 60 Hz -4°F to +175°F
(-20°C to +79°C)
Dimensions for C7061A in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
Dimensions for C7061F in inches (millimeters)
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
70-6910 805
Commercial/Industrial
Combustion Controls
Flame Detectors
Dimensions for C7061M in inches (millimeters)
M29114A
2-9/64 (55)
13/16 (21)
2-21/32
(68)
3-15/32
(88)
1-33/64
(39)
PARALLEL
PIPETHREAD
1-11/2 NPSM
33/64
(13)
2-9/64
(55)
1-35/64
(40)
CONDUIT TUBE CONNECTION
PORT 1/2 NPSM
806 70-6910
Flame Detectors
C7076 Adjustable Sensitivity Ultraviolet Flame Detector
Solid state dynamic self check flame detectors for use with
BC7000, R4140 or FSP5075 with R7476 Amplifier and 7800 SERIES
with R7886 Amplifier.
• Use Honeywell Flame Safeguard primary safety controls requiring
adjustable sensitivity ultraviolet flame detection.
• Detect ultraviolet radiation from flames.
• Include dual sensitivity adjustment.
• C7076A meets NEMA 4 standards with viewing window rated to 20
psi.
• C7076D has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Adjustable Sensitivity
Application: Gas fired burners; Oil fired burners
Electrical Connections: Terminal block
Vibration: 0.5 G max
Mounting: 1 in. NPT
Power Consumption: 7.0 W
Ambient Temperature Range: -40°F to +160°F (-40°C to +71°C)
Approvals, CSA: Certified: Master Report LR1620
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. FM26980
Comments: Dynamic self-checking flame detector with adjustable
sensitivity
Used With: Flame Amplifiers: R7476, R7886
Replacement Parts:
190971F/U – 100 Vac Coil and Shutter Assembly for C7076A, D
190998A/U – Aspiration assembly for C7076A
191002R/U – 120 Vac Plug in Electronics less UV Sensing Tube for
C7076D
191050/U – Quartz Viewing Window for C7076
191053/U – UV Sensing Tube for C7076
Dimensiions in inches (millimeters)
C7076A
C7076D M20749A
2-1/4
(57)
2-1/4
(57)
2-9/32
(58)
5-25/32 (147)
5-25/32
(147)
1-27/32
(47)
7-13/16 (198)
15/16
(24)
25/32 (20)
1-9/16 (40)
11-13/16 (300)
3/4 (19)
1-5/8
(19)
2-21/32
(68)
7-19/32
(194)
3/8 INCH NPT
1 (25)
29/32 (22) OPENING FOR
1/2-INCH CONDUIT
7-13/32 (188)
10-1/4 (261)
1-1/16
(27)
4
(102)
4 (102)
4-25/32 (122)
1 INCH NPT
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1
1
6-23/32
(171)
1-31/32 (50)
3-15/16 (100)
5/16-18 UNC (3 PLCS)
X 0.47 (12) DEEP
Material Number NEMA Rating Electrical
Ratings
Frequency Approximate, Dimensions Weight Approvals, Underwriters
Laboratories Inc.
Approvals,
Others
C7076A1007/U NEMA 4 120 Vac 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep
(102 mm high x 102 mm wide x 261 mm deep)
6.6 lb
(3 kg)
Listed: File No. MP268, Guide
No. MCCZ
C7076A1015/U NEMA 4 100 Vac 50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep
(102 mm high x 102 mm wide x 261 mm deep)
6.6 lb
(3 kg)
Listed: File No. MP268, Guide
No. MCCZ
C7076A1031/U NEMA 4 220 Vac;
240 Vac
50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep
(102 mm high x 102 mm wide x 261 mm deep)
6.6 lb
(3 kg)
Listed: File No. MP268, Guide
No. MCCZ
C7076D1027/U NEMA 7 120 Vac 60 Hz 6 5/8 in. high x 6 3/16 in. wide x 11 3/4 in. deep
(168 mm high x 158 mm wide x 300 mm deep)
17.6 lb
(8 kg)
Listed: File No. E34649, Guide
No. ZTSZ
Explosion
Proof
70-6910 807
Commercial/Industrial
Combustion Controls
Flame Detectors
C7927 Solid State Ultraviolet Flame Detector
Dimensiions in inches (millimeters)
8 FT (2.44 M)
1 (25)
C7927A1016 M24714
3-3/4
(95)
3-1/4
(82)
The Solid State Ultraviolet Flame Detectors, sense ultraviolet
radiation emitted by combustion flames. The flame detectors are
used with Honeywell flame safeguard controls to provide flame
supervision for gas, oil, or combination gas-oil burners.
• Properly installed the flame detectors are pressure rated for 5 psi.
• Flame detector is used with only the R7851B Flame Amplifier and
the 7800 SERIES controls.
• Has an integral collar threaded (internal 1/2-14 NPSM) for mounting
on a one-half inch sight pipe.
Type: Ultraviolet, Minipeeper
Application: Gas, Oil, or combination burners-intermittent operation
only (burner cycled at least once each 24 hours).
NEMA Rating: NEMA 1
Electrical Connections: 2 NEC Class 1 leadwires
Mounting: 1/2 in. NPT pipe mounting
Approximate, Dimensions: 1 in. diameter x 3 3/4 in. long (25 mm
diameter x 95 mm long)
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MP268
Approvals, CSA: Report 158158
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 3011020
Comments: Detects ultraviolet radiation in flames
Material Number Lead Length Ambient Temperature Range Used With
C7927A1016/U 96 in. (2438 mm) -40°F to +200°F (-40°C to +93°C) Flame Amplifiers: R7851B
808 70-6910
Flame Detectors
C7961 Dynamic Self-checking Solid State Ultraviolet Flame Detector
A self-checking flame detector using a solid state UV sensor to
detect ultraviolet radiation in flames for supervision of gas, oil or
combination gas-oil burners.
• Designed for use with 7800 series controls with the R7851C flame
amp.
• Oscillating shutter interrupts ultraviolet radiation reaching the UV
sensor to provide the solid state UV sensor checking function.
• Can be mounted horizontally, vertically or at any angle in between.
• The detector requires faceplate alignment and has integral
locating reference points to assure proper operation of the shutter
mechanism.
• Models available with threaded conduit fitting and color-coded
leadwires allow rapid electrical installation.
• C7961E1022 or E1030 5 pin Brad Harrison type (formally 41307N)
mating connector not supplied nor available through Honeywell.
• Incorporates UV sensor tube checking feature; used with
R7851C1008 Dynamic Self-check Amplifiers.
• Protective heat block built into mounting flange.
• -40°F (-40°C) rated ultraviolet sensing cell is supplied.
• C7961E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7961F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Self-Checking
Application: Gas, Oil or other fuels
Electrical Ratings: 120 Vac (-15% +10%)
Frequency: 50 Hz; 60 Hz
Ambient Temperature Range: -40°F to +175°F (-40°C to +80°C)
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MP268
Comments: Detects ultraviolet radiation generated by combustion of
gas, oil, or other fuels
Approvals, Swiss RE: Acceptable
Used With: R7851C Dynamic Self-Check Amplifier
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
Material
Number
NEMA
Rating
Lead
Length
Electrical
Connections
Mounting Approximate, Dimensions Weight Approvals,
CSA
Approvals,
Factory Mutual
Includes
C7961E1006/U NEMA 4 96 in.
(2438 mm)
NEC Class 1
color-coded
3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961E1014/U NEMA 4 96 in.
(2438 mm)
NEC Class 1
color-coded
1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961E1022/U NEMA 4 5 pin Brad
Harrison
Type
Connector
1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961E1030/U NEMA 4 5 pin Brad
Harrison
Type
Connector
3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961F1004/U Explosion
Proof
96 in.
(2438 mm)
NEC Class 1
color-coded
1 in. NPT 8 in. diameter x 12 in. long (203 mm
diameter x 305 mm long)
14.5 lb
(6.6 kg)
Approved:
Report No.
14740.01
Quartz Viewing
Window rated for
100 psi
70-6910 809
Commercial/Industrial
Combustion Controls
Flame Detectors
C7915 Infrared Flame Detector
The C7915 Combination mount Lead Sulfide cell senses infrared
radiation from gas, oil, and coal or dual-fuel flames.
• Used for combination or dual-fuel applications.
• Detects pilot and main flame.
• Mounts quickly and easily on a standard 3/4 in. sighting pipe.
• Works where flame rod or rectifying photocell mounts are difficult to
apply.
Type: Infrared (Lead Sulfide)
Application: Used for combination or dual-fuel applications
Electrical Connections: Two no. 18 AWG wires
Mounting: 3/4 in. NPT
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Comments: Infrared (Lead Sulfide) Flame Detector
Replacement Parts:
32007255-001/U – Lead Sulfide Cell for C7915
50019469-001/U – Magnifying Lens Assembly for C7915A
Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With
C7915A1010/U 30 in. (762 mm) 1 1/4 in. diameter x 2 1/4 in. long
(32 mm diameter x 58 mm long)
-20°F to 125°F operating range
(-18°C to 52°C operating range)
With magnifying lens,
32007255-001 Cell
Flame Amplifiers: R7852
C7915A1028/U 48 in. (1219 mm) 1 1/4 in. diameter x 2 1/4 in. long
(32 mm diameter x 58 mm long)
-20°F to 125°F operating range
(-18°C to 52°C operating range)
With magnifying lens,
32007255-001 Cell, Orifice, heat
block, and reducer bushing
Flame Amplifiers: R7852
C7915A1036/U 96 in. (2438 mm) 1 1/4 in. diameter x 2 1/4 in. long
(32 mm diameter x 58 mm long)
-20°F to 125°F operating range
(-18°C to 52°C operating range)
With magnifying lens,
32007255-001 Cell
Flame Amplifiers: R7852
C7962 Visible Light Flame Detector
Dimensiions in inches (millimeters)
4 FOOT (1.2 METER)
LEADWIRES (2)
M20912
3-1/4 (82)
3-3/4 (95)
1
(25)
C7962B
The C7962B Visible Light Flame Detector detects the visible light
emitted by fuel oil combustion flames. The C7962B Detector is
used with Honeywell Flame Safeguard controls to provide fuel oil
flame supervision in commercial and industrial burners.
• Used with 7800 SERIES Flame Safeguard controls.
• Used with R7851B Flame Amplifier.
• Has an integral collar threaded (internal 1/2-14 NPSM) for mounting
on 1/2 inch sight pipe.
Type: Visible Light Flame Detector
Application: Commercial, industrial oil burners
NEMA Ratings: NEMA 1
Electrical Connections: 2 NEC Class 1 leadwires
Vibration: 0.5 G max
Mounting: 1/2 in NPT pipe mounting
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MP268
Approvals, CSA: Report 158158
Approvals, Swiss RE: Acceptable
Accessories:
32007439-001/U – Mounting Bracket and screws for C7962B (3/8 in.
NPT to 1/2 in. NPT)
Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With
C7962B1002/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm
diameter x 95 mm long)
-40°F to +160°F (-40°C to +71°C) Flame Amplifiers:
R7851B
C7962B1010/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm
diameter x 95 mm long)
-40°F to +160°F (-40°C to +71°C) 32007439-001
Mounting Bracket and
screws
Flame Amplifiers:
R7851B
810 70-6910
Flame Detectors
Optical Flame Detector Accessories or Parts
Material Number Description Used With
105172C/U Pressure Seal-off Adapter (3/4 NPT) w/UV Quartz window for C7012, C7024, C7027, C7061 C7012, C7024, C7027, C7061;
C7024; C7012; C7061
110634A/U Magnifying Lens Assembly for C7015A C7015
113228/U UV Sensing Tube (-20°F to 175°F) for C7012; C7024 C7012; C7024
114372/U Bulk Pack -20 PSI window for C7012E, F; C7024; C7061 C7024; C7012; C7061
114638/U Rubber Washer (Red) for C7012A, E; C7024A; C7061A; C7961A C7012; C7061; C7024
120739/U Flange Gasket for C7012, C7024, C7061 C7024; C7012; C7061
120930/1662/F Cover for C7012A,G, C7024E, C7061A, C7961E C7012A,G, C7024E, C7061A,
C7961E; C7012
120934-520/U Mounting Flange (3/4") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A,
C7961E
122748/U 50 PSI Quartz Window for C7012, C7061 C7012; C7061; C7024
124198/U Mounting Flange (1") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A,
C7961E
129464M/U UV Power Tube (0°F to 250°F) for C7035 C7035
129464N/U UV Power Tube (-40°F to 250°F) for C7035, C7061 C7061; C7035
129811B/U Socket Assembly w/NPT threads C7035
190971B/U 120 Vac Coil and Shutter Assembly for C7012E, F, C7061A, F C7012E, F; C7061A, F
190971D/F 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E
190971D/U 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E
190971F/U 100 Vac Coil and Shutter Assembly for C7076A, D C7076A, D
190971G/U 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961 C7024;C7961
190998A/U Aspiration assembly for C7076A C7076A
190999/U Grommet for C7076 Sensors C7076
191002D/U 220/240 Vac Plug in Electronics less UV Sensing Tube for C7076A C7076A
191002R/U 120 Vac Plug in Electronics less UV Sensing Tube for C7076D C7076D
191050/U Quartz Viewing Window for C7076 C7076
191053/U UV Sensing Tube for C7076 C7076
191054/U Housing Gasket for C7076 C7076
191203/0767/U Hinge for C7076A C7076
191284/U Aluminum Shield for C7035 C7035
191702/U Electronics less UV sensing tube for C7012F (120 Vac) C7012F
32004080-001/U 120 Vac Electronics less UV Sensing Tube and Shutter for C7012C C7012C
32004080-002/U 24 Vdc Plug in Electronics less UV Sensing Tube for C7024F C7024F
32007255-001/U Lead Sulfide Cell for C7915 C7915
32007439-001/U Mounting Bracket and screws for C7962B (3/8 in. NPT to 1/2 in. NPT) C7962B
390427B/U Envelope with Reducer bushing (1/2" to 3/8" NPT) C7027; C7015
50019469-001/U Magnifying Lens Assembly for C7915A C7915; C7015
70-6910 811
Commercial/Industrial
Combustion Controls
Pilot Burners
Q179A, B Flame Rectifier Gas Pilots
Q179A, B Gas Pilot Burner Assemblies use the flame rectification
principle to prove the flame. Q179A, B are used in conjunction
with a suitable electronic flame safeguard control on industrial or
commercial gas and gas pilot ignited oil burners.
• Q179A is a gas pilot assembly (with a flame electrode rod) and
ignition electrode, making it suitable for applications requiring an
interrupted or intermittent electrically ignited gas pilot burner.
• Q179B has only the flame electrode and is suitable for use in
continuous pilot applications.
• Primary aerated type burner is equipped with stainless steel fins that
provide the proper flame rod area to ground area ratio for maximum
flame signal and flame stabilization.
• Stainless steel electrode(s) are mounted in ceramic insulators, which
permit electrode adjustment.
• Rajah connectors facilitate disconnecting (A1126 has terminal
screws).
• Bracket permits side or end mounting.
Type of Gas: Natural gas; Gas consumption – 2.0 cfh (0.06 m3/hr)
Aeration: Primary
Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm
compression coupling
Mounting: side or end mount
Approximate, Dimensions: 4 5/8 in. high x 1 11/16 in. wide x 3 in.
deep (118 mm high x 43 mm wide x 76 mm deep)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2
Approvals, Factory Mutual: Approved: Report No. 22961
Material Number Application Orifice Wiring Terminal Type Tip Style Includes Used With
Q179A1001/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah I Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1035/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree right
hand
Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1050/U For Intermittent or
Interrupted Ignition
0.028 in. dia. (0.711 mm dia.) Rajah T Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1076/U For Intermittent or
Interrupted Ignition
0.028 in. dia. (0.711 mm dia.) Rajah 45 degree Y Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1092/U For Intermittent or
Interrupted Ignition
0.028 in. dia. (0.711 mm dia.) Rajah 45 degree T Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1118/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left
hand
Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1126/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Screw Terminal I Flame electrode and
ignition electrode
with screw terminal
connections
Q624 or other suitable
ignition transformer.
Q179A1183/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah I Ignition Electrode Only Q624 or other suitable
ignition transformer.
Q179B1042/U For Continuous
(Standing) pilot
0.025 in. dia. (0.635 mm dia.) Rajah T Flame electrode
Q179B1109/U For Continuous
(Standing) pilot
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left
hand
Flame electrode
Q179B1117/U For Continuous
(Standing) pilot
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree I Flame electrode
812 70-6910
Pilot Burners
Q179C, D Miniature Rectifier Pilots
Q179C, D Gas Pilot Burner Assemblies use the flame rectification
principle to prove the flame. Q179C, D are used in conjunction
with a suitable electronic flame safeguard control on industrial or
commercial gas and gas pilot ignited oil burners.
• Q179C is a gas pilot assembly (with a flame electrode rod) and
ignition electrode, making it suitable for applications requiring an
interrupted or intermittent electrically ignited gas pilot burner.
• Q179D has only the flame electrode and is suitable for use in
continuous pilot applications.
• Primary aerated type burner is equipped with stainless steel fins that
provide the proper flame rod area to ground area ratio for maximum
flame signal and flame stabilization.
• Stainless steel electrode(s) are mounted in ceramic insulators, which
permit electrode adjustment.
• Rajah connectors facilitate disconnecting.
Aeration: Primary
Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm
compression coupling
Wiring Terminal Type: Rajah
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MH9928, Guide No. MCUR2
Approvals, CSA: Certified: Master Report LR95329-1
Material
Number
Application Mounting Tip Style Orifice Approximate, Dimensions Includes Used With Type of
Gas
Q179C1009/U For Intermittent or
Interrupted Ignition
Dual Wing-
Rear
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1025/U For Intermittent or
Interrupted Ignition
Single Wing-
Rear
L 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1033/U For Intermittent or
Interrupted Ignition
Dual Wing-
Left Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1041/U For Intermittent or
Interrupted Ignition
Dual Wing-
Right Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1058/U For Intermittent or
Interrupted Ignition
Single Wing-
Left Side
L 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1066/U For Intermittent or
Interrupted Ignition
Single Wing-
Right Side
K 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1090/U For Intermittent or
Interrupted Ignition
Dual Wing-
Rear
D 0.016 in. dia.
(0.40 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
LP
Q179D1008/U For Continuous
(Standing) pilot
Dual Wing-
Rear
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
Q179D1016/U For Continuous
(Standing) pilot
Dual Wing-
Left Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
Q179D1024/U For Continuous
(Standing) pilot
Dual Wing-
Right Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
Q179D1057/U For Continuous
(Standing) pilot
Single Wing-
Left Side
L 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
70-6910 813
Commercial/Industrial
Combustion Controls
Pilot Burners
C7005 Flame Rectifier Pilots
Gas Pilot Burner Assemblies include a flame rod to prove the pilot
flame. The assemblies are used with a suitable flame safeguard
control on industrial or commercial gas burners or oil burners
with gas pilots.
• Used with Honeywell controls using the flame rectification principle.
• C7005A is for continuous pilot applications.
• It includes an insulated flame rod, properly positioned relative to
the flame retention type nozzle. C7005B is similar to C7005A, but
includes an ignition electrode suitable for automatic, electric-spark
ignition, gas pilot applications.
• Individually mounted flame rod and ignition electrode in ceramic
insulators allow the head assembly to fit inside a 3-inch pipe.
• Stainless steel fins on the flame retention type pilot head provide
the correct ratio of flame rod area to ground area for maximum flame
signal, and are beneficial in stabilizing the pilot flame.
• Pilot flame retention nozzle and mixing tube are threaded internally,
1/2-14 NPT and 3/8-18 NPT, respectively, and can be assembled
with standard pipe fittings.
• Pilot can be installed in vertical, horizontal, or inclined position.
• Rajah connectors facilitate electrical connections.
Connection Type: 1/2 in. NPT male thread Gas Fitting
Wiring Terminal Type: Rajah
Approximate, Dimensions: 3 in. diameter x 3 1/2 in. deep (76 mm
diameter x 343 mm deep)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2
Approvals, Factory Mutual: Approved: Report No. 24181.04
Approvals, Swiss RE: Acceptable
Material Number Application Orifice Includes Used With Type of Gas
C7005A1037/U For Continuous (Standing) pilot 0.052 in. dia. Natural
C7005B1035/U For automatic electrically ignited pilot 0.052 in. dia. Ignition electrode Q624 or other suitable ignition transformer. Natural
C7005B1050/U For automatic electrically ignited pilot 0.028 in. dia. (0.711 mm dia.) Ignition electrode Q624 or other suitable ignition transformer. LP
Commercial Pilot Burners Parts or Accessories
Material Number Description Used With
100204B/U This Natural Gas Venturi Mixing Tube is used for C7005A and B C7005A, C7005B
101738/U This Insulator for Flame rod or Igniter is used with C7005A and B C7005A, C7005B
101738A/U This Ignition Assembly, including; electrode, bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B
101738B/U This Flame Rod Assembly, including; Kanthal Electrode, Bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B
101739/U This 4 in. Kanthal Ignition Electrode is used for C7005A and B C7005A, C7005B
101741/0020/U This 7/8 in. long Rajah Connector, with plug end, is used for C7005A and B C7005A, C7005B
101742/0021/U This Electrode Mounting Clip is used for C7005A and B C7005A, C7005B
101743/U This Mounting Bracket is used for C7005A and B C7005A, C7005B
103534/U This 8 in. Kanthal flame electrode is used with C7005A and C7005B C7005A, C7005B
104312/U This Rajah Connector for Flame Electrode is used with Q179A and B Q179A, Q179B
131065/U 131065 Adapts Q340 Thermal Couple to Q179B with 102462. Sold in custom packs Q179A, Q179B
133451A/U This T Port or LH 90 degree Flame Rod and Insulator, is used for Q179A and B Q179A, Q179B
37356/520/U This Rajah connector for ignition electrodes is used with Q179A, Q179B, Q179C, or Q179D Q179A, Q179B, Q179C, Q179D
388146KD/U This 0.016 in. diameter, LP Gas Spud Orifice, is used for Q179C and D. Sold in bulk packs Q179C, Q179D
395390-13/U This LP gas, 0.013 in. diameter Orifice, is used for Q179A and B Q179A, Q179B
395390-28/U This Natural gas, 0.028 in. diameter Orifice, is used for Q179A and B Q179A, Q179B
R1061012/U This Ignition cable or Flame Rod Cable is rated at 350°F, 20,000 volts R.M.S. and used with C7005B, Q179A and Q179C C7005B, Q179A, Q179C
R1298020/U This Cable Flame Rod Lead, is rated at 400°F, 600 volts R.M.S., and used with Q179 Q179
814 70-6910
Ignition Transformers
Q624 Solid State Ignition Transformer
Used to ignite pilots on commercial or industrial gas burners.
• Ignite gas pilots with spark gaps up to 1/4 in. (6.5 mm).
• Reliable light off with 15,000 peak voltage.
• Prevent detection of the ignition spark when properly applied in a
flame detection system with the C7027, C7035 or C7044 Minipeeper
Ultraviolet Flame Detector.
• For use only in interrupted ignition applications.
• Mount in same space used by conventional ignition transformer.
• Light weight, 3 lbs. (1.4 kg) versus 8-1/2 lbs. (3.9 kg) for standard
transformers.
Temperature Range: -40°F to +125°F
Approximate, Dimensions: 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep
(171.5 mm high x 108 mm wide x 76 mm deep)
Weight lb. (kg): 3 lb (1.4 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized
Approvals, CSA: Certified: File No. LR95329
Operating Humidity Range (% RH): 95% RH
Accessories:
32004766-001/U – 24 inch Ignition Cable for Q624 and Q652
32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652
32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
32004766-004/U – 60 inch Ignition Cable with straight boots
32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot
32004766-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-001/U – 24 inch Ignition Cable for Q624 and Q652
50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652
50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
50060793-004/U – 60 inch Ignition Cable with straight boots
50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot
50060793-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-007/U – 36 inch ignition cable w/90 degree boot on one end
only
50060793-008/U – Ignition Cable w/90 degree boot on one end only
50060793-009/U – Ignition Cable w/90 degree boot on one end only
50060793-010/U – Ignition Cable w/90 degree boot on one end only
50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end
used with Q624 and Q652
50060793-012/U – 36 inch Ignition Cable with 90 degree boot and
1/4 in. spad terminal used with Q624 and Q652
Dimensions in inches (millimeters)
TERMINAL
BOARD
MOUNTING
PLATE
HIGH VOLTAGE
ELECTRODE
COVER SCREW
KNOCKOUT FOR
1/2 INCH CONDUIT
1-1/4
(32)
13/16
(20.5)
5-1/4 (133.5)
19/64
(7)
4-1/4
(108)
1-1/4
(32)
3 (76)
M20858
5-15/16 (151)
6-3/4 (171.5)
Material Number Application Voltage Frequency
Q624A1014/U Gas Ignition Transformer 120 Vac 50 Hz; 60 Hz
70-6910 815
Commercial/Industrial
Combustion Controls
Ignition Transformers
Q652 Solid State Spark Generator
Used to ignite gas burners in commercial and industrial
applications.
• Lightweight, 1 lb. (0.4 kg).
• Include single high voltage electrode for gas applications.
• For use with gas pilots with electrode spacings between 0.029 and
0.125 in.
• Secondary Peak Voltage: 14Kv rms at 21Khz.
• Mount in same space used by conventional ignition transformer.
• For use only in interrupted ignition applications.
• Prevent detection of the ignition spark when properly applied in a
flame detection system with the C7027, C7035 or C7044 Minipeeper
Ultraviolet Flame Detector.
Temperature Range: 14°F to 113°F
Approximate, Dimensions: 4 15/32 in. high x 2 15/16 in. wide x 2 9/32
in. deep (101.6 mm high x 77.5 mm wide x 58.4 mm deep)
Weight lb. (kg): 1 lb (0.45 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized
File MH14381
Approvals, CSA: LA66894
Operating Humidity Range (% RH): 90% RH
Accessories:
32004766-001/U – 24 inch Ignition Cable for Q624 and Q652
32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652
32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
32004766-004/U – 60 inch Ignition Cable with straight boots
32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot
32004766-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-001/U – 24 inch Ignition Cable for Q624 and Q652
50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652
50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
50060793-004/U – 60 inch Ignition Cable with straight boots
50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot
50060793-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-007/U – 36 inch ignition cable w/90 degree boot on one end
only
50060793-008/U – Ignition Cable w/90 degree boot on one end only
50060793-009/U – Ignition Cable w/90 degree boot on one end only
50060793-010/U – Ignition Cable w/90 degree boot on one end only
50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end
used with Q624 and Q652
50060793-012/U – 36 inch Ignition Cable with 90 degree boot and
1/4 in. spad terminal used with Q624 and Q652
Dimensions in inches (millimeters)
M20870B
2-25/32
(71)
2-7/8 (73) 2-9/32 (59)
19 IN. (483 MM)
LEAD WIRES
HIGH VOLTAGE
ELECTRODE
3-17/64 (83)
3-21/32 (95)
4-5/32 (106)
2-15/16
(78)
Material Number Application Voltage Frequency
Q652B1006/U Gas Ignition Transformer 120 Vac 60 Hz
Q652B1014/U Solid State Ignitor Spark Generator-Gas Applications; 220V 60 Hz 220 Vac 60 Hz
816 70-6910
Ignition Transformers
Ignition Transformer Accessories or Parts
Material Number Description Used With
134666/510/U High voltage terminal insulator for Q652 and Q624 Q652; Q624
32004766-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624
32004766-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624
32004766-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624
32004766-004/U 60 inch Ignition Cable with straight boots Q652; Q624
32004766-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624
32004766-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624
32004766-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624
32004766-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624
32004766-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624
32004766-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624
32004766-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624
32004766-012/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624
4074BTN/U Bag assembly consisting of washer (103218), cap terminal (135793) and ferrule (37356) for Q624 Q624A
50060793-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624
50060793-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624
50060793-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624
50060793-004/U 60 inch Ignition Cable with straight boots Q652; Q624
50060793-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624
50060793-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624
50060793-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624
50060793-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624
50060793-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624
50060793-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624
50060793-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624
50060793-012/U 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624
50060793-013/U 48 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624
70-6910 817
Commercial/Industrial
Combustion Controls
Firing Rate Motors and Linkages
M9484D, E, F; M9494D, F Modutrol® IV Motors
Reversing, proportional motors used to drive burner firing rate
valves, dampers or auxiliary equipment. Replaces M941A, C, D
motors.
• Designed for flame safeguard applications in commercial/industrial
oil or gas burner system.
• Vibration resistant electronic drive circuit.
• Regulated by three-wire proportional controller.
• Stroke is field-adjustable to 90 or 160 degrees.
Frequency: 50 Hz; 60 Hz
Stroke: Adjustable; 90 to 160 degrees, Symmetrical
Power Consumption: 15 W
Input Signal: 135 ohm
Shaft Dimensions: double-ended, 3/8 in. square (double-ended, 9.5
mm square)
Deadweight Load on Shaft: Either End – 200 lb (300 lb combined
power and auxiliary shafts); 90.8 kg (136 kg combined power and
auxiliary shafts)
Approximate, Dimensions: 6.45 in high x 5.5 in wide x 7.3 in deep
(164 mm high x 140 mm wide x 185 mm deep)
Ambient Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No. E4436,
Guide No. XAPX for USA and Canada
Supply Voltage: 24 Vac
Accessories:
Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly
Valve. Includes 10 3/4 inch Linkage Rod.
Material
Number
Torque
Rating
(lb-in.)
Torque
Rating
(Nm)
Additional
Torque Ratings
(lb-in.)
Additional
Torque Ratings
(Nm)
Internal
Auxiliary
Switch
Auxiliary
Switch
Setting
Auxiliary Switch
Ratings
Switch Ratings Timing Factory
Stroke
Setting
M9484D1010/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
160 degrees
M9484E1009/U 75 lb-in. 8.5 Nm Breakaway –
150 lb-in.
Breakaway –
17.0 Nm
1 11 degrees 120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 15 seconds,
160 degree stroke
– 30 seconds
90 degrees
M9484E1017/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
1 1 degree 120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484E1033/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
1 7 degrees 120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484F1007/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 7 and
80 degrees
120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484F1023/U 75 lb-in. 8.5 Nm Breakaway –
150 lb-in.
Breakaway –
17.0 Nm
2 At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 15 seconds,
160 degree stroke
– 30 seconds
90 degrees
818 70-6910
Firing Rate Motors and Linkages
Material
Number
Torque
Rating
(lb-in.)
Torque
Rating
(Nm)
Additional
Torque Ratings
(lb-in.)
Additional
Torque Ratings
(Nm)
Internal
Auxiliary
Switch
Auxiliary
Switch
Setting
Auxiliary Switch
Ratings
Switch Ratings Timing Factory
Stroke
Setting
M9484F1031/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 7 and
80 degrees
120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484F1049/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 35 and
120 degrees
120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
160 degrees
M9484F1057/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 53 seconds
M9494D1000/U 300 lb-in. 34 Nm Breakaway –
600 lb-in.
Breakaway –
68.0 Nm
At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 60 seconds,
160 degree stroke
– 120 seconds
90 degrees
M9494F1003/U 300 lb-in. 34 Nm Breakaway –
600 lb-in.
Breakaway –
68.0 Nm
2 At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 60 seconds,
160 degree stroke
– 107 seconds
90 degrees
Q100 Butterfly Valve Linkages
Connects V51E valve to M9484 and M9494 Modutrol IV Motors with
adapter plate.
• Fits all sizes of V51E Valves. Mounts easily.
Material Number Linkage Type Used with Actuator Includes Used With
Q100B1006/U Butterfly Gas Valve Modutrol Motor 10 3/4 in. Linkage Rod all sizes V51E Gas Valve
70-6910 819
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V48A; V88A Diaphragm Gas Valves
Dimensions in inches (millimeters)
1
2
1
2
BLEED TAPPING: 1/8-27 NPT.
PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT
FOR 2 THROUGH 3 IN. SIZES.
M8487A
E
C
A
B D
F
APPROXIMATE DIMENSIONS
VALVE
SIZE
(IN.)
A B C D E F
IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4-11/16
5-1/16
5-9/16
5-9/16
6-15/16
6-15/16
6-15/16
119.1
128.6
141.3
141.3
176.2
176.2
176.2
3/4
1
1-1/4
1-1/4
2-1/4
2-1/4
2-1/4
19.1
25.4
31.8
31.8
57.2
57.2
57.2
4-5/8
5
5-7/8
5-7/8
9-1/2
9-1/2
9-1/2
117.5
127.0
149.2
149.2
241.3
241.3
241.3
3-1/2
3-11/16
5-5/16
5-5/16
8-3/8
8-3/8
8-3/8
88.9
93.7
134.9
134.9
212.7
212.7
212.7
1-5/8
2-1/16
2-3/8
2-3/8
3-9/16
3-9/16
3-9/16
41.3
52.4
60.3
60.3
90.5
90.5
90.5
3-13/16
4-5/16
5-5/16
5-5/16
5-5/16
9-5/16
9-5/16
96.8
109.5
134.9
134.9
236.5
236.5
236.5
1-13/16
(46)
3-11/16
(94)
Solenoid-operated diaphragm valves provide slow opening and
fast closing suitable for controlling natural, LP or manufactured
gases. They are normally used on atmospheric boilers,
commercial water heaters, and rooftop heaters.
• V48 for line voltage service; V88 for 24 Vac service.
• Close firmly with diaphragm that is both weight and spring loaded.
• Two second maximum closing time.
• Valve closes on power failure; recommended for final shutoff service.
• Set opening time with various sized bleed orifices or adjustable
bleed valve.
• Use with LP, natural or manufactured gases.
• Made with cast aluminum in straight-through valve pattern.
• Valve position indicator available for 1-1/4 in. V48A2227.
Type of Fuel: Natural; LP; Manufactured
Bleed Tapping: 1/8-27 NPT
Body Pattern: Straight-through
Valve Opening Time: 5 sec max
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Power Consumption: 9 W; 15 VA max
Electrical Connections: 6 in. Leadwires
Operating Temperature Range: 32°F to 125°F (0°C to 52°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ
Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5)
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Pilot Tapping Voltage Approximate, Dimensions Pressure
Rating
(psi)
Pressure
Rating
(kPa)
Current Ratings Comments Includes
V48A2151/U 3/4 in. DN20 1/8-27 NPT 120 Vac 5 7/16 in. high x 3 13/16 in. wide
x 4 5/8 in. deep (138 mm high x
97 mm wide x 118 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2169/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2177/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2185/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2227/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Includes position
indicator
Ground
terminal
V48A2243/U 2 in. DN50 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2250/U 2 1/2 in. DN65 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
820 70-6910
Diaphragm Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Pilot Tapping Voltage Approximate, Dimensions Pressure
Rating
(psi)
Pressure
Rating
(kPa)
Current Ratings Comments Includes
V48A2268/U 3 in. DN80 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2276/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2334/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2342/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V88A1618/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1626/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1634/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1659/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide
x 4 5/8 in. deep (138 mm high x
97 mm wide x 118 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1667/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide
x 4 5/8 in. deep (138 mm high x
97 mm wide x 118 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1675/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1683/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1691/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1709/U 2 in. DN50 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1717/U 2 1/2 in. DN65 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
70-6910 821
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V48J; V88J High Temperature Diaphragm Gas Valves
Dimensions in inches (millimeters)
1
2
1
2
BLEED TAPPING: 1/8-27 NPT.
PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT
FOR 2 THROUGH 3 IN. SIZES.
M8487A
E
C
A
B D
F
APPROXIMATE DIMENSIONS
VALVE
SIZE
(IN.)
A B C D E F
IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4-11/16
5-1/16
5-9/16
5-9/16
6-15/16
6-15/16
6-15/16
119.1
128.6
141.3
141.3
176.2
176.2
176.2
3/4
1
1-1/4
1-1/4
2-1/4
2-1/4
2-1/4
19.1
25.4
31.8
31.8
57.2
57.2
57.2
4-5/8
5
5-7/8
5-7/8
9-1/2
9-1/2
9-1/2
117.5
127.0
149.2
149.2
241.3
241.3
241.3
3-1/2
3-11/16
5-5/16
5-5/16
8-3/8
8-3/8
8-3/8
88.9
93.7
134.9
134.9
212.7
212.7
212.7
1-5/8
2-1/16
2-3/8
2-3/8
3-9/16
3-9/16
3-9/16
41.3
52.4
60.3
60.3
90.5
90.5
90.5
3-13/16
4-5/16
5-5/16
5-5/16
5-5/16
9-5/16
9-5/16
96.8
109.5
134.9
134.9
236.5
236.5
236.5
1-13/16
(46)
3-11/16
(94)
Solenoid-operated diaphragm valves provide slow opening and
fast closing suitable for controlling natural, LP or manufactured
gases. They are normally used on atmospheric boilers,
commercial water heaters, and rooftop heaters.
• Rated for 150°F (66°C) maximum temperature applications.
• V48 for line voltage service; V88 for 24 Vac service.
• Close firmly with diaphragm that is both weight and spring loaded.
• Two second maximum closing time.
• Valve closes on power failure; recommended for final shutoff service.
• Set opening time with various sized bleed orifices or adjustable
bleed valve.
• Use with LP, natural or manufactured gases.
• Made with cast aluminum in straight-through valve pattern.
Type of Fuel: Natural; LP; Manufactured
Bleed Tapping: 1/8-27 NPT
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through
Valve Opening Time: 5 sec max
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Electrical Connections: 6 in. Leadwires
Operating Temperature Range: 32°F to 150°F (0°C to 66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ
Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5)
Pressure Ratings (psi): 1 psi
Pressure Ratings (kPa): 6.9 kPa
Current Ratings: 0.62 max amps at rated Vac/Hz
Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption
V88J1006/U 1 in. DN25 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm
high x 127 mm wide x 109 mm deep)
9 W; 15 VA max
V88J1022/U 1 1/4 in. DN32 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep
(173 mm high x 135 mm wide x 149 mm deep)
9 W; 15 VA max
822 70-6910
Diaphragm Gas Valves
V4943/V8943A On/Off Diaphragm Gas Valves
V4943A/V8943A are on/off diaphragm gas valve used on boilers,
unit heaters, duct furnaces, makeup air and rooftop heaters.
• Designed for replacement for V4843A/V8843A Gas Valves.
• Suitable for use on atmospheric boilers, commercial water heaters,
and rooftop heaters.
• V8943A/V4943A models are solenoid-operated diaphragm valves for
on/off flow control of natural or LP gas.
• Valve body of die-cast aluminum with a straight-through pattern.
• V4943 are used with line voltage, on/off controllers; V8943A are
used with 24 Vac thermostats or controllers.
• Valve closes on power failure; recommended for final shutoff service.
Type of Fuel: Natural; LP
Bleed Tapping: Internal Bleed
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through, non-offset
Opening Characteristics: Rapid Opening On-Off
Valve Opening Time: 6 sec max
Valve Closing Time: 3 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Electrical Connections: 1/4 in. (6 mm) spade terminals (quick
connects). 30 in. (762 mm) leadwires and cover for electrical conduit
connection provided.
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ (60 Hz only)
Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3371-03,
83 (Z21.21, Z21.78)
Pressure Ratings (psi): 1/2 psi
Pressure Ratings (kPa): 3.4 kPa
Comments: (2) 30" leadwires
Current Ratings: 0.055 max amps at rated Vac/Hz
Dimensions in inches (millimeters)
6-9/16 (167)
FOR 1, 1-1/4
OR
7-3/8 (187)
FOR 1-1/2, 2
SIDE VIEW
6 (152)
6
(152)
TOP VIEW
M23232
VENT CONNECTIONS
(V4944/V8944 HAVE TWO)
Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption
V4943A1011/U 1 in. DN25 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
6 VA max
V4943A1029/U 1 1/4 in. DN32 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
6 VA max
V4943A1037/U 1 1/2 in. DN40 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
6 VA max
V4943A1045/U 2 in. DN50 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
6 VA max
V8943A1012/U 1 in. DN25 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
8 VA max
V8943A1020/U 1 1/4 in. DN32 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
8 VA max
V8943A1038/U 1 1/2 in. DN40 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
8 VA max
V8943A1046/U 2 in. DN50 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
8 VA max
70-6910 823
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V4943/V8943B, C, N Single Stage Pressure Regulating Valves
V4943B, N/8943B, C, N are Single-stage Pressure Regulating
Valves. These valves are used on boilers, unit heaters, duct
furnaces, makeup air and rooftop heaters.
• Designed for replacement for V4843/V8843 Gas Valves.
• Suitable for use on atmospheric boilers, commercial water heaters,
and rooftop heaters.
• V4943/V8943B, C, N models are solenoid-operated diaphragm
valves that combine the functions of safety shutoff and pressure
regulation in a single unit.
• V4943/V8943B, N are for use with natural gas.
• V4943/V8943C are for use with LP gas.
• Valve body of die-cast aluminum with a straight-through pattern.
• V4943 are used with line voltage, on/off controllers; V8943 are used
with 24 Vac thermostats or controllers.
• Valve closes on power failure; recommended for final shutoff service.
Bleed Tapping: 5/16-24 UNF
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through, non-offset
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Electrical Connections: 1/4 in. (6 mm) spade terminals (quick
connects). 30 in. (762 mm) leadwires and cover for electrical conduit
connection provided.
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ (60 Hz only)
Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01,
81 (Z21.21, Z21.78)
Pressure Ratings (psi): 1/2 psi
Pressure Ratings (kPa): 3.4 kPa
Comments: (2) 30" leadwires
Dimensions in inches (millimeter)
6-9/16 (167)
FOR 1, 1-1/4
OR
7-3/8 (187)
FOR 1-1/2, 2
SIDE VIEW
6 (152)
6
(152)
TOP VIEW
M23232
VENT CONNECTIONS
(V4944/V8944 HAVE TWO)
Material
Number
Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Voltage Approximate, Dimensions Valve
Opening
Time
Current
Ratings
Pressure Regulator
Setpoint (in. wc)
Power
Consumption
V4943B1019/U Natural 1 in. DN25 Slow Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max;
6.6 VA
V4943B1027/U Natural 1 1/4 in. DN32 Slow Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943B1035/U Natural 1 1/2 in. DN40 Slow Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943B1043/U Natural 2 in. DN50 Slow Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943N1012/U Natural 1 in. DN25 Rapid Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943N1020/U Natural 1 1/4 in. DN32 Rapid Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
824 70-6910
Diaphragm Gas Valves
Material
Number
Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Voltage Approximate, Dimensions Valve
Opening
Time
Current
Ratings
Pressure Regulator
Setpoint (in. wc)
Power
Consumption
V4943N1038/U Natural 1 1/2 in. DN40 Rapid Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943N1046/U Natural 2 in. DN50 Rapid Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V8943B1010/U Natural 1 in. DN25 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943B1028/U Natural 1 1/4 in. DN32 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943B1036/U Natural 1 1/2 in. DN40 Slow Opening
1-stage
24 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943B1044/U Natural 2 in. DN50 Slow Opening
1-stage
24 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943C1018/U LP 1 in. DN25 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High
Fire – 8.8 in. wc to
11.5 in. wc; Factory
Setting, High Fire –
10.0 in. wc
9 VA max
V8943C1026/U LP 1 1/4 in. DN32 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High
Fire – 8.8 in. wc to
11.5 in. wc; Factory
Setting, High Fire –
10.0 in. wc
9 VA max
V8943N1013/U Natural 1 in. DN25 Rapid Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943N1021/U Natural 1 1/4 in. DN32 Rapid Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943N1039/U Natural 1 1/2 in. DN40 Rapid Opening
1-stage
24 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
70-6910 825
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V4944/V8944B, C, L, N Two Stage Pressure Regulating Gas Valves
V4944B, L, N/8944B, C, L, N are Two-stage Pressure Regulating
Gas Valves. These valves are used on boilers, unit heaters, duct
furnaces, makeup air and rooftop heaters.
• Designed for replacement for V4844/V8844 Gas Valves.
• Suitable for use on atmospheric boilers, commercial water heaters,
and rooftop heaters.
• V4944/V8944B, C, L, N models are solenoid-operated diaphragm
valves that combine the functions of safety shutoff and pressure
regulation in a single unit.
• V4944/V8944B, N are for use with natural gas.
• V4944/V8944C, L are for use with LP gas.
• Valve body of die-cast aluminum with a straight-through pattern.
• V4944 are used with line voltage, dual-stage controllers; V8944 are
used with 24 Vac dual-stage thermostats or controllers.
• Valve closes on power failure; recommended for final shutoff service.
Bleed Tapping: Two 5/16-24 UNF
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through, non-offset
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Voltage: V4944-120 Vac; V8944-24 Vac
Frequency: 60 Hz
Power Consumption: V4944-9 VA max; V8944-12.4 VA max
Electrical Connections: 1/4 in. (6 mm) spade terminals (quick
connects), leadwires and cover for electrical conduit connection
provided.
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ (60 Hz only)
Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01,
81 (Z21.21, Z21.78)
Pressure Ratings (psi): 1/2 psi
Pressure Ratings (kPa): 3.4 kPa
Current Ratings: V4944-0.077 max amps at rated Vac/Hz;
V8944-0.516 max amps at rated Vac/Hz
Dimensions in inches (millimeter)
6-9/16 (167)
FOR 1, 1-1/4
OR
7-3/8 (187)
FOR 1-1/2, 2
SIDE VIEW
6 (152)
6
(152)
TOP VIEW
M23232
VENT CONNECTIONS
(V4944/V8944 HAVE TWO)
Material Number Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Valve
Opening Time
Pressure Regulator Setpoint (in. wc) Comments
V4944B1018/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944B1026/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944B1059/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.7 in. wc; Factory
Setting, High Fire – 3.0 in. wc
(3) 30" leadwires
V4944B1075/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.6 in. wc; Factory
Setting, High Fire – 3.5 in. wc
V4944B1091/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.6 in. wc; Factory
Setting, High Fire – 3.5 in. wc
V4944L1024/U LP 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
826 70-6910
Diaphragm Gas Valves
Material Number Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Valve
Opening Time
Pressure Regulator Setpoint (in. wc) Comments
V4944N1011/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1029/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1037/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1045/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1060/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.0 in. wc; Factory
Setting, High Fire – 3.0 in. wc
(3) 85" leadwires
V8944B1019/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944B1027/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944B1035/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944B1043/U Natural 2 in. DN50 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944C1017/U LP 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
V8944C1025/U LP 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
V8944C1033/U LP 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
V8944N1012/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1020/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1038/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1046/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1053/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.2 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1061/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.2 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
70-6910 827
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
Diaphragm Gas Valve Replacement Parts or Accessories
Material Number Description Used With
116930/U 24 Vac, 60 Hz Replacement Coil for V88A Solenoid Operated Valve V88A
116931/U 120 V/60 Hz Replacement Coil for V48A Solenoid Operated Valve V48; V48A
116932/U 220-240 V/50-60 Hz Replacement Coil for V48A Solenoid Operated Valve V48A
118888/U 24V 60 Hz Replacement Coil for V88J V88J
122160/U Orifice - .018" for V48, V88 V48, V88
124674/U Orifice - .011" for V48, V88 V48, V88
126590/U Adjustable Bleed Valve Assembly for V48, V88, V4004. V8004. 1/8 in. NPT to
1/4 in. compression fitting
V48, V88
204480/U Regulator vent pipe fitting to be used with V4843/V8843B, C, L, N and V4844/
V8844B, C, L, N and V4943/V8943, V4944/V8944
V4843B; V4843C; V4843L; V4843N; V8843B; V8843C; V8843L;
V8843N; V4844B; V4844C; V4844L; V4844N; V8844B; V8844C;
V8844L; V8844N; V4943; V8943; V4944; V8944
828 70-6910
Butterfly Gas Valves
V51 Butterfly Gas/Air Valve
Provides modulating control of natural, manufactured, LP gases
or air.
• Use in commercial and industrial installations where large amounts
of gas must be closely controlled.
• NOT for use as safety shutoff valve.
• Adaptable to most modulating jobs.
• Modutrol motor, such as the M9484 or M9494, may be mounted
directly on valve or close to it.
• Valve mechanism has strain release.
• Adjustable stroke over low fire-high fire range.
• Straight-through valve pattern.
• Rugged cast aluminum body provides durability and maintenancefree
operation.
Type of Fuel: Air; natural; manufactured; LP
Body Pattern: Straight-through
Mounting: Motor shaft horizontal
Materials: Body – Aluminum
Operating Temperature Range: 32°F to 140°F (0°C to 60°C)
Approvals, Underwriters Laboratories Inc.: File No. MH5968 Vol. 1
Sec. 1, Guide no. MHKZ
Pressure Ratings (psi): 5 psi
Pressure Ratings (kPa): 34.5 kPa
Used With: Mod Motor with Q100 Linkage
Accessories:
32003396-001/U – V51E mounting kit for 1-1/2 and 2 in. valve actuators
includes brackets and hardware
32003396-002/U – V51E mounting kit for 2-1/2, 3 and 4 in. valve
actuators includes brackets and hardware
Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly
Valve. Includes 10 3/4 inch Linkage Rod.
Dimensions in inches (millimeter)
VALVE
SIZE (in.)
1 1/2
2
2 1/2
3
4
2 21/32
3 5/32
3 27/32
4 1/32
5 21/64
67.5
80.2
97.6
102.4
135.3
A
A
1
in. mm
1 9/16
1 13/16
2 5/16
2 25/64
3 5/32
39.7
46.0
58.7
60.7
80.2
B
B
in. mm
4 1/4
4 1/4
4 13/16
5
5 3/8
108.0
108.0
122.2
127.0
136.5
C
C
in. mm
3 1/32
3 17/32
4 23/32
4 23/32
5 17/64
77.0
89.7
119.9
119.9
133.8
D
D
in. mm
M9532A
1 2 1
1 MAXIMUM DIMENSIONS.
2 NOMINAL DIMENSIONS.
V51E DIMENSIONS
Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Pressure Tapping Approximate, Dimensions
V51E1000/U 1 1/2 in. DN40 4200 cfh 118.9 m3/hr Inlet and outlet pressure
taps – Two downstream
1/4 in. NPT taps
2 11/16 in. high x 3 1/16 in. wide x 5 13/16 in.
deep (68 mm high x 77 mm wide x 148 mm deep)
V51E1018/U 2 in. DN50 9210 cfh 260.7 m3/hr 3 3/16 in. high x 3 9/16 in. wide x 6 1/16 in. deep
(80 mm high x 90 mm wide x 154 mm deep)
V51E1034/U 2 1/2 in. DN65 8390 cfh 199.8 m3/hr 3 7/8 in. high x 4 3/4 in. wide x 7 1/8 in. deep
(98 mm high x 120 mm wide x 181 mm deep)
V51E1059/U 3 in. DN80 14640 cfh 414.5 m3/hr 4 1/16 in. high x 4 3/4 in. wide x 7 3/8 in. deep
(102 mm high x 120 mm wide x 188 mm deep)
V51E1075/U 4 in. DN100 33000 cfh 934.2 m3/hr 5 3/8 in. high x 5 1/4 in. wide x 8 9/16 in. deep
(135 mm high x 134 mm wide x 217 mm deep)
70-6910 829
Commercial/Industrial
Combustion Controls
Butterfly Gas Valves
V5197 Integrated Valve Train Butterfly Gas Valve
Dimensions in inches (millimeters)
10-5/16
(277)
4-27/32 (123)
6-7/16 (165)
2-1/2 (64)
7-1/8
(181)
3-25/32
(96)
M17528
The V5197A valve provides flow control of air, natural gas, liquid
petroleum, & manufactured gases which require a high turn down
ratio. The adjustment screw controls the maximum flow of gas, but
keeps the linear modulating characteristics & stroke.
• Used with air, natural, manufactured or liquefied petroleum (LP)
gases.
• For modulating applications that do not require final shutoff service
of firing rate valve.
• Two valve body types (small and large) applicable to seven pipe
sizes: Small body type for 3/4 in. (19 mm), 1 in. (25 mm), 1-1/4 in.
(32 mm), 1-1/2 in. (38 mm) and 2 in. (51 mm) pipes, NPT or ISO 7
threads. Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm) and 3
in. (76 mm) pipes, NPT or ISO 7 threads.
• Two downstream 1/4 in. NPT threaded pressure taps available.
• Accepts C6097 Pressure Switch mounted directly to flange
(downstream pressure tap only).
• Unpainted cast aluminum body.
• Suitable for electric or pneumatic operators with the appropriate
linkage.
• May be used with manufacturers own linkage and drive motor.
• Flow adjustment screw on bottom of valve controls maximum flow.
• Visual position indicator.
Type of Fuel: Air; natural; manufactured; LP
Pressure Tapping: Inlet and outlet pressure taps – Two downstream
1/4 in. NPT taps
Mounting: Directly bolted to Integrated Valve Train (IVT) components
or IVT adapters
Materials: Body – Die-cast aluminum
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: Component Listed
Approvals, CSA: Design Certified
Approvals, Swiss RE: Acceptable
Pressure Ratings (psi): 15 psi max
Pressure Ratings (kPa): 1 Bar
Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions
V5197A1003 3/4 in.; 1 in.; 1 1/4 in.;
1 1/2 in.; 2 in.
DN20; DN25; DN32;
DN40; DN50
2450 cfh for 3/4 in.;
3080 cfh for 1 in.;
4430 cfh for 1 1/4 in.;
5010 cfh for 1 1/2 in.;
5480 cfh for 2 in.
51 mm is 155/
38 mm is 142/
32 mm is 125/
25 mm is 87/
19 mm is 69
10 5/16 in. high x 6 7/16 in. wide x 7 11/32 in. deep
(277 mm high x 165 mm wide x 187 mm deep)
V5197A1011 2 in.; 2 1/2 in.; 3 in. DN65; DN80; DN50 12,600 cfh for 2 in.;
14,800 cfh for 2 1/2
in.; 16,900 cfh for 3 in.
76 mm is 478/
64 mm is 419/
51 mm is 356
12 11/16 in. high x 9 1/4 in. wide x 8 13/16 in. deep
(322 mm high x 235 mm wide x 224 mm deep)
Firing Rate Gas Valve Parts
Material Number Description Used With
49084/0021/U Adjusting arm for V51E. V51E
49085B/U Strain Release Assembly V51E
830 70-6910
Gas Valve Actuators
Selection Chart: V5055 and V5097 Industrial Gas Valves with V4055,
V4062 or V9055 Fluid Power Actuators
The chart below describes every model of V5055 or V5097 Valve in
the left column, and every model of Fluid Power Actuator across the
top. While it’s possible to combine any valve with any actuator, we’ve
marked the recommended valve/actuator combinations which cover
most applications with a •.
Each valve described in the left column is available:
• In these sizes: 3/4 to 3 in. (NPT or parallel BSP). V5055A, B, C are
also available in 4 in. size (flange connection only).
• With upstream and/or downstream tap.
Options available on some Fluid Power Actuators include:
• Damper arm shaft, with or without spring return.
• NEMA 4 enclosure.
• Fast or slow open time (13 or 26 seconds).
• Auxiliary switch.
• Valve seal overtravel interlock switch.
For complete specifications and ordering information on V5055 and
V5097 Valves and V4055, V4062 and V9055 Fluid Power Actuators,
refer to Index for specific page numbers.
Fluid Power Actuators/ Industrial Gas Valves Standard pressurea High Pressurea
V5055A, Fb, V5097A V5055B, V5097B V5055C, V5097C V5055D, V5097D V5055E, V5097E
Type Model Pressure Ratinga On-Off Characterized Guidec VSOId On-Off VSOId
V4055
On-Off
A, Ge Standard • • •
B High • f • f •
Dd Fd e Standard • •
Ed High • f •
V4062
Hi-Lo-Off
A Standard • •
B High • f • f •
Dd Standard •
V9055
Modulating
A Standard •
Dd Standard •
a Refer to the table below for actual pressure ratings of the various
combinations of valves and actuators.
b V5055F models meet EN161 leakage requirements.
c Characterized guide provides a more linear relationship between stem
travel and gas flow. Check Honeywell form 70-8311 to verify that flow
curve characteristics match application requirements.
d Valve Seal Overtravel Interlock. Valve has two shutoff seals, actuator has
a proof-of-closure switch.
e V4055F, G models include switch for manual control.
f These combinations have higher pressure ratings; see the table below.
The following combinations of V5055 and V5097 Valves, and V4055, V4062 and V9055 Fluid Power Actuators are approved by these agencies.
Underwriters Laboratories, Inc: Listed: MH1639
V4055A/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055B/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055E/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055F/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.).
V4055G/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.).
V4062A, D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V9055A, D/V5055A, B, C, E (3/4-4 in.) or V5097A-E (3/4-3 in.).
Factory Mutual Approved: Report No. 20698, 20835, 21172 and
24061:
Valve Actuator Approvals:
V4055A/V5055A and V5097A.
V4055D/V5055C and V5097C.
V4055A/V5055B and V5097B.
V4055B/V5055D and V5097D.
V4055E/V5055E and V5097E.
V4055F/V5055Ca and V5097C.
V4055G/V5055A, Ba and V5097A, B.
V9055A/V5055B, C and V5097B, C.
a Manual reset safety shut-off valves.
Pressure Ratings of Valve-Actuator Combinations
Model Pipe Size Standard Pressure Actuators
V4055A, D, F, G, V4062A, D, V9055A, D
High Pressure Actuators
V4O55B, E, V4062B
M.O.P.D. a Max. Rated Pressure b M.O.P.D. a Max. Rated Pressure b
Standard Pressure
Valves V5055A, B, C,
F, V5097A, B, C
3/4" to 1-1/2" c 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar
2" to 3" d 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar
4" flanged e 3 PSI 207 mbar 15 PSI 1.0 Bar 5 PSI 340 mbar 15 PSI 1.0 Bar
High Pressure Valves
V5055D, E, V5097D, E
3/4" to 1-1/2" c 5 PSI 340 mbar 75 PSI 5.0 Bar 25 PSI 1720 mbar 75 PSI 5.0 Bar
2" to 3" d 5 PSI 340 mbar 45 PSI 3.0 Bar 15 PSI 1030 mbar 45 PSI 3.0 Bar
a Max Operating Pressure Differential (UL) or Max Operating Pressure
(CSA); maximum allowable pressure drop from inlet to outlet for proper
operation.
b Max Rated Pressure (UL) or Max Close-off Pressure (CSA); maximum
pressure that the valve can be exposed to without leakage or damage to
the valve.
c Applies for small-body V5097 valves 3/4” up to 2” pipe size.
d Applies for large-body V5097 valves 2” up to 3” pipe size.
e V5055A, B, C only.
70-6910 831
Commercial/Industrial
Combustion Controls
Gas Valve Actuators
V4055A, B, D, E On-Off Fluid Power Gas Valve Actuator
Use in combination with V5055 or V5097 Gas Valves to control gas
supply to commercial and industrial burners.
• Use where smooth light off is important.
• One-second maximum closing time.
• Continuously displays the valve position with a red indicator when
open and a yellow indicator when closed.
• Mount in any position directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Operating Temperature Ratings: 60 Hz Models: -40°F to +150°F
(-40°C to +66°C). 50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to
+70°C).
Contact Ratings: V4055D, E ONLY-Proof of Closure (Factory Mutual)
Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp
Used With: V5055; V5097 Gas Valves
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with
V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No.
MH1639 Guide No. YIOZ
Approvals, Factory Mutual: V4055A-When used with the V5055A,
B or V5097A, B: Approved, Report Nos. 20698, 20835, 21172, and
24061; V4055B, D, E-When used with the V5055D or V5097D:
Approved, Report Nos. 20698, 20835, 21172, and 24061
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Dimensions in inches (millimeters)
B
A
1
1
(32.5)
KNOCKOUT
FOR 1/2 INCH
CONDUIT (4)
5 (127.0)
1-9/32
27/32
(21.4)
3-23/32
(94.5)
6-3/4 (171.5)
ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL.
M10981A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4

283
283
283
283
298
298
298

2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8

70
70
70
70
86
86
86

DIM A
V5055 V5097
IN. MM
DIM B
IN. MM
DIM A
IN. MM
DIM B
IN. MM
VALVE VALVE
Material
Number
Electrical
Ratings
Frequency Timing Internal
Auxiliary Switch
Maximum
Safe Operating
Pressure (psi)
Maximum
Safe Operating
Pressure (kPa)
Auxiliary Switch
Ratings
Comments Includes
V4055A1007/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa
V4055A1031/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa
V4055A1064/U 120 Vac 50 Hz; 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1080/U 240 Vac 50 Hz; 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1098/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1114/U 240 Vac 50 Hz; 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1296/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
Yes - adjusted to
90% stroke
5 psi 34 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
V4055A1304/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
with return
spring installed
V4055A1312/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Nema 4
Enclosure
V4055B1021/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Damper Shaft
V4055B1039/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Damper Shaft
832 70-6910
Gas Valve Actuators
Material
Number
Electrical
Ratings
Frequency Timing Internal
Auxiliary Switch
Maximum
Safe Operating
Pressure (psi)
Maximum
Safe Operating
Pressure (kPa)
Auxiliary Switch
Ratings
Comments Includes
V4055B1088/U 220 Vac 50 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa
V4055D1001/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055D1019/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055D1027/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
Yes 5 psi 34 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
Nema 4
Enclosure
V4055D1035/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
Yes 5 psi 34 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
V4055D1043/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa
V4055E1016/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Damper Shaft
V4055E1024/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
Yes 15 or 25 psi 103 or 172 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
Nema 4
Enclosure
Damper Shaft
V4055E1040/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Nema 4
Enclosure
Damper Shaft
70-6910 833
Commercial/Industrial
Combustion Controls
Gas Valve Actuators
V4055F, G Manual Reset Safety Shut-off Gas Valve Actuators
Provide manual reset, safety shut-off functions as required on FM,
IHEA-IRI and NFPA 86A,B,C industrial furnaces, ovens and kilns.
Use with V5055 or V5097 Gas Valves to control gas supply.
• Close in one second maximum.
• Continuously displays the valve position with a red indicator when
closed.
• Mount directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Frequency: 60 Hz
Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with
V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No.
MH1639 Guide No. YIOZ
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Dimensions in inches (millimeters)
B
A
1
1
(32.5)
KNOCKOUT
FOR 1/2 INCH
CONDUIT (4)
5 (127.0)
1-9/32
27/32
(21.4)
3-23/32
(94.5)
6-3/4 (171.5)
ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL.
M10981A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4

283
283
283
283
298
298
298

2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8

70
70
70
70
86
86
86

DIM A
V5055 V5097
IN. MM
DIM B
IN. MM
DIM A
IN. MM
DIM B
IN. MM
VALVE VALVE
Material
Number
Electrical
Ratings
Internal
Auxiliary
Switch
Timing Maximum
Safe
Operating
Pressure
(psi)
Maximum
Safe
Operating
Pressure
(kPa)
Contact Ratings Description Approvals, Factory
Mutual
Used With
V4055F1006/U 120 Vac No Opening – 13 sec;
Closing – < 1 sec
5 psi 34 kPa Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2
hp; 4.9 AFL, 29.4
ALR, 1/2 hp
Manual reset safety
shutoff valve with
proof of closure
switch.
When used with the
V5055D or V5097D:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
V4055G1004/U 120 Vac No Opening – 13 sec;
Closing – < 1 sec
5 psi 34 kPa Manual ON-OFF
actuator normally used
with V5055/V5907A,
B valve bodies. Low
pressure.
When used with
the V5055A, B
or V5097A, B:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
834 70-6910
Gas Valve Actuators
V4062 Off-Lo-Hi Fluid Power Gas Valve Actuators
Use with V5055 or V5097 Gas Valves to control gas supply for
commercial and industrial burners. Valve opens to low fire
position when power is applied; valve opens all the way on
demand.
• Provide final safety shutoff service when used with V5055 or V5097
gas valve.
• One-second maximum closing time.
• Continuously displays the valve position with a red indicator when
open and a yellow indicator when closed.
• Mount in any position directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Electrical Ratings: 120 Vac
Frequency: 60 Hz
Maximum Safe Operating Pressure (psi): 5 psi
Maximum Safe Operating Pressure (kPa): 34 kPa
Temperature Range: -40°F to +150°F (-40°C to +66°C)
Used With: V5034; V5055; V5097; VE5000
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with
V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No.
MH1639 Guide No. YIOZ
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Dimensions in inches (millimeters)
B
A
1
1
(32.5)
KNOCKOUT
FOR 1/2 INCH
CONDUIT (4)
5 (127.0)
1-9/32
27/32
(21.4)
3-23/32
(94.5)
6-3/4 (171.5)
ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL.
M10981A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4

283
283
283
283
298
298
298

2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8

70
70
70
70
86
86
86

DIM A
V5055 V5097
IN. MM
DIM B
IN. MM
DIM A
IN. MM
DIM B
IN. MM
VALVE VALVE
Material
Number
Internal
Auxiliary Switch
Timing Contact Ratings Auxiliary Switch Range Description Comments Includes
V4062A1008/U No Opening – 26 sec;
Closing – < 1 sec
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
V4062A1123/U Yes Opening – 26 sec;
Closing – < 1 sec
120 Vac – 9.8 AFL, 58.8
ALR, 1/2 hp; 240 Vac –
4.9 AFL, 29.4 ALR, 1/2 hp
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
with return
spring installed
V4062A1131/U No Opening – 13 sec;
Closing – < 1 sec
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
V4062A1156/U No Opening – 26 sec;
Closing – < 1 sec
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
For Series 60
Floating Control
V4062A1198/U Yes - adjusted
to 90 degree
stroke
Opening – 13 sec;
Closing – < 1 sec
120 Vac – 9.8 AFL, 58.8
ALR, 1/2 hp; 240 Vac –
4.9 AFL, 29.4 ALR, 1/2 hp
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
with return
spring installed
V4062D1002/U No Opening – 26 sec;
Closing – < 1 sec
Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2 hp;
4.9 AFL, 29.4 ALR,
1/2 hp
HI-LO-OFF actuator with
Proof of Closure normally
used on V5055C, E/V5907C,
E valve bodies (Low
Pressure)
Damper Shaft
V4062D1010/U No Opening – 13 sec;
Closing – < 1 sec
Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2 hp;
4.9 AFL, 29.4 ALR,
1/2 hp
HI-LO-OFF actuator with
Proof of Closure normally
used on V5055C, E/V5907C,
E valve bodies (Low
Pressure)
Damper Shaft
70-6910 835
Commercial/Industrial
Combustion Controls
Gas Valve Actuators
V9055 Modulating Fluid Power Gas Valve Actuators
Use with V5055 or V5097 Gas Valves to control gas supply for
commercial and industrial burners. Valve opens to low fire
position when power is applied; valve opens all the way on
demand.
• Include integral shaft to drive combustion air damper in unison with
valve.
• One-second maximum closing time.
• Continuously displays the valve position with a red indicator when
open and a yellow indicator when closed.
• Mount in any position directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Frequency: 60 Hz
Temperature Range: -40°F to +125°F (-40°C to +52°C)
Internal Auxiliary Switch: No
Includes: Damper Shaft
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with V5055A,
B, C, E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.) Listed MH1696
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Accessories:
203422C/U – 4-20 ma Adapter for V9055
Material
Number
Electrical
Ratings
Comments Timing Maximum
Safe
Operating
Pressure
(psi)
Maximum
Safe
Operating
Pressure
(kPa)
Contact Ratings Description Approvals, Factory
Mutual
Used With
V9055A1055/U 120 Vac Opening – 26 sec;
Closing – < 1 sec
5 psi 34 kPa Low pressure
Modulating-OFF actuator
for use with V5055B
valve bodies
When used with
the V5055B, C
or V5097B, C:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
V9055A1063/U 120 Vac Nema 4
Enclosure
Opening – 26 sec;
Closing – < 1 sec
5 psi 34 kPa Low pressure
Modulating-OFF actuator
for use with V5055B
valve bodies
When used with
the V5055B, C
or V5097B, C:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
V9055D1000/U 120 Vac Opening – 26 sec;
Closing – < 1 sec
5 psi 34 kPa Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2 hp;
4.9 AFL, 29.4 ALR,
1/2 hp
Low pressure
Modulating-OFF actuator
with Proof of Closure
normally used on
V5055C, E/V5907C, E
valve bodies.
V5034; V5055;
V5097; VE5000
836 70-6910
Gas Valve Actuators
Dimensions in inches (millimeters)
B
E
F
C
D
G A
1 3
D
1/4 INCH NPT
DOWNSTREAM TAP
AND PLUG
1/4 INCH NPT
UPSTREAM TAP
AND PLUG (1/4 BSP
ON INTERNATIONAL
MODELS)
2
1
2
3
[32.5]
KNOCKOUT
FOR1/2 INCH
CONDUIT (4)
OCTAGON
3/4 [19.1] BOLT
HOLES (8)
ON 3-3/4 (95)
RADIUS
1
9
32
1
3
16
[30]
9
3
16
[233]
27
32 [21.5]
3 23
32
5
[94.5]
3 [127.0]
19
32 [91]
6 3
4
[171.5]
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-13/16
8-13/16
11-7/32
5-3/4
5-3/4
5-3/4
5-3/4
8-3/8
9-1/4
9-1/4
12-1/2
13-1/8
13-1/8
13-1/8
13-1/8
13-1/4
13-3/4
13-3/4
16-3/16
2-13/16
2-13/16
2-13/16
2-13/16
3-1/2
4-1/2
4-1/2

333.4
333.4
333.4
333.4
336.5
349.3
349.3
411.0
DIM A
IN. MM
DIM B
IN. MM
DIM C
IN. MM
DIM D
IN. MM
DIM E
IN. MM
DIM F
IN. MM
DIM G OCTAGON
IN. MM IN. MM
ALLOW 4 INCHES CLEARANCE FOR ACTUATOR REMOVAL.
ADD 1/8 INCH TO DIMENSION FOR MODELS WITH NEMA 4 ENCLOSURE.
ADD 1/4 INCH TO DIMENSION A FOR MODELS WITH NEMA 4 ENCLOSURE.
M7321
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
208.0
208.0
208.0
208.0
211.1
223.8
223.8
285.0
146.1
146.1
146.1
146.1
212.7
235.0
235.0
317.5
2-1/4
2-1/4
2-1/4
2-1/4
2-3/4
2-3/4
2-3/4
4-5/8
57.2
57.2
57.2
57.2
69.9
69.9
69.9
117.5
4-13/16
4-13/16
4-13/16
4-13/16
7-19/32
7-19/32
7-19/32

122.2
122.2
122.2
122.2
192.9
192.9
192.9

71.4
71.4
71.4
71.4
88.9
114.3
114.3

Fluid Actuator Accessories and Parts
Material Number Description Used With
133568/U Auxiliary Switch (Adjustable Valve Position) for V4055, V4062 or V9055 V4055; V4062; V9055
133569/U Replacement Pre-ignition Interlock (Proof of Closure) Switch for V4055D, E; V4062D or V9055D V4055; V4062; V9055
203422C/U 4-20 ma Adapter for V9055 V9055
7616BR/U Crank Arm assembly with clip for Damper Arm of V4055, V4062 or V9055 V4055; V4062; V9055
70-6910 837
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
V5055 Industrial Gas Valves
Safety shutoff valves used with V4055, V4062 and V9055 fluid
power actuators to control gas flow to commercial and industrial
burners.
• Use with natural or LP gases.
• Mount directly in gas supply line.
• Include 1/4 in. NPT upstream and downstream taps and plug.
• 4 in. models have only flanged connections.
• V5055 normally closed valves are rated for final shutoff service
safety shutoff.
• V5055A, C, D, E Valves are for On-Off service.
• V5055B Valve has a characterized guide and in combination with the
V4055, V4062, and V9055 Fluid Power Actuators, provides slowopening,
hi-lo-off, and modulating functions respectively.
• V5055C, E, F Valves have a double seal and are used with V4055D,
E Actuators to provide proof-of-closure switch and valve seal overtravel
interlock.
• V5055D, E, F Valves are for high pressure applications.
Operating Temperature Range: -40°F to +150°F; When used with
V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 –
-40°C to +52°C)
Approvals, Underwriters Laboratories Inc.: When used with V4055A,
B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ
Approvals, CSA: When used with V4055, V4062, and V5097: Certified
General listed File No. 158158, Class 3371 for USA and Canada
Approvals, Swiss RE: When used with the V4055A, G and V9055A:
Approved, Report Nos. 20698, 20835, 21172, and 24061
Used With: V9055; V4055; V4062
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055A1004/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1012/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055A1020/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055A1038/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1046/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1053/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1228/U 4 in. DN100 10200 cfh 288.8 m3/hr Flanged With V4055A, D or V4062
– 3 psi (20.7 kPa); With
V4055B or E – 5 psi
(340 mbar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1343/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
838 70-6910
Industrial Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055B1002/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1010/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055B1028/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055B1069/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1077/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1085/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1150/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062
– 3 psi (20.7 kPa); With
V4055B or E – 5 psi (340
mbar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1000/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1018/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1026/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055C1034/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1042/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
70-6910 839
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055C1059/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1109/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062
– 3 psi (20.7 kPa); With
V4055B or E – 5 psi (340
mbar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1182/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055D1008/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1016/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1024/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1032/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1040/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1057/U 3 in. DN80 5230 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1065/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055E1005/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055E1013/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055E1021/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055E1039/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
840 70-6910
Industrial Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055E1047/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055E1054/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055E1062/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055F1003/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
Meets Intent of
DIN Seat Leakage
Requirements
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055F1011/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
Meets Intent of
DIN Seat Leakage
Requirements
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055F1037/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
Meets Intent of
DIN Seat Leakage
Requirements
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
Dimensions in inches (millimeters)
B
E
F
C
D
A 1
1/4 INCH NPT
DOWNSTREAM
TAP AND PLUG
1
KNOCKOUT
FOR1/2 INCH
CONDUIT (4)
OCTAGON
5 (127)
27/32 (21)
3-23/32 (95)
6-3/4 (172)
ALLOW 2 IN. (51 mm) CLEARANCE FOR ACTUATOR REMOVAL.
M27268A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
VALVE
SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
283
283
283
283
286
299
299
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
70
70
70
70
73
86
86
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-13/16
8-13/16
208
208
208
208
211
224
224
5-3/4
5-3/4
5-3/4
5-3/4
8-3/8
9-1/4
9-1/4
146
146
146
146
213
235
235
2-1/4
2-1/4
2-1/4
2-1/4
2-3/4
2-3/4
2-3/4
57
57
57
57
70
70
70
4-7/8
4-7/8
4-7/8
4-7/8
7-19/32
7-19/32
7-19/32
124
124
124
124
193
193
193
2-13/16
2-13/16
2-13/16
2-13/16
3-1/2
4-1/2
4-1/2
71
71
71
71
89
114
114
DIM A
IN. MM
DIM B
IN. MM
DIM C
IN. MM
DIM D
IN. MM
DIM E
IN. MM
DIM F
IN. MM
OCTAGON
IN. MM
1-9/32
(33)
1/4 INCH NPT UPSTREAM
TAP AND PLUG
70-6910 841
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
OCTAGON
H
6-3/4 (171)
1-9/32 (33)
A
B
C
D
DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J
E
G
F
J
OCTAGON
5 (127)
VALVE
SIZE
(IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4
283
283
283
283
298
298
298
2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8
70
70
70
70
86
86
86
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-5/16
8-5/16
208
208
208
208
211
211
211
8-1/4
8-1/4
8-1/4
8-1/4
11-3/4
11-3/4
11-3/4
210
210
210
210
298
298
298
IN. MM IN. MM IN. MM
62
62
62
62
91
91
91
5
5
5
5
8
8
8
127
127
127
127
203
203
203
58
58
58
58
113
113
113
23
23
23
23
38
38
38
100
100
100
100
165
165
165
71
71
71
71
114
114
114
3/4
1
1-1/4
1-1/2
2
2-1/2
3
M27581
1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL.
1
2-7/16
2-7/16
2-7/16
2-7/16
3-5/8
3-5/8
3-5/8
2-5/16
2-5/16
2-5/16
2-5/16
4-7/16
4-7/16
4-7/16
7/8
7/8
7/8
7/8
1-1/2
1-1/2
1-1/2
3-15/16
3-15/16
3-15/16
3-15/16
6-1/2
6-1/2
6-1/2
2-13/16
2-13/16
2-13/16
2-13/16
4-1/2
4-1/2
4-1/2
842 70-6910
Industrial Gas Valves
V5097 Integrated Valve Train
Safety shutoff valves used with V4055, V4062 and V9055 fluid
power actuators to control gas flow to commercial and industrial
burners.
• Use with natural or LP gases.
• Mount directly in gas supply line.
• Two Valve body types. Small body type for 3/4 in., 1 in., 1-1/4 in.,
1-1/2 in., 2 in. pipes. Large body types for 2 in., 2-1/2 in. and 3 in.
pipes.
• Seven pipe adapter sizes from 3/4 in. to 3 in. have NPT or BSP
threaded connections.
• Provides three 1/4 in. upstream and two 1/4 in. downstream tap and
plug.
• CE version provides an additional downstream tap and plug.
• Yellow SHUT indicator attached to the valve stem provides an
indication of the valve closed position.
• V5097A, C, D, E Valves are for on-off service.
• V5097B Valve has a characterized guide and in combination with the
V4055, V4062 and V9055 Fluid Power Actuators, provides slowopening,
HI-LO-OFF, and modulating functions, respectively.
• V5097C, E Valves have a double seal and are used with V4055D, E
Actuators to provide proof-of-closure switch and valve seal overtravel
interlock.
• Actuators to provide proof-of-closure switch and valve seal overtravel
interlock.
• V5097D, E Valves are for high pressure applications.
• Two valve body types (small and large) applicable to server pipe
size.
Operating Temperature Range: -40°F to +150°F; When used with
V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 –
-40°C to +52°C)
Approvals, Underwriters Laboratories Inc.: When used with V4055A,
B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ
Approvals, CSA: When used with V4055, V4062, and V5097: Certified
General listed File No. 158158, Class 3371 for USA and Canada
Approvals, Swiss RE: When used with the V4055A, G: Approved,
Report Nos. 20698, 20835, 21172, and 24061
Approvals, CE: CE #E3070 (Gastec)
Comments: Select Proper Pipe Adapter
Includes: Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT
downstream taps
Used With: V9055; V4055; V4062
Material Number Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity (m3/hr) Maximum Operating
Differential Pressure
Integrated Valve
Train Body Size
Approvals, Factory Mutual
V5097A1004/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Small body When used with the V4055A,
G: Approved, Report Nos.
20698, 20835, 21172, and
24061
V5097A1012/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055A,
G: Approved, Report Nos.
20698, 20835, 21172, and
24061
V5097B1002/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Small body When used with the V4055A,
G and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24061
V5097B1010/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055A,
G and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24061
V5097C1000/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Small body When used with the V4055D,
F and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24066
V5097C1018/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055D,
F and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24066
V5097D1008/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi (1.6 bar)
Small body When used with the V4055B:
Approved, Report Nos.
20698, 20835, 21172, and
24068
V5097D1016/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055B:
Approved, Report Nos.
20698, 20835, 21172, and
24068
V5097E1005/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi (1.6 bar)
Small body When used with the V4055E:
Approved, Report Nos.
20698, 20835, 21172, and
24068
V5097E1013/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055E:
Approved, Report Nos.
20698, 20835, 21172, and
24068
70-6910 843
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
Dimensions in inches (millimeters)
6-3/4 (171)
1-9/32
(33)
A
B
C
D
DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J
E
G
H
F
J
OCTAGON
OCTAGON
5 (127)
VALVE
SIZE
(IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4
283
283
283
283
298
298
298
2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8
70
70
70
70
86
86
86
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-5/16
8-5/16
208
208
208
208
211
211
211
8-1/4
8-1/4
8-1/4
8-1/4
11-3/4
11-3/4
11-3/4
210
210
210
210
298
298
298
IN. MM IN. MM IN. MM
62
62
62
62
91
91
91
5
5
5
5
8
8
8
127
127
127
127
203
203
203
58
58
58
58
113
113
113
23
23
23
23
38
38
38
100
100
100
100
165
165
165
71
71
71
71
114
114
114
3/4
1
1-1/4
1-1/2
2
2-1/2
3
M11682B
1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL.
1
2-7/16
2-7/16
2-7/16
2-7/16
3-5/8
3-5/8
3-5/8
2-5/16
2-5/16
2-5/16
2-5/16
4-7/16
4-7/16
4-7/16
7/8
7/8
7/8
7/8
1-1/2
1-1/2
1-1/2
3-15/16
3-15/16
3-15/16
3-15/16
6-1/2
6-1/2
6-1/2
2-13/16
2-13/16
2-13/16
2-13/16
4-1/2
4-1/2
4-1/2
844 70-6910
Industrial Gas Valves
Integrated Valve Train Pipe Adapters
Material Number Pipe Size
(inch)
Pipe Size
(DN)
Connection
Type
Integrated Valve
Train Body Size
Description Used With
32000109-001/U 3/4 in. DN20 NPT Small body 3/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-002/U 1 in. DN25 NPT Small body 1 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32000109-003/U 1 1/4 in. DN32 NPT Small body 1 1/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-004/U 1 1/2 in. DN40 NPT Small body 1 1/2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-005/U 2 in. DN50 NPT Small body 2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32000109-006/U 3/4 in. DN20 BSP Small body 3/4 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-007/U 1 in. DN25 BSP Small body 1 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-001/U 2 in. DN50 NPT Large body 2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-002/U 2 1/2 in. DN65 NPT Large body 2 1/2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32001605-003/U 3 in. DN80 NPT Large body 3 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-004/U 2 in. DN50 BSP Large body 2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-005/U 2 1/2 in. DN65 BSP Large body 2 1/2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32001605-006/U 3 in. DN80 BSP Large body 3 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
V5055/5097 Replacement Parts or Accessories
Material Number Description Used With
133392A/U O-Ring Assembly for 2 in., 2 1/2 in., and 3 in. V5055 valves V5055/V5097 valves
133393A/U O-Ring Assembly for 1 in., 1 1/4 in., and 1 1/2 in. V5055 valves V5055/V5097 valves
133398AA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055A valves V5055/V5097 valves
133398BA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055B valves V5055/V5097 valves
133398CA/U Replacement Bonnet Assembly, with 137253A replacement Seal Assembly for small body (3/4, 1, 1 1/2 in.)
V5055/V5097C.
V5055/V5097 valves
133417AA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055A valves V5055/V5097 valves
133417BA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055B valves V5055/V5097 valves
133417CA/U Bonnet Assembly for 2, 2 1/2, or 3 in. V5055C or V5097C valves V5055C/V5097C valves
137253A/U Replacement seal assembly. For 4 inch V5055. V5055
4074EYE/U Bag assembly for V5097 (large body) includes 6 ea bolts, nuts and washers. Large Body V5097
4074EYF/U Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. Small Body V5097
4074EYK/U Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. Small Body V5097
4074EYL/U Bag assembly for V5097 (large body) includes (2) O-rings, (1) grease capsule. Large Body V5097
70-6910 845
Commercial/Industrial
Combustion Controls
Pilot Gas Valves
V4046C; V8046C Pilot Gas Valves
Dimensions in inches (millimeters)
1-3/16
(30)
DIM. A
1-3/8
(35)
1-5/8
(41)
1-3/4 (45)
2-5/8 (67)
1-3/4 (45)
DIM. B
1-1/4 (32)
BASIC
CENTER
45
BASIC
CENTER
8-32 x 1/4 IN.(6)
DEEP (2)
1/2-14
NPSM
36 IN. (915)
LEADS (2)
THREAD
SIZE
MODEL
V4046C,
V8046C
BODY
SIZE
THREAD
SIZE
SMALL
SMALL
LARGE
LARGE
1/8-27 NPT
1/4-18 NPT
1/4-18 NPT
3/8-18 NPT
5/16
3/8
1/2
1/2
8
10
13
13
2-3/4
3
3-1/4
3-1/4
70
76
83
83
DIM. A DIM. B
IN MM IN MM
M16595A
Provide on-off control of natural, LP and manufactured gases to
pilot burners in industrial and commercial applications.
• Magnetically operated, normally closed.
• Provide instantaneous action when energized.
• On power failure, valve closes in one second maximum.
• Use in any position, directly in pipe line or on support bracket.
• Replace the solenoid coil without removing the valve body from the
piping connections.
• Straight-through valve pattern.
• Available in line voltage or low voltage models.
Type of Fuel: Air; natural; manufactured; LP
Body Pattern: Straight-through
Valve Opening Time: 1 sec max
Valve Closing Time: 1 sec max
Mounting: Directly in pipe or on support bracket
Materials: Body – Aluminum
Power Consumption: 8 W
Operating Temperature Range: -40°F to +125°F (-40°C to +52°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MH1639,
V3, S3 - Guide No. YIOZ
Approvals, CSA: Certificate No. 158158-2500006058, Guide No.
C3371-03, 83
Approvals, Factory Mutual: Approved: Report No. 17450
Pressure Ratings (psi): 10 psi
Pressure Ratings (kPa): 68.9 kPa
Material Number Pipe Size (inch) Capacity (cfh) Capacity (m3/hr) Voltage Frequency Electrical Connections Approvals,
Swiss RE
V4046C1005/U 1/8 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1021/U 1/4 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1047/U 1/4 in. 55 cfh 1.56 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1054/U 3/8 in. 67 cfh 1.90 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1120/U 3/8 in. 67 cfh 1.90 m3/hr 120 Vac 60 Hz Two 10 ft. leadwires and 1/2 in. conduit bushing Acceptable
V8046C1006/U 1/8 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
V8046C1014/U 1/4 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
V8046C1022/U 1/4 in. 55 cfh 1.56 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
V8046C1030/U 3/8 in. 67 cfh 1.90 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
846 70-6910
Solenoid Gas Valves
V4295; V8295 Solenoid Gas Valves
V4295A/V8295A normally closed and V4295S/V8295S normally
open (vent) solenoid gas valves, are suitable for furnaces, ovens,
atmospheric burners, commercial water heaters, rooftop make-up
air units, power burners, and commercial/industrial boilers.
• V8295A, S are used with 24 Vac controllers.
• V4295A, S are used with 120 Vac controllers.
• Positive close off of gas flow when de-energized.
• High valve spring force allows up to 0.7 psi back pressure at valve
seat.
• No inlet pressure influence at valve seat.
• Inlet pressure changes do not affect ability to close valve.
• Low operating noise.
• Low rush-in current.
• Upstream and downstream taps allows tapping and testing pressure
points.
Type of Fuel: Air; natural; manufactured; mixed; LP
Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT
Body Pattern: Straight-through, non-offset
Valve Opening Time:less than 1 sec
Valve Closing Time: less than 1 sec
Mounting: Vertical to 90 degrees from vertical
Materials: Body – Die-cast aluminum
Frequency: 50 Hz; 60 Hz
Electrical Connections: Screw terminals
Operating Temperature Range: -40°F to +140°F (-40°C to +60°C)
Approvals, Swiss RE: Acceptable
Approvals, Control Safety Devices: Acceptable
Material
Number
Pipe
Size
(inch)
Pipe
Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Voltage Approximate,
Dimensions
Current
Ratings
Pressure
Ratings
(psi)
Pressure
Ratings
(kPa)
Approvals,
Underwriters
Laboratories
Inc.
Approvals,
CSA
Approvals,
Factory
Mutual
V4295A1015 1/2 in. DN15 250 cfh 7.1 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1023 3/4 in. DN20 645 cfh 18.3 m3/hr 120 Vac 5 1/4 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(133 mm high x 87 mm
wide x 70 mm deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1031 1 in. DN25 790 cfh 22.4 m3/hr 120 Vac 5 1/4 in. high x
3 15/16 in. wide x 3 in.
deep (133 mm high x
100 mm wide x 76 mm
deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1049 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 120 Vac 8 in. high x 5 15/16 in.
wide x 4 3/8 in. deep
(203 mm high x 151 mm
wide x 111 mm deep)
0.34
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1056 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 120 Vac 8 3/8 in. high x
5 15/16 in. wide x
4 3/8 in. deep (213 mm
high x 151 mm wide x
111 mm deep)
0.3 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1064 2 in. DN50 3465 cfh 98.1 m3/hr 120 Vac 8 3/8 in. high x
6 11/16 in. wide x
5 3/8 in. deep (213 mm
high x 170 mm wide x
137 mm deep)
0.525
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1072 2 1/2 in. DN65 5070 cfh 143.5 m3/
hr
120 Vac 12 3/4 in. high x
9 1/2 in wide x 7 7/8 in.
deep (324 mm high x
241 mm wide x 200 mm
deep)
0.575
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1080 3 in. DN80 6100 cfh 172.7 m3/
hr
120 Vac 12 3/4 in. high x
9 1/2 in wide x 7 7/8 in.
deep (324 mm high x
241 mm wide x 200 mm
deep)
0.675
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
70-6910 847
Commercial/Industrial
Combustion Controls
Solenoid Gas Valves
Material
Number
Pipe
Size
(inch)
Pipe
Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Voltage Approximate,
Dimensions
Current
Ratings
Pressure
Ratings
(psi)
Pressure
Ratings
(kPa)
Approvals,
Underwriters
Laboratories
Inc.
Approvals,
CSA
Approvals,
Factory
Mutual
V4295A1098 3/8 in. 210 cfh 5.9 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.16
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1106 1/2 in. DN15 290 cfh 8.2 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.16
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1114 3/4 in. DN20 610 cfh 17.3 m3/hr 120 Vac 3 3/16 in. high x
3 7/16 in. wide x
2 3/4 in. deep (81 mm
high x 87 mm wide x
70 mm deep)
0.2 max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1122 1 in. DN25 825 cfh 23.4 m3/hr 120 Vac 6 5/16 in. high x
3 15/16 in. wide x 3 in.
deep (160 mm high x
100 mm wide x 76 mm
deep)
0.2 max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1130 1 1/4 in. DN32 1950 cfh 55.2 m3/hr 120 Vac 8 9/16 in. high x
5 15/16 in. wide x
4 3/8 in. deep (217 mm
high x 151 mm wide x
111 mm deep)
0.55
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1148/U 1 1/2 in. DN40 2270 cfh 64.3 m3/hr 120 Vac 8 9/16 in. high x
5 15/16 in. wide x
4 3/8 in. deep (217 mm
high x 151 mm wide x
111 mm deep)
0.55
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1155 2 in. DN50 3740 cfh 105.9 m3/
hr
120 Vac 9 3/16 in. high x
6 11/16 in. wide x
5 3/8 in. deep (233 mm
high x 170 mm wide x
137 mm deep)
0.54
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295S1005 3/4 in. DN20 350 cfh 9.9 m3/hr 120 Vac 5 1/2 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(140 mm high x 87 mm
wide x 70 mm deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295S1013 1 in. DN25 420 cfh 11.9 m3/hr 120 Vac 5 1/2 in. high x
3 15/16 in. wide x 3 in.
deep (140 mm high x
100 mm wide x 76 mm
deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295S1021 1 1/4 in. DN32 1100 cfh 31.1 m3/hr 120 Vac 8 3/4 in. high x
5 15/16 in. wide x
4 3/8 in. deep (222 mm
high x 151 mm wide x
111 mm deep)
0.34
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 83
Approved:
Report No.
J.I.OD6A2.
AF
V8295A1016 1/2 in. DN15 250 cfh 7.1 m3/hr 24 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1024 3/4 in. DN20 645 cfh 18.3 m3/hr 24 Vac 5 1/4 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(133 mm high x 87 mm
wide x 70 mm deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1032 1 in. DN25 790 cfh 22.4 m3/hr 24 Vac 5 1/4 in. high x
3 15/16 in. wide x 3 in.
deep (133 mm high x
100 mm wide x 76 mm
deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
848 70-6910
Solenoid Gas Valves
Material
Number
Pipe
Size
(inch)
Pipe
Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Voltage Approximate,
Dimensions
Current
Ratings
Pressure
Ratings
(psi)
Pressure
Ratings
(kPa)
Approvals,
Underwriters
Laboratories
Inc.
Approvals,
CSA
Approvals,
Factory
Mutual
V8295A1040 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 24 Vac 8 in. high x 5 15/16 in.
wide x 4 3/8 in. deep
(203 mm high x 151 mm
wide x 111 mm deep)
1.6 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1057 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 24 Vac 8 3/8 in. high x
5 15/16 in. wide x
4 3/8 in. deep (213 mm
high x 151 mm wide x
111 mm deep)
1.7 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1065 2 in. DN50 3465 cfh 98.1 m3/hr 24 Vac 8 3/8 in. high x
6 11/16 in. wide x
5 3/8 in. deep (213 mm
high x 170 mm wide x
137 mm deep)
2.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295S1006 3/4 in. DN20 350 cfh 9.9 m3/hr 24 Vac 5 1/2 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(140 mm high x 87 mm
wide x 70 mm deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
70-6910 849
Commercial/Industrial
Combustion Controls
Solenoid Gas Valves
V4297A Solenoid Safety Shut-off Valve for IVT
V4297A are normally closed solenoid gas valve. Suitable for
use on furnaces, ovens, atmospheric burners, commercial
water heaters, rooftop make-up air units, power burners, and
commercial/industrial boilers.
• V4297A are used with 120 Vac controllers.
• Positive close off of gas flow when de-energized.
• High valve spring force allows up to 0.7 psi back pressure at valve
seat.
• No inlet pressure influence at valve seat.
• Inlet pressure changes do not affect ability to close valve.
• Low operating noise.
• Low rush-in current.
• Upstream and downstream taps allows tapping and testing pressure
points.
• For use with the Integrated Valve Train.
• Accepts C6097 Pressure Switch mounted directly to flange
(upstream pressure tap only).
Type of Fuel: Air; natural; manufactured; mixed; LP
Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT
Body Pattern: Straight-through, non-offset
Valve Opening Time: less than 1 sec
Valve Closing Time: less than 1 sec
Flanges: Required, Order Separately
Mounting: Directly bolted to Integrated Valve Train Components
Materials: Body – Die-cast aluminum
Voltage: 110 Vac; 120 Vac
Frequency: 50 Hz; 60 Hz
Electrical Connections: Screw terminals
Operating Temperature Range: -40°F to +130°F (-40°C to +54°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No.
MH18476, V1, S1 - Guide No. YIOZ
Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371-
03, 04, 83
Approvals, Swiss RE: Acceptable
Pressure Ratings (psi): 5 psi
Pressure Ratings (kPa): 34.5 kPa
Replacement Parts:
4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea
bolts, nuts and washers.
4074EYK/U – Bag assembly for V5097 (small body) includes (2)
O-rings, (1) grease capsule.
Dimensions in inches (millimeters)
2 (51)
5 (127)
5-1/2 (140)
5-5/8 (143)
3-3/4 (95)
1-1/2
(38)
2-3/4
(70)
1/2 (13)
5-3/4 (147)
6-1/4
(159)
10-1/4
(260)
M23226
TOP VIEW
Material
Number
Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity
(m3/hr)
Approximate, Dimensions Integrated Valve
Train Body Size
Current Ratings
V4297A1005 3/4 in. to 1 1/4 in. DN20 or DN25 or
DN32
650 cfh; 700 cfh;
780 cfh
19.8 m3/hr 9 in. high x 5 3/4 in. wide x 5 5/8 in.
deep (229 mm high x 147 mm wide x
143 mm deep)
Small body, small
flow
0.2 max amps at
rated Vac/Hz
V4297A1013 3/4 in. to 2 in. DN20 or DN25 or
DN32 or DN40 or
DN50
1190 cfh; 1460 cfh;
2260 cfh; 2735 cfh;
3060 cfh
10 1/4 in. high x 5 3/4 in. wide x 5 5/8 in.
deep (260 mm high x 147 mm wide x
143 mm deep)
Small body, large
flow
0.5 max amps at
rated Vac/Hz
850 70-6910
Solenoid Gas Valves
V4297S Normally Open Vent Valve for IVT
V4297S are normally open (vent) solenoid gas valves. Suitable
for use on furnaces, ovens, atmospheric burners, commercial
water heaters, rooftop make-up air units, power burners, and
commercial/industrial boilers.
• V4297S is used with 120 Vac controllers.
• Low operating noise.
• Low rush-in current.
• Upstream and downstream taps allows tapping and testing pressure
points.
• For use with the Integrated Valve Train.
Type of Fuel: Air; natural; manufactured; mixed; LP
Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT
Body Pattern: Straight-through, non-offset
Valve Opening Time: less than 1 sec
Valve Closing Time: less than 1 sec
Flanges: Required for Stand Alone
Mounting: Directly bolted to Integrated Valve Train Components
Materials: Body – Die-cast aluminum
Voltage: 110 Vac; 120 Vac
Frequency: 50 Hz; 60 Hz
Electrical Connections: Screw terminals
Operating Temperature Range: -40°F to +145°F (-40°C to +63°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No.
MH18476, V1, S1 - Guide No. YIOZ
Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371-
03, 04, 83
Approvals, Swiss RE: Acceptable
Pressure Ratings (psi): 5 psi
Pressure Ratings (kPa): 34.5 kPa
Replacement Parts:
4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea
bolts, nuts and washers.
4074EYK/U – Bag assembly for V5097 (small body) includes (2)
O-rings, (1) grease capsule.
4074EYL/U – Bag assembly for V5097 (large body) includes (2)
O-rings, (1) grease capsule.
Dimensions in inches (millimeters)
2-5/8
3 (69)
(76)
1-1/2
(38)
5/16
(8)
3/4 (18)
3/4 (18)
2
(51)
5 (127) 8 (203)
1-1/2
3/16 (5) (32)
M23252
2
(51)
12-3/8
(314)
3-1/8
(79)
1/2 (13) 4-1/2 (114)
5/8
(16)
1 (25)
1/2
(13)
1-1/4 IN.
NPT
1/2 (13)
(3 HOLES)
3/8 (10)
(3 HOLES)
2-5/8
(69)
9-1/2
(241)
3-1/8
(79)
3/8
(10)
1/2
(13)
1/2
(13)
7/8
(22)
4-1/8
(105)
3-1/8 (79) 5 (127)
3/8
(10)
1/2
(13)
1-1/4
(32)
2 (51)
1-1/2
(32)
3/16 (5)
1-15/16
(49)
2-3/8
(60)
M23251
2 (51)
1 IN.
NPT
Material Number Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions Integrated Valve Train
Body Size
Current Ratings
V4297S1003 DN25 714 cfh 20.2 m3/hr 9 1/2 in. high x 3 1/8 in. wide x 5 in.
deep (241 mm high x 79 mm wide x
127 mm deep)
Small body 0.2 max amps at rated
Vac/Hz
V4297S1011 DN32 1115 cfh 31.6 m3/hr 12 3/8 in. high x 5 in. wide x 8 in.
deep (314 mm high x 127 mm wide x
203 mm deep)
Large body 0.34 max amps at
rated Vac/Hz
70-6910 851
Commercial/Industrial
Combustion Controls
Servo Regulated Gas Valves
V4730C; V4734C; V8730C Gas/Air Servo Regulated Gas Valves
Body Pattern: Straight flange
Valve Opening Time: Dead time maximum: 1 second; First valve –
< 1 second; Second valve – reaches 50% of the adjustable outlet
pressure within 5 seconds
Materials: Body: Aluminum alloy, die-cast
Frequency: 50 Hz; 60 Hz
Ambient Temperature Range: 5°F to 140°F (-15°C to +60°C)
Approvals, Underwriters Laboratories Inc.: File No. MH18476
Approvals, CSA: File: Certificate No: 158158-1227192
Approvals, Others: Gas Appliance Directive: 90.396/EEC, PIN:
0063AT1198, Low Voltage Directive: 73/23/EEC, Electro Magnetic
Compatibility Directive: 89/336/EEC
Maximum Safe Operating Pressure (psi): 0.5 psi (CSA approved),
1.45 psi for 120V; 1 psi for 24V (UL approved)
Maximum Operating Pressure (mbar): 200 mbar (UL approved)
100 mbar for 120V; 69 mbar for 24V (UL approved), 35 mbar (CSA
approved)
Comments: The minimum load for which the system can be used is
14-17% of the reference load, which equals a minimum pressure
differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas
control.
Coil Insulation Solenoid Valves: Class H insulation system
Current Ratings: V1 Current Rating – 0.16A; V2 Current Rating –
0.16A; V1 + V2 Current Rating – 0.32A
Material Number Pipe Size
(inch)
Capacity (kW) Capacity (kBtuh) Voltage Electrical
Connections
Pipe Connection Includes Max. Capacity
with Strainer (cfh)
V4730C1006-0000 1/2 in. Natural Gas 0.64
sp.gr –
22-150 KW
Natural Gas 0.64
sp.gr – 73-
512 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-001 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 221
cfh
V4730C1014-0000 3/4 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-002 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V4730C1022-0000 1 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-003 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V4730C1030-0000 1 1/4 in. Natural Gas
0.64 sp.gr –
55-382 KW
when used with
VMU335,
71-500KW
Natural Gas 0.64
sp.gr – 185-
1300 kBtuh
when used with
VMU335,245-
1710 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-004 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1300
cfh
852 70-6910
Servo Regulated Gas Valves
Material Number Pipe Size
(inch)
Capacity (kW) Capacity (kBtuh) Voltage Electrical
Connections
Pipe Connection Includes Max. Capacity
with Strainer (cfh)
V4734C1002-0000 1 1/4 in. Natural Gas
0.64 sp.gr –
97-680 KW
when used with
VMU680
Natural Gas 0.64
sp.gr – 326-
2287 kBtuh
when used with
VMU680
120 Vac
(+10%, -15%)
Mesh screen filter and
32006652-004 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
V8730C1007-0000 1/2 in. Natural Gas 0.64
sp.gr –
22-150 KW
Natural Gas 0.64
sp.gr – 73-
512 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-001 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 221
cfh
V8730C1015-0000 3/4 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-002 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V8730C1023-0000 1 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-003 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V8730C1031-0000 1 1/4 in. Natural Gas
0.64 sp.gr –
55-382 KW
when used with
VMU335,
71-500 KW
Natural Gas 0.64
sp.gr – 185-
1300 kBtuh
when used with
VMU335,
245-1710 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-004 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1300