ECC or Buildings Branch | Flame Safeguard part 2 Flame Detectors C7012 Solid State Purple Peeper® Ultraviolet Flame Detector Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels. • Mount horizontally, vertically or at any angle in between. • Provide quick electrical hookup with threaded conduit fitting and color-coded leadwires. • Reduced nuisance shutdowns by wiring two in parallel. • C7012E1278 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • C7012A, E meets NEMA 4 standards with viewing window rated to 20 psi. • C7012C, F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper Application: Gas, Oil or Coal fired burners Lead Length: 96 in. (2438 mm) Power Consumption: 2.5 W Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 14740.01 Material Number Frequency Weight NEMA Rating Electrical Connections Mounting Electrical Ratings Ambient Temperature Range Approvals, Underwriters Laboratories Inc. Approvals, Others Includes Used With C7012A1145/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, R7847A, R7257; Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1152/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 1 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1160/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 1 in. NPT 120 Vac -40°F to +175°F (-40°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1186/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 208 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1194/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 240 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1202/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 100 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, R7847A, R7257 C7012A1210/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, R7847A, R7257 C7012C1042/U 50 Hz; 60 Hz 14.5 lb (6.6 kg) Explosion Proof 4 NEC Class 1 Colorcoded lead wires. 1 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. E34649, Guide No. ZTSZ Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012G1019/U 50 Hz 4.25 lb (1.9 kg) NEMA 4 5 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 220 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Meets DIN Standards Cast case and cover Flame Amplifiers: R7247C, R7847C 70-6910 799 Commercial/Industrial Combustion Controls Flame Detectors Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) 800 70-6910 Flame Detectors C7012 Solid State Purple Peeper® Ultraviolet Flame Detector (Self-Checking) Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels. • Mount horizontally, vertically or at any angle in between. • Provide quick electrical hookup with threaded conduit fitting and color-coded leadwires. • Reduced nuisance shutdowns by wiring two in parallel. • C7012E1278 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • C7012A, E meets NEMA 4 standards with viewing window rated to 20 psi. • C7012C, F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper, Self-Checking Application: Gas, Oil or Coal fired burners Lead Length: 96 in. (2438 mm) Power Consumption: 7.0 W Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 14740.01 Used With: Flame Amplifiers: R7247C, R7847C Material Number Frequency Weight NEMA Rating Electrical Connections Mounting Electrical Ratings Ambient Temperature Range Approvals, Underwriters Laboratories Inc. Approvals, Others Includes C7012E1104/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1112/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 1 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1120/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 1 in. NPT 120 Vac -40°F to +175°F (-40°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1146/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 208 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover, with Hot refractory tube C7012E1153/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 240 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1187/U 50 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 220 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ DIN (Europe) Cast case and cover C7012E1195/U 50 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 110 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ BGC (Europe) Cast case and cover C7012E1203/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 240 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ BGC (Europe) Cast case and cover C7012E1278/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 Brad Harrison type number 41310 connector 1 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012F1052/U 50 Hz; 60 Hz 14.5 lb (6.6 kg) Explosion Proof 6 NEC Class 1 Color-coded lead wires. 1 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. E34649, Guide No. ZTSZ Explosion-proof, two piece, violet, cast aluminum enclosure Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) 70-6910 801 Commercial/Industrial Combustion Controls Flame Detectors C7024 Solid State Purple Peeper® Ultraviolet Flame Detector 24 Vdc solid state electronic flame detectors for sensing the ultraviolet radiation emitted by the combustion of most carbon containing fuels, such as natural gas, LP gases, and oil. • Use with R7824C Dynamic Self-Check Flame Signal Amplifier. • Circuitry provides low power consumption and high reliability. • Mount horizontally, vertically or at any angle in between. • Field-replaceable UV radiation sensing tube and quartz viewing window. • Quick electrical installation with threaded conduit fitting and colorcoded leadwires. • Reduce nuisance shutdowns by wiring two in parallel. • Oscillating shutter interrupts UV radiation using the R7824C amplifier. • C7024E meets NEMA 4 standards with viewing window rated to 20 psi. • C7024F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper, Self-Checking Application: Coal fired burners; Gas fired burners; Oil fired burners Lead Length: 96 in. (2438 mm) Electrical Connections: Six NEC CLASS 1 color-coded leaders Electrical Ratings: 24 Vdc Power Consumption: 7.8 W maximum. Ambient Temperature Range: -20°F to +175°F (-20°C to +79°C) Approvals, CSA: Certified: Master Report LR95329-3 Used With: Flame Amplifiers: R7824C Accessories: 190971G/U – 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961 Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) Material Number NEMA Rating Mounting Approximate, Dimensions Weight Approvals, Underwriters Laboratories Inc. Includes Comments C7024E1001/U NEMA 4 3/4 in. NPT 5 1/4 in. diameter (includes mounting flange) x 7 7/32 in. long (133 mm diameter (includes mounting flange) x 183 mm long) 4.25 lb (1.9 kg) Component Recognized: File No. MP268 Cast case and cover Flame Amplifiers: R7824C C7024F1009/U Explosion Proof 1 in. NPT 8 in. diameter x 12 in. long (203 mm diameter x 305 mm long) 14.5 lb (6.6 kg) Component Recognized: For use in hazardous locations; Class 1 Groups C and D; Class 2, Groups E, F and G; File no. E34649 Flame Amplifiers: R7824C 802 70-6910 Flame Detectors C7027; C7044 Minipeeper Ultraviolet Flame Detector Compact Flame Detector for use with flame safeguard controls with ultraviolet amplifiers. • Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection. • C7027 mounts on a 1/2 in. sighting pipe by using an integral collar. • Detectors can be wired in parallel for difficult sighting applications. • C7027 seals against pressures up to 5 psi (34.5 kPa) when correctly installed. • Allows for blast tube mounting due to compact size. • C7044 mounts with a two screw bracket. • The C7044 UV sensor tube is enclosed in a stainless steel housing. • C7044 has the capability of side or end viewing in flame monitoring applications. Type: Ultraviolet, Minipeeper Electrical Connections: 2 NEC Class 1 leadwires Vibration: 0.5 G max Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290 Material Number Application Lead Length Mounting Ambient Temperature Range Approvals, Others Includes Comments C7027A1023/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) Detects ultraviolet radiation in flames C7027A1031/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) Detects ultraviolet radiation in flames C7027A1049/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1056/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) DIN (Europe) Detects ultraviolet radiation in flames C7027A1064/U Coal fired burners; Gas fired burners; Oil fired burners 288 in. (7315 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1072/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1080/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) 136733 Heat Block and 390427B bushing Detects ultraviolet radiation in flames C7027A1114/U Coal fired burners; Gas fired burners; Oil fired burners 44 in. (1118 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) installed 22" flexible conduit Detects ultraviolet radiation in flames C7027A1122/U Oil fired burners; Gas fired burners; Coal fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1130/U Gas fired burners; Oil fired burners; Coal fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to +215°F (-40°C to +102°C) Detects ultraviolet radiation in flames C7044A1006/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) Mounting Bracket provided 0°F to 215°F (-18°C to +102°C) Mounting bracket Detects ultraviolet radiation in flames - Side Viewing Dimensiions in inches (millimeters) COLLAR WITH 1/2-14 NPSM INTERNAL THREADS 4 (102) 8 FOOT (2.44 METER) LEADWIRES (2) M1943G C7027A1064 HAS 24 FOOT (7.32 METER) LEADWIRES. C7027A1114 HAS 44 IN. (1.118 M) LEADWIRES WITH 22 IN. (558 MM) FLEXIBLE CONDUIT. 1 2 2 3-1/2 (89) 1-1/16 (27) 1 MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL THREADS) INSTEAD OF CLAMP TYPE CONNECTOR. 6 FOOT [1.83 METER] LEAD WIRES (2) 3-5/8 (92) 1/2 (13) 1-27/64 (36) 3/8 (10) 7/8 (22) 9/16 (14) M1944D MOUNTING BRACKET 70-6910 803 Commercial/Industrial Combustion Controls Flame Detectors C7035 Minipeeper Ultraviolet Flame Detector Dimensiions in inches (millimeters) 1/2-14 NPSM INTERNAL THREADS COLLAR WITH 2 (51) 2 1 - 11-1/2 NPSM INTERNAL THREADS 1 1 DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL MOUNTING THREADS. DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL MOUNTING THREADS. C7035A1056 HAS 12 FOOT (3.66 METER) LEADWIRES. 2 3 INSERTION DEPTH 6 FOOT [1.83 METER] LEADWIRES (2) 3 M1945E 2-5/8 (67) 1-1/2 (38) 31/32 (25) 4-1/8 (105) 1-3/16 (30) Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers. • Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection. • Mounts on a 1 in. sighting pipe by using an integral collar. • Protects the sensing tube with a shield. • Meets outdoor rain tight requirements of Underwriters Laboratories Inc., NEMA 4 and NEMA 4X. • Wires in parallel for difficult sighting applications. • Seals against pressures as high as 5 psi (34.5 kPa) when correctly installed. • Field-replaceable ultraviolet sensing tube. Type: Ultraviolet, Minipeeper NEMA Ratings: NEMA 3 and NEMA 4 Electrical Connections: 2 NEC Class 1 leadwires Vibration: 0.5 G max Mounting: Integral nut for 1 in. sighting pipe. Approximate, Dimensions: 1 1/2 in. diameter x 4 1/8 in. long (38 mm diameter x 105 mm long) Weight: 6 oz (0.17 kg) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Comments: Detects ultraviolet radiation in flames Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290 Material Number Application Lead Length Ambient Temperature Range Approvals, Others Includes C7035A1023/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) C7035A1031/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C) C7035A1049/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) DIN (Europe) C7035A1056/U Coal fired burners; Gas fired burners; Oil fired burners 144 in. (3658 mm) -40°F to +250°F (-40°C to +121°C) C7035A1064/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C) C7035A1080/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) 600F leads C7035A1098/U Oil fired burners; Gas fired burners; Coal fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C) 804 70-6910 Flame Detectors C7061 Dynamic Self-Check Ultraviolet Flame Detector Dynamic self-checking flame detector used with R7861 Dynamic Self-check Amplifiers for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels. • Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the UV sensor tube checking function. • Can be mounted horizontally, vertically or at any angle in between. • The detector requires faceplate alignment and has integral locating reference points to assure proper operation of the shutter mechanism. • Field replaceable ultraviolet sensing tube and quartz viewing window. • Models with threaded conduit fitting and color-coded leadwires allow rapid electrical installation. • C7061A1038 or A1046 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • Two detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications. • Protective heat block built into mounting flange. • -40°F (-40°C) rated ultraviolet sensing tube is supplied. • C7061E meets NEMA 4 standards with viewing window rated to 20 psi. • C7061F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper, Self-Checking Application: Gas fired burners; Oil fired burners Comments: Dynamic self-checking flame detector Used With: Flame Amplifiers: R7861 Approvals, Underwriters Laboratories Inc.: C7061A, M-Listed: File No. MP268, Guide No. MCCZ; C7061F-Recognized: For use in hazardous locations, Class 1 Groups C and D; class 2, Groups E, F and G; File no. E34649 Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 14740.01 Material Number NEMA Rating Lead Length Electrical Connections Mounting Electrical Ratings Frequency Ambient Temperature Range Approvals, Others C7061A1004/U NEMA 4 77 in. (1981 mm) PVC jacketed cable 3/4 in. NPT 120 Vac 50 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1012/U NEMA 4 96 in. (2438 mm) Color-coded leadwires 3/4 in. NPT 120 Vac 51 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1020/U NEMA 4 Terminal block 3/4 in. NPT 120 or 230 Vac 52 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1038/U NEMA 4 Brad Harrison type number 41310 connector 3/4 in. NPT 120 Vac 53 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1046/U NEMA 4 Brad Harrison type number 41310 connector 1 in. NPT 120 Vac 54 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1053/U NEMA 4 96 in. (2438 mm) Color-coded leadwires 1 in. NPT 120 Vac 55 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061F1003 Explosion Proof Terminal block 1 in. NPT 120 or 230 Vac 56 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) CE and conforms to EEXD IIc C7061F2001/U Explosion Proof 96 in. (2438 mm) Color-coded leadwires 1 in. NPT 120 Vac 57 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061M1008/U NEMA 4 96 in. (2438 mm) Color-coded leadwires 1 in. NPT 120 Vac 58 Hz; 60 Hz -4°F to +175°F (-20°C to +79°C) C7061M1016/U NEMA 4 Brad Harrison type number 41310 connector 1 in. NPT 120 Vac 59 Hz; 60 Hz -4°F to +175°F (-20°C to +79°C) Dimensions for C7061A in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. Dimensions for C7061F in inches (millimeters) M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) 70-6910 805 Commercial/Industrial Combustion Controls Flame Detectors Dimensions for C7061M in inches (millimeters) M29114A 2-9/64 (55) 13/16 (21) 2-21/32 (68) 3-15/32 (88) 1-33/64 (39) PARALLEL PIPETHREAD 1-11/2 NPSM 33/64 (13) 2-9/64 (55) 1-35/64 (40) CONDUIT TUBE CONNECTION PORT 1/2 NPSM 806 70-6910 Flame Detectors C7076 Adjustable Sensitivity Ultraviolet Flame Detector Solid state dynamic self check flame detectors for use with BC7000, R4140 or FSP5075 with R7476 Amplifier and 7800 SERIES with R7886 Amplifier. • Use Honeywell Flame Safeguard primary safety controls requiring adjustable sensitivity ultraviolet flame detection. • Detect ultraviolet radiation from flames. • Include dual sensitivity adjustment. • C7076A meets NEMA 4 standards with viewing window rated to 20 psi. • C7076D has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Adjustable Sensitivity Application: Gas fired burners; Oil fired burners Electrical Connections: Terminal block Vibration: 0.5 G max Mounting: 1 in. NPT Power Consumption: 7.0 W Ambient Temperature Range: -40°F to +160°F (-40°C to +71°C) Approvals, CSA: Certified: Master Report LR1620 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. FM26980 Comments: Dynamic self-checking flame detector with adjustable sensitivity Used With: Flame Amplifiers: R7476, R7886 Replacement Parts: 190971F/U – 100 Vac Coil and Shutter Assembly for C7076A, D 190998A/U – Aspiration assembly for C7076A 191002R/U – 120 Vac Plug in Electronics less UV Sensing Tube for C7076D 191050/U – Quartz Viewing Window for C7076 191053/U – UV Sensing Tube for C7076 Dimensiions in inches (millimeters) C7076A C7076D M20749A 2-1/4 (57) 2-1/4 (57) 2-9/32 (58) 5-25/32 (147) 5-25/32 (147) 1-27/32 (47) 7-13/16 (198) 15/16 (24) 25/32 (20) 1-9/16 (40) 11-13/16 (300) 3/4 (19) 1-5/8 (19) 2-21/32 (68) 7-19/32 (194) 3/8 INCH NPT 1 (25) 29/32 (22) OPENING FOR 1/2-INCH CONDUIT 7-13/32 (188) 10-1/4 (261) 1-1/16 (27) 4 (102) 4 (102) 4-25/32 (122) 1 INCH NPT POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 1 1 6-23/32 (171) 1-31/32 (50) 3-15/16 (100) 5/16-18 UNC (3 PLCS) X 0.47 (12) DEEP Material Number NEMA Rating Electrical Ratings Frequency Approximate, Dimensions Weight Approvals, Underwriters Laboratories Inc. Approvals, Others C7076A1007/U NEMA 4 120 Vac 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep (102 mm high x 102 mm wide x 261 mm deep) 6.6 lb (3 kg) Listed: File No. MP268, Guide No. MCCZ C7076A1015/U NEMA 4 100 Vac 50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep (102 mm high x 102 mm wide x 261 mm deep) 6.6 lb (3 kg) Listed: File No. MP268, Guide No. MCCZ C7076A1031/U NEMA 4 220 Vac; 240 Vac 50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep (102 mm high x 102 mm wide x 261 mm deep) 6.6 lb (3 kg) Listed: File No. MP268, Guide No. MCCZ C7076D1027/U NEMA 7 120 Vac 60 Hz 6 5/8 in. high x 6 3/16 in. wide x 11 3/4 in. deep (168 mm high x 158 mm wide x 300 mm deep) 17.6 lb (8 kg) Listed: File No. E34649, Guide No. ZTSZ Explosion Proof 70-6910 807 Commercial/Industrial Combustion Controls Flame Detectors C7927 Solid State Ultraviolet Flame Detector Dimensiions in inches (millimeters) 8 FT (2.44 M) 1 (25) C7927A1016 M24714 3-3/4 (95) 3-1/4 (82) The Solid State Ultraviolet Flame Detectors, sense ultraviolet radiation emitted by combustion flames. The flame detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil, or combination gas-oil burners. • Properly installed the flame detectors are pressure rated for 5 psi. • Flame detector is used with only the R7851B Flame Amplifier and the 7800 SERIES controls. • Has an integral collar threaded (internal 1/2-14 NPSM) for mounting on a one-half inch sight pipe. Type: Ultraviolet, Minipeeper Application: Gas, Oil, or combination burners-intermittent operation only (burner cycled at least once each 24 hours). NEMA Rating: NEMA 1 Electrical Connections: 2 NEC Class 1 leadwires Mounting: 1/2 in. NPT pipe mounting Approximate, Dimensions: 1 in. diameter x 3 3/4 in. long (25 mm diameter x 95 mm long) Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MP268 Approvals, CSA: Report 158158 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 3011020 Comments: Detects ultraviolet radiation in flames Material Number Lead Length Ambient Temperature Range Used With C7927A1016/U 96 in. (2438 mm) -40°F to +200°F (-40°C to +93°C) Flame Amplifiers: R7851B 808 70-6910 Flame Detectors C7961 Dynamic Self-checking Solid State Ultraviolet Flame Detector A self-checking flame detector using a solid state UV sensor to detect ultraviolet radiation in flames for supervision of gas, oil or combination gas-oil burners. • Designed for use with 7800 series controls with the R7851C flame amp. • Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the solid state UV sensor checking function. • Can be mounted horizontally, vertically or at any angle in between. • The detector requires faceplate alignment and has integral locating reference points to assure proper operation of the shutter mechanism. • Models available with threaded conduit fitting and color-coded leadwires allow rapid electrical installation. • C7961E1022 or E1030 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • Incorporates UV sensor tube checking feature; used with R7851C1008 Dynamic Self-check Amplifiers. • Protective heat block built into mounting flange. • -40°F (-40°C) rated ultraviolet sensing cell is supplied. • C7961E meets NEMA 4 standards with viewing window rated to 20 psi. • C7961F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Self-Checking Application: Gas, Oil or other fuels Electrical Ratings: 120 Vac (-15% +10%) Frequency: 50 Hz; 60 Hz Ambient Temperature Range: -40°F to +175°F (-40°C to +80°C) Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MP268 Comments: Detects ultraviolet radiation generated by combustion of gas, oil, or other fuels Approvals, Swiss RE: Acceptable Used With: R7851C Dynamic Self-Check Amplifier Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) Material Number NEMA Rating Lead Length Electrical Connections Mounting Approximate, Dimensions Weight Approvals, CSA Approvals, Factory Mutual Includes C7961E1006/U NEMA 4 96 in. (2438 mm) NEC Class 1 color-coded 3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961E1014/U NEMA 4 96 in. (2438 mm) NEC Class 1 color-coded 1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961E1022/U NEMA 4 5 pin Brad Harrison Type Connector 1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961E1030/U NEMA 4 5 pin Brad Harrison Type Connector 3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961F1004/U Explosion Proof 96 in. (2438 mm) NEC Class 1 color-coded 1 in. NPT 8 in. diameter x 12 in. long (203 mm diameter x 305 mm long) 14.5 lb (6.6 kg) Approved: Report No. 14740.01 Quartz Viewing Window rated for 100 psi 70-6910 809 Commercial/Industrial Combustion Controls Flame Detectors C7915 Infrared Flame Detector The C7915 Combination mount Lead Sulfide cell senses infrared radiation from gas, oil, and coal or dual-fuel flames. • Used for combination or dual-fuel applications. • Detects pilot and main flame. • Mounts quickly and easily on a standard 3/4 in. sighting pipe. • Works where flame rod or rectifying photocell mounts are difficult to apply. Type: Infrared (Lead Sulfide) Application: Used for combination or dual-fuel applications Electrical Connections: Two no. 18 AWG wires Mounting: 3/4 in. NPT Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Comments: Infrared (Lead Sulfide) Flame Detector Replacement Parts: 32007255-001/U – Lead Sulfide Cell for C7915 50019469-001/U – Magnifying Lens Assembly for C7915A Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With C7915A1010/U 30 in. (762 mm) 1 1/4 in. diameter x 2 1/4 in. long (32 mm diameter x 58 mm long) -20°F to 125°F operating range (-18°C to 52°C operating range) With magnifying lens, 32007255-001 Cell Flame Amplifiers: R7852 C7915A1028/U 48 in. (1219 mm) 1 1/4 in. diameter x 2 1/4 in. long (32 mm diameter x 58 mm long) -20°F to 125°F operating range (-18°C to 52°C operating range) With magnifying lens, 32007255-001 Cell, Orifice, heat block, and reducer bushing Flame Amplifiers: R7852 C7915A1036/U 96 in. (2438 mm) 1 1/4 in. diameter x 2 1/4 in. long (32 mm diameter x 58 mm long) -20°F to 125°F operating range (-18°C to 52°C operating range) With magnifying lens, 32007255-001 Cell Flame Amplifiers: R7852 C7962 Visible Light Flame Detector Dimensiions in inches (millimeters) 4 FOOT (1.2 METER) LEADWIRES (2) M20912 3-1/4 (82) 3-3/4 (95) 1 (25) C7962B The C7962B Visible Light Flame Detector detects the visible light emitted by fuel oil combustion flames. The C7962B Detector is used with Honeywell Flame Safeguard controls to provide fuel oil flame supervision in commercial and industrial burners. • Used with 7800 SERIES Flame Safeguard controls. • Used with R7851B Flame Amplifier. • Has an integral collar threaded (internal 1/2-14 NPSM) for mounting on 1/2 inch sight pipe. Type: Visible Light Flame Detector Application: Commercial, industrial oil burners NEMA Ratings: NEMA 1 Electrical Connections: 2 NEC Class 1 leadwires Vibration: 0.5 G max Mounting: 1/2 in NPT pipe mounting Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MP268 Approvals, CSA: Report 158158 Approvals, Swiss RE: Acceptable Accessories: 32007439-001/U – Mounting Bracket and screws for C7962B (3/8 in. NPT to 1/2 in. NPT) Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With C7962B1002/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm diameter x 95 mm long) -40°F to +160°F (-40°C to +71°C) Flame Amplifiers: R7851B C7962B1010/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm diameter x 95 mm long) -40°F to +160°F (-40°C to +71°C) 32007439-001 Mounting Bracket and screws Flame Amplifiers: R7851B 810 70-6910 Flame Detectors Optical Flame Detector Accessories or Parts Material Number Description Used With 105172C/U Pressure Seal-off Adapter (3/4 NPT) w/UV Quartz window for C7012, C7024, C7027, C7061 C7012, C7024, C7027, C7061; C7024; C7012; C7061 110634A/U Magnifying Lens Assembly for C7015A C7015 113228/U UV Sensing Tube (-20°F to 175°F) for C7012; C7024 C7012; C7024 114372/U Bulk Pack -20 PSI window for C7012E, F; C7024; C7061 C7024; C7012; C7061 114638/U Rubber Washer (Red) for C7012A, E; C7024A; C7061A; C7961A C7012; C7061; C7024 120739/U Flange Gasket for C7012, C7024, C7061 C7024; C7012; C7061 120930/1662/F Cover for C7012A,G, C7024E, C7061A, C7961E C7012A,G, C7024E, C7061A, C7961E; C7012 120934-520/U Mounting Flange (3/4") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A, C7961E 122748/U 50 PSI Quartz Window for C7012, C7061 C7012; C7061; C7024 124198/U Mounting Flange (1") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A, C7961E 129464M/U UV Power Tube (0°F to 250°F) for C7035 C7035 129464N/U UV Power Tube (-40°F to 250°F) for C7035, C7061 C7061; C7035 129811B/U Socket Assembly w/NPT threads C7035 190971B/U 120 Vac Coil and Shutter Assembly for C7012E, F, C7061A, F C7012E, F; C7061A, F 190971D/F 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E 190971D/U 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E 190971F/U 100 Vac Coil and Shutter Assembly for C7076A, D C7076A, D 190971G/U 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961 C7024;C7961 190998A/U Aspiration assembly for C7076A C7076A 190999/U Grommet for C7076 Sensors C7076 191002D/U 220/240 Vac Plug in Electronics less UV Sensing Tube for C7076A C7076A 191002R/U 120 Vac Plug in Electronics less UV Sensing Tube for C7076D C7076D 191050/U Quartz Viewing Window for C7076 C7076 191053/U UV Sensing Tube for C7076 C7076 191054/U Housing Gasket for C7076 C7076 191203/0767/U Hinge for C7076A C7076 191284/U Aluminum Shield for C7035 C7035 191702/U Electronics less UV sensing tube for C7012F (120 Vac) C7012F 32004080-001/U 120 Vac Electronics less UV Sensing Tube and Shutter for C7012C C7012C 32004080-002/U 24 Vdc Plug in Electronics less UV Sensing Tube for C7024F C7024F 32007255-001/U Lead Sulfide Cell for C7915 C7915 32007439-001/U Mounting Bracket and screws for C7962B (3/8 in. NPT to 1/2 in. NPT) C7962B 390427B/U Envelope with Reducer bushing (1/2" to 3/8" NPT) C7027; C7015 50019469-001/U Magnifying Lens Assembly for C7915A C7915; C7015 70-6910 811 Commercial/Industrial Combustion Controls Pilot Burners Q179A, B Flame Rectifier Gas Pilots Q179A, B Gas Pilot Burner Assemblies use the flame rectification principle to prove the flame. Q179A, B are used in conjunction with a suitable electronic flame safeguard control on industrial or commercial gas and gas pilot ignited oil burners. • Q179A is a gas pilot assembly (with a flame electrode rod) and ignition electrode, making it suitable for applications requiring an interrupted or intermittent electrically ignited gas pilot burner. • Q179B has only the flame electrode and is suitable for use in continuous pilot applications. • Primary aerated type burner is equipped with stainless steel fins that provide the proper flame rod area to ground area ratio for maximum flame signal and flame stabilization. • Stainless steel electrode(s) are mounted in ceramic insulators, which permit electrode adjustment. • Rajah connectors facilitate disconnecting (A1126 has terminal screws). • Bracket permits side or end mounting. Type of Gas: Natural gas; Gas consumption – 2.0 cfh (0.06 m3/hr) Aeration: Primary Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm compression coupling Mounting: side or end mount Approximate, Dimensions: 4 5/8 in. high x 1 11/16 in. wide x 3 in. deep (118 mm high x 43 mm wide x 76 mm deep) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2 Approvals, Factory Mutual: Approved: Report No. 22961 Material Number Application Orifice Wiring Terminal Type Tip Style Includes Used With Q179A1001/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah I Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1035/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree right hand Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1050/U For Intermittent or Interrupted Ignition 0.028 in. dia. (0.711 mm dia.) Rajah T Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1076/U For Intermittent or Interrupted Ignition 0.028 in. dia. (0.711 mm dia.) Rajah 45 degree Y Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1092/U For Intermittent or Interrupted Ignition 0.028 in. dia. (0.711 mm dia.) Rajah 45 degree T Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1118/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left hand Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1126/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Screw Terminal I Flame electrode and ignition electrode with screw terminal connections Q624 or other suitable ignition transformer. Q179A1183/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah I Ignition Electrode Only Q624 or other suitable ignition transformer. Q179B1042/U For Continuous (Standing) pilot 0.025 in. dia. (0.635 mm dia.) Rajah T Flame electrode Q179B1109/U For Continuous (Standing) pilot 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left hand Flame electrode Q179B1117/U For Continuous (Standing) pilot 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree I Flame electrode 812 70-6910 Pilot Burners Q179C, D Miniature Rectifier Pilots Q179C, D Gas Pilot Burner Assemblies use the flame rectification principle to prove the flame. Q179C, D are used in conjunction with a suitable electronic flame safeguard control on industrial or commercial gas and gas pilot ignited oil burners. • Q179C is a gas pilot assembly (with a flame electrode rod) and ignition electrode, making it suitable for applications requiring an interrupted or intermittent electrically ignited gas pilot burner. • Q179D has only the flame electrode and is suitable for use in continuous pilot applications. • Primary aerated type burner is equipped with stainless steel fins that provide the proper flame rod area to ground area ratio for maximum flame signal and flame stabilization. • Stainless steel electrode(s) are mounted in ceramic insulators, which permit electrode adjustment. • Rajah connectors facilitate disconnecting. Aeration: Primary Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm compression coupling Wiring Terminal Type: Rajah Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MH9928, Guide No. MCUR2 Approvals, CSA: Certified: Master Report LR95329-1 Material Number Application Mounting Tip Style Orifice Approximate, Dimensions Includes Used With Type of Gas Q179C1009/U For Intermittent or Interrupted Ignition Dual Wing- Rear D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1025/U For Intermittent or Interrupted Ignition Single Wing- Rear L 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1033/U For Intermittent or Interrupted Ignition Dual Wing- Left Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1041/U For Intermittent or Interrupted Ignition Dual Wing- Right Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1058/U For Intermittent or Interrupted Ignition Single Wing- Left Side L 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1066/U For Intermittent or Interrupted Ignition Single Wing- Right Side K 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1090/U For Intermittent or Interrupted Ignition Dual Wing- Rear D 0.016 in. dia. (0.40 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. LP Q179D1008/U For Continuous (Standing) pilot Dual Wing- Rear D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural Q179D1016/U For Continuous (Standing) pilot Dual Wing- Left Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural Q179D1024/U For Continuous (Standing) pilot Dual Wing- Right Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural Q179D1057/U For Continuous (Standing) pilot Single Wing- Left Side L 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural 70-6910 813 Commercial/Industrial Combustion Controls Pilot Burners C7005 Flame Rectifier Pilots Gas Pilot Burner Assemblies include a flame rod to prove the pilot flame. The assemblies are used with a suitable flame safeguard control on industrial or commercial gas burners or oil burners with gas pilots. • Used with Honeywell controls using the flame rectification principle. • C7005A is for continuous pilot applications. • It includes an insulated flame rod, properly positioned relative to the flame retention type nozzle. C7005B is similar to C7005A, but includes an ignition electrode suitable for automatic, electric-spark ignition, gas pilot applications. • Individually mounted flame rod and ignition electrode in ceramic insulators allow the head assembly to fit inside a 3-inch pipe. • Stainless steel fins on the flame retention type pilot head provide the correct ratio of flame rod area to ground area for maximum flame signal, and are beneficial in stabilizing the pilot flame. • Pilot flame retention nozzle and mixing tube are threaded internally, 1/2-14 NPT and 3/8-18 NPT, respectively, and can be assembled with standard pipe fittings. • Pilot can be installed in vertical, horizontal, or inclined position. • Rajah connectors facilitate electrical connections. Connection Type: 1/2 in. NPT male thread Gas Fitting Wiring Terminal Type: Rajah Approximate, Dimensions: 3 in. diameter x 3 1/2 in. deep (76 mm diameter x 343 mm deep) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2 Approvals, Factory Mutual: Approved: Report No. 24181.04 Approvals, Swiss RE: Acceptable Material Number Application Orifice Includes Used With Type of Gas C7005A1037/U For Continuous (Standing) pilot 0.052 in. dia. Natural C7005B1035/U For automatic electrically ignited pilot 0.052 in. dia. Ignition electrode Q624 or other suitable ignition transformer. Natural C7005B1050/U For automatic electrically ignited pilot 0.028 in. dia. (0.711 mm dia.) Ignition electrode Q624 or other suitable ignition transformer. LP Commercial Pilot Burners Parts or Accessories Material Number Description Used With 100204B/U This Natural Gas Venturi Mixing Tube is used for C7005A and B C7005A, C7005B 101738/U This Insulator for Flame rod or Igniter is used with C7005A and B C7005A, C7005B 101738A/U This Ignition Assembly, including; electrode, bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B 101738B/U This Flame Rod Assembly, including; Kanthal Electrode, Bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B 101739/U This 4 in. Kanthal Ignition Electrode is used for C7005A and B C7005A, C7005B 101741/0020/U This 7/8 in. long Rajah Connector, with plug end, is used for C7005A and B C7005A, C7005B 101742/0021/U This Electrode Mounting Clip is used for C7005A and B C7005A, C7005B 101743/U This Mounting Bracket is used for C7005A and B C7005A, C7005B 103534/U This 8 in. Kanthal flame electrode is used with C7005A and C7005B C7005A, C7005B 104312/U This Rajah Connector for Flame Electrode is used with Q179A and B Q179A, Q179B 131065/U 131065 Adapts Q340 Thermal Couple to Q179B with 102462. Sold in custom packs Q179A, Q179B 133451A/U This T Port or LH 90 degree Flame Rod and Insulator, is used for Q179A and B Q179A, Q179B 37356/520/U This Rajah connector for ignition electrodes is used with Q179A, Q179B, Q179C, or Q179D Q179A, Q179B, Q179C, Q179D 388146KD/U This 0.016 in. diameter, LP Gas Spud Orifice, is used for Q179C and D. Sold in bulk packs Q179C, Q179D 395390-13/U This LP gas, 0.013 in. diameter Orifice, is used for Q179A and B Q179A, Q179B 395390-28/U This Natural gas, 0.028 in. diameter Orifice, is used for Q179A and B Q179A, Q179B R1061012/U This Ignition cable or Flame Rod Cable is rated at 350°F, 20,000 volts R.M.S. and used with C7005B, Q179A and Q179C C7005B, Q179A, Q179C R1298020/U This Cable Flame Rod Lead, is rated at 400°F, 600 volts R.M.S., and used with Q179 Q179 814 70-6910 Ignition Transformers Q624 Solid State Ignition Transformer Used to ignite pilots on commercial or industrial gas burners. • Ignite gas pilots with spark gaps up to 1/4 in. (6.5 mm). • Reliable light off with 15,000 peak voltage. • Prevent detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector. • For use only in interrupted ignition applications. • Mount in same space used by conventional ignition transformer. • Light weight, 3 lbs. (1.4 kg) versus 8-1/2 lbs. (3.9 kg) for standard transformers. Temperature Range: -40°F to +125°F Approximate, Dimensions: 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep (171.5 mm high x 108 mm wide x 76 mm deep) Weight lb. (kg): 3 lb (1.4 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized Approvals, CSA: Certified: File No. LR95329 Operating Humidity Range (% RH): 95% RH Accessories: 32004766-001/U – 24 inch Ignition Cable for Q624 and Q652 32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652 32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 32004766-004/U – 60 inch Ignition Cable with straight boots 32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot 32004766-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-001/U – 24 inch Ignition Cable for Q624 and Q652 50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652 50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 50060793-004/U – 60 inch Ignition Cable with straight boots 50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot 50060793-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-007/U – 36 inch ignition cable w/90 degree boot on one end only 50060793-008/U – Ignition Cable w/90 degree boot on one end only 50060793-009/U – Ignition Cable w/90 degree boot on one end only 50060793-010/U – Ignition Cable w/90 degree boot on one end only 50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 50060793-012/U – 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Dimensions in inches (millimeters) TERMINAL BOARD MOUNTING PLATE HIGH VOLTAGE ELECTRODE COVER SCREW KNOCKOUT FOR 1/2 INCH CONDUIT 1-1/4 (32) 13/16 (20.5) 5-1/4 (133.5) 19/64 (7) 4-1/4 (108) 1-1/4 (32) 3 (76) M20858 5-15/16 (151) 6-3/4 (171.5) Material Number Application Voltage Frequency Q624A1014/U Gas Ignition Transformer 120 Vac 50 Hz; 60 Hz 70-6910 815 Commercial/Industrial Combustion Controls Ignition Transformers Q652 Solid State Spark Generator Used to ignite gas burners in commercial and industrial applications. • Lightweight, 1 lb. (0.4 kg). • Include single high voltage electrode for gas applications. • For use with gas pilots with electrode spacings between 0.029 and 0.125 in. • Secondary Peak Voltage: 14Kv rms at 21Khz. • Mount in same space used by conventional ignition transformer. • For use only in interrupted ignition applications. • Prevent detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector. Temperature Range: 14°F to 113°F Approximate, Dimensions: 4 15/32 in. high x 2 15/16 in. wide x 2 9/32 in. deep (101.6 mm high x 77.5 mm wide x 58.4 mm deep) Weight lb. (kg): 1 lb (0.45 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized File MH14381 Approvals, CSA: LA66894 Operating Humidity Range (% RH): 90% RH Accessories: 32004766-001/U – 24 inch Ignition Cable for Q624 and Q652 32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652 32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 32004766-004/U – 60 inch Ignition Cable with straight boots 32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot 32004766-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-001/U – 24 inch Ignition Cable for Q624 and Q652 50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652 50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 50060793-004/U – 60 inch Ignition Cable with straight boots 50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot 50060793-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-007/U – 36 inch ignition cable w/90 degree boot on one end only 50060793-008/U – Ignition Cable w/90 degree boot on one end only 50060793-009/U – Ignition Cable w/90 degree boot on one end only 50060793-010/U – Ignition Cable w/90 degree boot on one end only 50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 50060793-012/U – 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Dimensions in inches (millimeters) M20870B 2-25/32 (71) 2-7/8 (73) 2-9/32 (59) 19 IN. (483 MM) LEAD WIRES HIGH VOLTAGE ELECTRODE 3-17/64 (83) 3-21/32 (95) 4-5/32 (106) 2-15/16 (78) Material Number Application Voltage Frequency Q652B1006/U Gas Ignition Transformer 120 Vac 60 Hz Q652B1014/U Solid State Ignitor Spark Generator-Gas Applications; 220V 60 Hz 220 Vac 60 Hz 816 70-6910 Ignition Transformers Ignition Transformer Accessories or Parts Material Number Description Used With 134666/510/U High voltage terminal insulator for Q652 and Q624 Q652; Q624 32004766-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624 32004766-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624 32004766-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624 32004766-004/U 60 inch Ignition Cable with straight boots Q652; Q624 32004766-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624 32004766-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624 32004766-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624 32004766-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624 32004766-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624 32004766-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624 32004766-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624 32004766-012/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624 4074BTN/U Bag assembly consisting of washer (103218), cap terminal (135793) and ferrule (37356) for Q624 Q624A 50060793-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624 50060793-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624 50060793-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624 50060793-004/U 60 inch Ignition Cable with straight boots Q652; Q624 50060793-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624 50060793-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624 50060793-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624 50060793-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624 50060793-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624 50060793-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624 50060793-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624 50060793-012/U 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624 50060793-013/U 48 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624 70-6910 817 Commercial/Industrial Combustion Controls Firing Rate Motors and Linkages M9484D, E, F; M9494D, F Modutrol® IV Motors Reversing, proportional motors used to drive burner firing rate valves, dampers or auxiliary equipment. Replaces M941A, C, D motors. • Designed for flame safeguard applications in commercial/industrial oil or gas burner system. • Vibration resistant electronic drive circuit. • Regulated by three-wire proportional controller. • Stroke is field-adjustable to 90 or 160 degrees. Frequency: 50 Hz; 60 Hz Stroke: Adjustable; 90 to 160 degrees, Symmetrical Power Consumption: 15 W Input Signal: 135 ohm Shaft Dimensions: double-ended, 3/8 in. square (double-ended, 9.5 mm square) Deadweight Load on Shaft: Either End – 200 lb (300 lb combined power and auxiliary shafts); 90.8 kg (136 kg combined power and auxiliary shafts) Approximate, Dimensions: 6.45 in high x 5.5 in wide x 7.3 in deep (164 mm high x 140 mm wide x 185 mm deep) Ambient Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. E4436, Guide No. XAPX for USA and Canada Supply Voltage: 24 Vac Accessories: Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly Valve. Includes 10 3/4 inch Linkage Rod. Material Number Torque Rating (lb-in.) Torque Rating (Nm) Additional Torque Ratings (lb-in.) Additional Torque Ratings (Nm) Internal Auxiliary Switch Auxiliary Switch Setting Auxiliary Switch Ratings Switch Ratings Timing Factory Stroke Setting M9484D1010/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 160 degrees M9484E1009/U 75 lb-in. 8.5 Nm Breakaway – 150 lb-in. Breakaway – 17.0 Nm 1 11 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 15 seconds, 160 degree stroke – 30 seconds 90 degrees M9484E1017/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 1 1 degree 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484E1033/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 1 7 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484F1007/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 7 and 80 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484F1023/U 75 lb-in. 8.5 Nm Breakaway – 150 lb-in. Breakaway – 17.0 Nm 2 At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 15 seconds, 160 degree stroke – 30 seconds 90 degrees 818 70-6910 Firing Rate Motors and Linkages Material Number Torque Rating (lb-in.) Torque Rating (Nm) Additional Torque Ratings (lb-in.) Additional Torque Ratings (Nm) Internal Auxiliary Switch Auxiliary Switch Setting Auxiliary Switch Ratings Switch Ratings Timing Factory Stroke Setting M9484F1031/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 7 and 80 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484F1049/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 35 and 120 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 160 degrees M9484F1057/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 53 seconds M9494D1000/U 300 lb-in. 34 Nm Breakaway – 600 lb-in. Breakaway – 68.0 Nm At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 60 seconds, 160 degree stroke – 120 seconds 90 degrees M9494F1003/U 300 lb-in. 34 Nm Breakaway – 600 lb-in. Breakaway – 68.0 Nm 2 At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 60 seconds, 160 degree stroke – 107 seconds 90 degrees Q100 Butterfly Valve Linkages Connects V51E valve to M9484 and M9494 Modutrol IV Motors with adapter plate. • Fits all sizes of V51E Valves. Mounts easily. Material Number Linkage Type Used with Actuator Includes Used With Q100B1006/U Butterfly Gas Valve Modutrol Motor 10 3/4 in. Linkage Rod all sizes V51E Gas Valve 70-6910 819 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V48A; V88A Diaphragm Gas Valves Dimensions in inches (millimeters) 1 2 1 2 BLEED TAPPING: 1/8-27 NPT. PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT FOR 2 THROUGH 3 IN. SIZES. M8487A E C A B D F APPROXIMATE DIMENSIONS VALVE SIZE (IN.) A B C D E F IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4-11/16 5-1/16 5-9/16 5-9/16 6-15/16 6-15/16 6-15/16 119.1 128.6 141.3 141.3 176.2 176.2 176.2 3/4 1 1-1/4 1-1/4 2-1/4 2-1/4 2-1/4 19.1 25.4 31.8 31.8 57.2 57.2 57.2 4-5/8 5 5-7/8 5-7/8 9-1/2 9-1/2 9-1/2 117.5 127.0 149.2 149.2 241.3 241.3 241.3 3-1/2 3-11/16 5-5/16 5-5/16 8-3/8 8-3/8 8-3/8 88.9 93.7 134.9 134.9 212.7 212.7 212.7 1-5/8 2-1/16 2-3/8 2-3/8 3-9/16 3-9/16 3-9/16 41.3 52.4 60.3 60.3 90.5 90.5 90.5 3-13/16 4-5/16 5-5/16 5-5/16 5-5/16 9-5/16 9-5/16 96.8 109.5 134.9 134.9 236.5 236.5 236.5 1-13/16 (46) 3-11/16 (94) Solenoid-operated diaphragm valves provide slow opening and fast closing suitable for controlling natural, LP or manufactured gases. They are normally used on atmospheric boilers, commercial water heaters, and rooftop heaters. • V48 for line voltage service; V88 for 24 Vac service. • Close firmly with diaphragm that is both weight and spring loaded. • Two second maximum closing time. • Valve closes on power failure; recommended for final shutoff service. • Set opening time with various sized bleed orifices or adjustable bleed valve. • Use with LP, natural or manufactured gases. • Made with cast aluminum in straight-through valve pattern. • Valve position indicator available for 1-1/4 in. V48A2227. Type of Fuel: Natural; LP; Manufactured Bleed Tapping: 1/8-27 NPT Body Pattern: Straight-through Valve Opening Time: 5 sec max Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Power Consumption: 9 W; 15 VA max Electrical Connections: 6 in. Leadwires Operating Temperature Range: 32°F to 125°F (0°C to 52°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5) Material Number Pipe Size (inch) Pipe Size (DN) Pilot Tapping Voltage Approximate, Dimensions Pressure Rating (psi) Pressure Rating (kPa) Current Ratings Comments Includes V48A2151/U 3/4 in. DN20 1/8-27 NPT 120 Vac 5 7/16 in. high x 3 13/16 in. wide x 4 5/8 in. deep (138 mm high x 97 mm wide x 118 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2169/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2177/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2185/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2227/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Includes position indicator Ground terminal V48A2243/U 2 in. DN50 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2250/U 2 1/2 in. DN65 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal 820 70-6910 Diaphragm Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Pilot Tapping Voltage Approximate, Dimensions Pressure Rating (psi) Pressure Rating (kPa) Current Ratings Comments Includes V48A2268/U 3 in. DN80 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2276/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2334/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2342/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V88A1618/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1626/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1634/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1659/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide x 4 5/8 in. deep (138 mm high x 97 mm wide x 118 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1667/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide x 4 5/8 in. deep (138 mm high x 97 mm wide x 118 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1675/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1683/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1691/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1709/U 2 in. DN50 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1717/U 2 1/2 in. DN65 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz 70-6910 821 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V48J; V88J High Temperature Diaphragm Gas Valves Dimensions in inches (millimeters) 1 2 1 2 BLEED TAPPING: 1/8-27 NPT. PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT FOR 2 THROUGH 3 IN. SIZES. M8487A E C A B D F APPROXIMATE DIMENSIONS VALVE SIZE (IN.) A B C D E F IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4-11/16 5-1/16 5-9/16 5-9/16 6-15/16 6-15/16 6-15/16 119.1 128.6 141.3 141.3 176.2 176.2 176.2 3/4 1 1-1/4 1-1/4 2-1/4 2-1/4 2-1/4 19.1 25.4 31.8 31.8 57.2 57.2 57.2 4-5/8 5 5-7/8 5-7/8 9-1/2 9-1/2 9-1/2 117.5 127.0 149.2 149.2 241.3 241.3 241.3 3-1/2 3-11/16 5-5/16 5-5/16 8-3/8 8-3/8 8-3/8 88.9 93.7 134.9 134.9 212.7 212.7 212.7 1-5/8 2-1/16 2-3/8 2-3/8 3-9/16 3-9/16 3-9/16 41.3 52.4 60.3 60.3 90.5 90.5 90.5 3-13/16 4-5/16 5-5/16 5-5/16 5-5/16 9-5/16 9-5/16 96.8 109.5 134.9 134.9 236.5 236.5 236.5 1-13/16 (46) 3-11/16 (94) Solenoid-operated diaphragm valves provide slow opening and fast closing suitable for controlling natural, LP or manufactured gases. They are normally used on atmospheric boilers, commercial water heaters, and rooftop heaters. • Rated for 150°F (66°C) maximum temperature applications. • V48 for line voltage service; V88 for 24 Vac service. • Close firmly with diaphragm that is both weight and spring loaded. • Two second maximum closing time. • Valve closes on power failure; recommended for final shutoff service. • Set opening time with various sized bleed orifices or adjustable bleed valve. • Use with LP, natural or manufactured gases. • Made with cast aluminum in straight-through valve pattern. Type of Fuel: Natural; LP; Manufactured Bleed Tapping: 1/8-27 NPT Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through Valve Opening Time: 5 sec max Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Electrical Connections: 6 in. Leadwires Operating Temperature Range: 32°F to 150°F (0°C to 66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5) Pressure Ratings (psi): 1 psi Pressure Ratings (kPa): 6.9 kPa Current Ratings: 0.62 max amps at rated Vac/Hz Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption V88J1006/U 1 in. DN25 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 9 W; 15 VA max V88J1022/U 1 1/4 in. DN32 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 9 W; 15 VA max 822 70-6910 Diaphragm Gas Valves V4943/V8943A On/Off Diaphragm Gas Valves V4943A/V8943A are on/off diaphragm gas valve used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters. • Designed for replacement for V4843A/V8843A Gas Valves. • Suitable for use on atmospheric boilers, commercial water heaters, and rooftop heaters. • V8943A/V4943A models are solenoid-operated diaphragm valves for on/off flow control of natural or LP gas. • Valve body of die-cast aluminum with a straight-through pattern. • V4943 are used with line voltage, on/off controllers; V8943A are used with 24 Vac thermostats or controllers. • Valve closes on power failure; recommended for final shutoff service. Type of Fuel: Natural; LP Bleed Tapping: Internal Bleed Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through, non-offset Opening Characteristics: Rapid Opening On-Off Valve Opening Time: 6 sec max Valve Closing Time: 3 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Electrical Connections: 1/4 in. (6 mm) spade terminals (quick connects). 30 in. (762 mm) leadwires and cover for electrical conduit connection provided. Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ (60 Hz only) Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3371-03, 83 (Z21.21, Z21.78) Pressure Ratings (psi): 1/2 psi Pressure Ratings (kPa): 3.4 kPa Comments: (2) 30" leadwires Current Ratings: 0.055 max amps at rated Vac/Hz Dimensions in inches (millimeters) 6-9/16 (167) FOR 1, 1-1/4 OR 7-3/8 (187) FOR 1-1/2, 2 SIDE VIEW 6 (152) 6 (152) TOP VIEW M23232 VENT CONNECTIONS (V4944/V8944 HAVE TWO) Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption V4943A1011/U 1 in. DN25 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 VA max V4943A1029/U 1 1/4 in. DN32 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 VA max V4943A1037/U 1 1/2 in. DN40 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 VA max V4943A1045/U 2 in. DN50 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 VA max V8943A1012/U 1 in. DN25 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 8 VA max V8943A1020/U 1 1/4 in. DN32 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 8 VA max V8943A1038/U 1 1/2 in. DN40 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 8 VA max V8943A1046/U 2 in. DN50 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 8 VA max 70-6910 823 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V4943/V8943B, C, N Single Stage Pressure Regulating Valves V4943B, N/8943B, C, N are Single-stage Pressure Regulating Valves. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters. • Designed for replacement for V4843/V8843 Gas Valves. • Suitable for use on atmospheric boilers, commercial water heaters, and rooftop heaters. • V4943/V8943B, C, N models are solenoid-operated diaphragm valves that combine the functions of safety shutoff and pressure regulation in a single unit. • V4943/V8943B, N are for use with natural gas. • V4943/V8943C are for use with LP gas. • Valve body of die-cast aluminum with a straight-through pattern. • V4943 are used with line voltage, on/off controllers; V8943 are used with 24 Vac thermostats or controllers. • Valve closes on power failure; recommended for final shutoff service. Bleed Tapping: 5/16-24 UNF Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through, non-offset Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Electrical Connections: 1/4 in. (6 mm) spade terminals (quick connects). 30 in. (762 mm) leadwires and cover for electrical conduit connection provided. Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ (60 Hz only) Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01, 81 (Z21.21, Z21.78) Pressure Ratings (psi): 1/2 psi Pressure Ratings (kPa): 3.4 kPa Comments: (2) 30" leadwires Dimensions in inches (millimeter) 6-9/16 (167) FOR 1, 1-1/4 OR 7-3/8 (187) FOR 1-1/2, 2 SIDE VIEW 6 (152) 6 (152) TOP VIEW M23232 VENT CONNECTIONS (V4944/V8944 HAVE TWO) Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Voltage Approximate, Dimensions Valve Opening Time Current Ratings Pressure Regulator Setpoint (in. wc) Power Consumption V4943B1019/U Natural 1 in. DN25 Slow Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max; 6.6 VA V4943B1027/U Natural 1 1/4 in. DN32 Slow Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943B1035/U Natural 1 1/2 in. DN40 Slow Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943B1043/U Natural 2 in. DN50 Slow Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943N1012/U Natural 1 in. DN25 Rapid Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943N1020/U Natural 1 1/4 in. DN32 Rapid Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max 824 70-6910 Diaphragm Gas Valves Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Voltage Approximate, Dimensions Valve Opening Time Current Ratings Pressure Regulator Setpoint (in. wc) Power Consumption V4943N1038/U Natural 1 1/2 in. DN40 Rapid Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943N1046/U Natural 2 in. DN50 Rapid Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V8943B1010/U Natural 1 in. DN25 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943B1028/U Natural 1 1/4 in. DN32 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943B1036/U Natural 1 1/2 in. DN40 Slow Opening 1-stage 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943B1044/U Natural 2 in. DN50 Slow Opening 1-stage 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943C1018/U LP 1 in. DN25 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, High Fire – 10.0 in. wc 9 VA max V8943C1026/U LP 1 1/4 in. DN32 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, High Fire – 10.0 in. wc 9 VA max V8943N1013/U Natural 1 in. DN25 Rapid Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943N1021/U Natural 1 1/4 in. DN32 Rapid Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943N1039/U Natural 1 1/2 in. DN40 Rapid Opening 1-stage 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max 70-6910 825 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V4944/V8944B, C, L, N Two Stage Pressure Regulating Gas Valves V4944B, L, N/8944B, C, L, N are Two-stage Pressure Regulating Gas Valves. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters. • Designed for replacement for V4844/V8844 Gas Valves. • Suitable for use on atmospheric boilers, commercial water heaters, and rooftop heaters. • V4944/V8944B, C, L, N models are solenoid-operated diaphragm valves that combine the functions of safety shutoff and pressure regulation in a single unit. • V4944/V8944B, N are for use with natural gas. • V4944/V8944C, L are for use with LP gas. • Valve body of die-cast aluminum with a straight-through pattern. • V4944 are used with line voltage, dual-stage controllers; V8944 are used with 24 Vac dual-stage thermostats or controllers. • Valve closes on power failure; recommended for final shutoff service. Bleed Tapping: Two 5/16-24 UNF Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through, non-offset Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Voltage: V4944-120 Vac; V8944-24 Vac Frequency: 60 Hz Power Consumption: V4944-9 VA max; V8944-12.4 VA max Electrical Connections: 1/4 in. (6 mm) spade terminals (quick connects), leadwires and cover for electrical conduit connection provided. Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ (60 Hz only) Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01, 81 (Z21.21, Z21.78) Pressure Ratings (psi): 1/2 psi Pressure Ratings (kPa): 3.4 kPa Current Ratings: V4944-0.077 max amps at rated Vac/Hz; V8944-0.516 max amps at rated Vac/Hz Dimensions in inches (millimeter) 6-9/16 (167) FOR 1, 1-1/4 OR 7-3/8 (187) FOR 1-1/2, 2 SIDE VIEW 6 (152) 6 (152) TOP VIEW M23232 VENT CONNECTIONS (V4944/V8944 HAVE TWO) Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Valve Opening Time Pressure Regulator Setpoint (in. wc) Comments V4944B1018/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944B1026/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944B1059/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.7 in. wc; Factory Setting, High Fire – 3.0 in. wc (3) 30" leadwires V4944B1075/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.6 in. wc; Factory Setting, High Fire – 3.5 in. wc V4944B1091/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.6 in. wc; Factory Setting, High Fire – 3.5 in. wc V4944L1024/U LP 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires 826 70-6910 Diaphragm Gas Valves Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Valve Opening Time Pressure Regulator Setpoint (in. wc) Comments V4944N1011/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1029/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1037/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1045/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1060/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.0 in. wc; Factory Setting, High Fire – 3.0 in. wc (3) 85" leadwires V8944B1019/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944B1027/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944B1035/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944B1043/U Natural 2 in. DN50 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944C1017/U LP 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires V8944C1025/U LP 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires V8944C1033/U LP 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires V8944N1012/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1020/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1038/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1046/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1053/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.2 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1061/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.2 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires 70-6910 827 Commercial/Industrial Combustion Controls Diaphragm Gas Valves Diaphragm Gas Valve Replacement Parts or Accessories Material Number Description Used With 116930/U 24 Vac, 60 Hz Replacement Coil for V88A Solenoid Operated Valve V88A 116931/U 120 V/60 Hz Replacement Coil for V48A Solenoid Operated Valve V48; V48A 116932/U 220-240 V/50-60 Hz Replacement Coil for V48A Solenoid Operated Valve V48A 118888/U 24V 60 Hz Replacement Coil for V88J V88J 122160/U Orifice - .018" for V48, V88 V48, V88 124674/U Orifice - .011" for V48, V88 V48, V88 126590/U Adjustable Bleed Valve Assembly for V48, V88, V4004. V8004. 1/8 in. NPT to 1/4 in. compression fitting V48, V88 204480/U Regulator vent pipe fitting to be used with V4843/V8843B, C, L, N and V4844/ V8844B, C, L, N and V4943/V8943, V4944/V8944 V4843B; V4843C; V4843L; V4843N; V8843B; V8843C; V8843L; V8843N; V4844B; V4844C; V4844L; V4844N; V8844B; V8844C; V8844L; V8844N; V4943; V8943; V4944; V8944 828 70-6910 Butterfly Gas Valves V51 Butterfly Gas/Air Valve Provides modulating control of natural, manufactured, LP gases or air. • Use in commercial and industrial installations where large amounts of gas must be closely controlled. • NOT for use as safety shutoff valve. • Adaptable to most modulating jobs. • Modutrol motor, such as the M9484 or M9494, may be mounted directly on valve or close to it. • Valve mechanism has strain release. • Adjustable stroke over low fire-high fire range. • Straight-through valve pattern. • Rugged cast aluminum body provides durability and maintenancefree operation. Type of Fuel: Air; natural; manufactured; LP Body Pattern: Straight-through Mounting: Motor shaft horizontal Materials: Body – Aluminum Operating Temperature Range: 32°F to 140°F (0°C to 60°C) Approvals, Underwriters Laboratories Inc.: File No. MH5968 Vol. 1 Sec. 1, Guide no. MHKZ Pressure Ratings (psi): 5 psi Pressure Ratings (kPa): 34.5 kPa Used With: Mod Motor with Q100 Linkage Accessories: 32003396-001/U – V51E mounting kit for 1-1/2 and 2 in. valve actuators includes brackets and hardware 32003396-002/U – V51E mounting kit for 2-1/2, 3 and 4 in. valve actuators includes brackets and hardware Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly Valve. Includes 10 3/4 inch Linkage Rod. Dimensions in inches (millimeter) VALVE SIZE (in.) 1 1/2 2 2 1/2 3 4 2 21/32 3 5/32 3 27/32 4 1/32 5 21/64 67.5 80.2 97.6 102.4 135.3 A A 1 in. mm 1 9/16 1 13/16 2 5/16 2 25/64 3 5/32 39.7 46.0 58.7 60.7 80.2 B B in. mm 4 1/4 4 1/4 4 13/16 5 5 3/8 108.0 108.0 122.2 127.0 136.5 C C in. mm 3 1/32 3 17/32 4 23/32 4 23/32 5 17/64 77.0 89.7 119.9 119.9 133.8 D D in. mm M9532A 1 2 1 1 MAXIMUM DIMENSIONS. 2 NOMINAL DIMENSIONS. V51E DIMENSIONS Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Pressure Tapping Approximate, Dimensions V51E1000/U 1 1/2 in. DN40 4200 cfh 118.9 m3/hr Inlet and outlet pressure taps – Two downstream 1/4 in. NPT taps 2 11/16 in. high x 3 1/16 in. wide x 5 13/16 in. deep (68 mm high x 77 mm wide x 148 mm deep) V51E1018/U 2 in. DN50 9210 cfh 260.7 m3/hr 3 3/16 in. high x 3 9/16 in. wide x 6 1/16 in. deep (80 mm high x 90 mm wide x 154 mm deep) V51E1034/U 2 1/2 in. DN65 8390 cfh 199.8 m3/hr 3 7/8 in. high x 4 3/4 in. wide x 7 1/8 in. deep (98 mm high x 120 mm wide x 181 mm deep) V51E1059/U 3 in. DN80 14640 cfh 414.5 m3/hr 4 1/16 in. high x 4 3/4 in. wide x 7 3/8 in. deep (102 mm high x 120 mm wide x 188 mm deep) V51E1075/U 4 in. DN100 33000 cfh 934.2 m3/hr 5 3/8 in. high x 5 1/4 in. wide x 8 9/16 in. deep (135 mm high x 134 mm wide x 217 mm deep) 70-6910 829 Commercial/Industrial Combustion Controls Butterfly Gas Valves V5197 Integrated Valve Train Butterfly Gas Valve Dimensions in inches (millimeters) 10-5/16 (277) 4-27/32 (123) 6-7/16 (165) 2-1/2 (64) 7-1/8 (181) 3-25/32 (96) M17528 The V5197A valve provides flow control of air, natural gas, liquid petroleum, & manufactured gases which require a high turn down ratio. The adjustment screw controls the maximum flow of gas, but keeps the linear modulating characteristics & stroke. • Used with air, natural, manufactured or liquefied petroleum (LP) gases. • For modulating applications that do not require final shutoff service of firing rate valve. • Two valve body types (small and large) applicable to seven pipe sizes: Small body type for 3/4 in. (19 mm), 1 in. (25 mm), 1-1/4 in. (32 mm), 1-1/2 in. (38 mm) and 2 in. (51 mm) pipes, NPT or ISO 7 threads. Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm) and 3 in. (76 mm) pipes, NPT or ISO 7 threads. • Two downstream 1/4 in. NPT threaded pressure taps available. • Accepts C6097 Pressure Switch mounted directly to flange (downstream pressure tap only). • Unpainted cast aluminum body. • Suitable for electric or pneumatic operators with the appropriate linkage. • May be used with manufacturers own linkage and drive motor. • Flow adjustment screw on bottom of valve controls maximum flow. • Visual position indicator. Type of Fuel: Air; natural; manufactured; LP Pressure Tapping: Inlet and outlet pressure taps – Two downstream 1/4 in. NPT taps Mounting: Directly bolted to Integrated Valve Train (IVT) components or IVT adapters Materials: Body – Die-cast aluminum Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: Component Listed Approvals, CSA: Design Certified Approvals, Swiss RE: Acceptable Pressure Ratings (psi): 15 psi max Pressure Ratings (kPa): 1 Bar Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions V5197A1003 3/4 in.; 1 in.; 1 1/4 in.; 1 1/2 in.; 2 in. DN20; DN25; DN32; DN40; DN50 2450 cfh for 3/4 in.; 3080 cfh for 1 in.; 4430 cfh for 1 1/4 in.; 5010 cfh for 1 1/2 in.; 5480 cfh for 2 in. 51 mm is 155/ 38 mm is 142/ 32 mm is 125/ 25 mm is 87/ 19 mm is 69 10 5/16 in. high x 6 7/16 in. wide x 7 11/32 in. deep (277 mm high x 165 mm wide x 187 mm deep) V5197A1011 2 in.; 2 1/2 in.; 3 in. DN65; DN80; DN50 12,600 cfh for 2 in.; 14,800 cfh for 2 1/2 in.; 16,900 cfh for 3 in. 76 mm is 478/ 64 mm is 419/ 51 mm is 356 12 11/16 in. high x 9 1/4 in. wide x 8 13/16 in. deep (322 mm high x 235 mm wide x 224 mm deep) Firing Rate Gas Valve Parts Material Number Description Used With 49084/0021/U Adjusting arm for V51E. V51E 49085B/U Strain Release Assembly V51E 830 70-6910 Gas Valve Actuators Selection Chart: V5055 and V5097 Industrial Gas Valves with V4055, V4062 or V9055 Fluid Power Actuators The chart below describes every model of V5055 or V5097 Valve in the left column, and every model of Fluid Power Actuator across the top. While it’s possible to combine any valve with any actuator, we’ve marked the recommended valve/actuator combinations which cover most applications with a •. Each valve described in the left column is available: • In these sizes: 3/4 to 3 in. (NPT or parallel BSP). V5055A, B, C are also available in 4 in. size (flange connection only). • With upstream and/or downstream tap. Options available on some Fluid Power Actuators include: • Damper arm shaft, with or without spring return. • NEMA 4 enclosure. • Fast or slow open time (13 or 26 seconds). • Auxiliary switch. • Valve seal overtravel interlock switch. For complete specifications and ordering information on V5055 and V5097 Valves and V4055, V4062 and V9055 Fluid Power Actuators, refer to Index for specific page numbers. Fluid Power Actuators/ Industrial Gas Valves Standard pressurea High Pressurea V5055A, Fb, V5097A V5055B, V5097B V5055C, V5097C V5055D, V5097D V5055E, V5097E Type Model Pressure Ratinga On-Off Characterized Guidec VSOId On-Off VSOId V4055 On-Off A, Ge Standard • • • B High • f • f • Dd Fd e Standard • • Ed High • f • V4062 Hi-Lo-Off A Standard • • B High • f • f • Dd Standard • V9055 Modulating A Standard • Dd Standard • a Refer to the table below for actual pressure ratings of the various combinations of valves and actuators. b V5055F models meet EN161 leakage requirements. c Characterized guide provides a more linear relationship between stem travel and gas flow. Check Honeywell form 70-8311 to verify that flow curve characteristics match application requirements. d Valve Seal Overtravel Interlock. Valve has two shutoff seals, actuator has a proof-of-closure switch. e V4055F, G models include switch for manual control. f These combinations have higher pressure ratings; see the table below. The following combinations of V5055 and V5097 Valves, and V4055, V4062 and V9055 Fluid Power Actuators are approved by these agencies. Underwriters Laboratories, Inc: Listed: MH1639 V4055A/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055B/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055E/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055F/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.). V4055G/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.). V4062A, D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V9055A, D/V5055A, B, C, E (3/4-4 in.) or V5097A-E (3/4-3 in.). Factory Mutual Approved: Report No. 20698, 20835, 21172 and 24061: Valve Actuator Approvals: V4055A/V5055A and V5097A. V4055D/V5055C and V5097C. V4055A/V5055B and V5097B. V4055B/V5055D and V5097D. V4055E/V5055E and V5097E. V4055F/V5055Ca and V5097C. V4055G/V5055A, Ba and V5097A, B. V9055A/V5055B, C and V5097B, C. a Manual reset safety shut-off valves. Pressure Ratings of Valve-Actuator Combinations Model Pipe Size Standard Pressure Actuators V4055A, D, F, G, V4062A, D, V9055A, D High Pressure Actuators V4O55B, E, V4062B M.O.P.D. a Max. Rated Pressure b M.O.P.D. a Max. Rated Pressure b Standard Pressure Valves V5055A, B, C, F, V5097A, B, C 3/4" to 1-1/2" c 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar 2" to 3" d 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar 4" flanged e 3 PSI 207 mbar 15 PSI 1.0 Bar 5 PSI 340 mbar 15 PSI 1.0 Bar High Pressure Valves V5055D, E, V5097D, E 3/4" to 1-1/2" c 5 PSI 340 mbar 75 PSI 5.0 Bar 25 PSI 1720 mbar 75 PSI 5.0 Bar 2" to 3" d 5 PSI 340 mbar 45 PSI 3.0 Bar 15 PSI 1030 mbar 45 PSI 3.0 Bar a Max Operating Pressure Differential (UL) or Max Operating Pressure (CSA); maximum allowable pressure drop from inlet to outlet for proper operation. b Max Rated Pressure (UL) or Max Close-off Pressure (CSA); maximum pressure that the valve can be exposed to without leakage or damage to the valve. c Applies for small-body V5097 valves 3/4” up to 2” pipe size. d Applies for large-body V5097 valves 2” up to 3” pipe size. e V5055A, B, C only. 70-6910 831 Commercial/Industrial Combustion Controls Gas Valve Actuators V4055A, B, D, E On-Off Fluid Power Gas Valve Actuator Use in combination with V5055 or V5097 Gas Valves to control gas supply to commercial and industrial burners. • Use where smooth light off is important. • One-second maximum closing time. • Continuously displays the valve position with a red indicator when open and a yellow indicator when closed. • Mount in any position directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Operating Temperature Ratings: 60 Hz Models: -40°F to +150°F (-40°C to +66°C). 50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to +70°C). Contact Ratings: V4055D, E ONLY-Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp Used With: V5055; V5097 Gas Valves Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ Approvals, Factory Mutual: V4055A-When used with the V5055A, B or V5097A, B: Approved, Report Nos. 20698, 20835, 21172, and 24061; V4055B, D, E-When used with the V5055D or V5097D: Approved, Report Nos. 20698, 20835, 21172, and 24061 Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Dimensions in inches (millimeters) B A 1 1 (32.5) KNOCKOUT FOR 1/2 INCH CONDUIT (4) 5 (127.0) 1-9/32 27/32 (21.4) 3-23/32 (94.5) 6-3/4 (171.5) ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL. M10981A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 — 283 283 283 283 298 298 298 — 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 — 70 70 70 70 86 86 86 — DIM A V5055 V5097 IN. MM DIM B IN. MM DIM A IN. MM DIM B IN. MM VALVE VALVE Material Number Electrical Ratings Frequency Timing Internal Auxiliary Switch Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Auxiliary Switch Ratings Comments Includes V4055A1007/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa V4055A1031/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa V4055A1064/U 120 Vac 50 Hz; 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1080/U 240 Vac 50 Hz; 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1098/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1114/U 240 Vac 50 Hz; 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1296/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec Yes - adjusted to 90% stroke 5 psi 34 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp V4055A1304/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft with return spring installed V4055A1312/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Nema 4 Enclosure V4055B1021/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Damper Shaft V4055B1039/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Damper Shaft 832 70-6910 Gas Valve Actuators Material Number Electrical Ratings Frequency Timing Internal Auxiliary Switch Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Auxiliary Switch Ratings Comments Includes V4055B1088/U 220 Vac 50 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa V4055D1001/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055D1019/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055D1027/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec Yes 5 psi 34 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Nema 4 Enclosure V4055D1035/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec Yes 5 psi 34 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp V4055D1043/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa V4055E1016/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Damper Shaft V4055E1024/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec Yes 15 or 25 psi 103 or 172 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Nema 4 Enclosure Damper Shaft V4055E1040/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Nema 4 Enclosure Damper Shaft 70-6910 833 Commercial/Industrial Combustion Controls Gas Valve Actuators V4055F, G Manual Reset Safety Shut-off Gas Valve Actuators Provide manual reset, safety shut-off functions as required on FM, IHEA-IRI and NFPA 86A,B,C industrial furnaces, ovens and kilns. Use with V5055 or V5097 Gas Valves to control gas supply. • Close in one second maximum. • Continuously displays the valve position with a red indicator when closed. • Mount directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Frequency: 60 Hz Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Dimensions in inches (millimeters) B A 1 1 (32.5) KNOCKOUT FOR 1/2 INCH CONDUIT (4) 5 (127.0) 1-9/32 27/32 (21.4) 3-23/32 (94.5) 6-3/4 (171.5) ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL. M10981A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 — 283 283 283 283 298 298 298 — 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 — 70 70 70 70 86 86 86 — DIM A V5055 V5097 IN. MM DIM B IN. MM DIM A IN. MM DIM B IN. MM VALVE VALVE Material Number Electrical Ratings Internal Auxiliary Switch Timing Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Contact Ratings Description Approvals, Factory Mutual Used With V4055F1006/U 120 Vac No Opening – 13 sec; Closing – < 1 sec 5 psi 34 kPa Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp Manual reset safety shutoff valve with proof of closure switch. When used with the V5055D or V5097D: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 V4055G1004/U 120 Vac No Opening – 13 sec; Closing – < 1 sec 5 psi 34 kPa Manual ON-OFF actuator normally used with V5055/V5907A, B valve bodies. Low pressure. When used with the V5055A, B or V5097A, B: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 834 70-6910 Gas Valve Actuators V4062 Off-Lo-Hi Fluid Power Gas Valve Actuators Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand. • Provide final safety shutoff service when used with V5055 or V5097 gas valve. • One-second maximum closing time. • Continuously displays the valve position with a red indicator when open and a yellow indicator when closed. • Mount in any position directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Electrical Ratings: 120 Vac Frequency: 60 Hz Maximum Safe Operating Pressure (psi): 5 psi Maximum Safe Operating Pressure (kPa): 34 kPa Temperature Range: -40°F to +150°F (-40°C to +66°C) Used With: V5034; V5055; V5097; VE5000 Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Dimensions in inches (millimeters) B A 1 1 (32.5) KNOCKOUT FOR 1/2 INCH CONDUIT (4) 5 (127.0) 1-9/32 27/32 (21.4) 3-23/32 (94.5) 6-3/4 (171.5) ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL. M10981A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 — 283 283 283 283 298 298 298 — 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 — 70 70 70 70 86 86 86 — DIM A V5055 V5097 IN. MM DIM B IN. MM DIM A IN. MM DIM B IN. MM VALVE VALVE Material Number Internal Auxiliary Switch Timing Contact Ratings Auxiliary Switch Range Description Comments Includes V4062A1008/U No Opening – 26 sec; Closing – < 1 sec Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft V4062A1123/U Yes Opening – 26 sec; Closing – < 1 sec 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft with return spring installed V4062A1131/U No Opening – 13 sec; Closing – < 1 sec Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft V4062A1156/U No Opening – 26 sec; Closing – < 1 sec Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies For Series 60 Floating Control V4062A1198/U Yes - adjusted to 90 degree stroke Opening – 13 sec; Closing – < 1 sec 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft with return spring installed V4062D1002/U No Opening – 26 sec; Closing – < 1 sec Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp HI-LO-OFF actuator with Proof of Closure normally used on V5055C, E/V5907C, E valve bodies (Low Pressure) Damper Shaft V4062D1010/U No Opening – 13 sec; Closing – < 1 sec Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp HI-LO-OFF actuator with Proof of Closure normally used on V5055C, E/V5907C, E valve bodies (Low Pressure) Damper Shaft 70-6910 835 Commercial/Industrial Combustion Controls Gas Valve Actuators V9055 Modulating Fluid Power Gas Valve Actuators Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand. • Include integral shaft to drive combustion air damper in unison with valve. • One-second maximum closing time. • Continuously displays the valve position with a red indicator when open and a yellow indicator when closed. • Mount in any position directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Frequency: 60 Hz Temperature Range: -40°F to +125°F (-40°C to +52°C) Internal Auxiliary Switch: No Includes: Damper Shaft Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A, B, C, E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.) Listed MH1696 Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Accessories: 203422C/U – 4-20 ma Adapter for V9055 Material Number Electrical Ratings Comments Timing Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Contact Ratings Description Approvals, Factory Mutual Used With V9055A1055/U 120 Vac Opening – 26 sec; Closing – < 1 sec 5 psi 34 kPa Low pressure Modulating-OFF actuator for use with V5055B valve bodies When used with the V5055B, C or V5097B, C: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 V9055A1063/U 120 Vac Nema 4 Enclosure Opening – 26 sec; Closing – < 1 sec 5 psi 34 kPa Low pressure Modulating-OFF actuator for use with V5055B valve bodies When used with the V5055B, C or V5097B, C: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 V9055D1000/U 120 Vac Opening – 26 sec; Closing – < 1 sec 5 psi 34 kPa Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp Low pressure Modulating-OFF actuator with Proof of Closure normally used on V5055C, E/V5907C, E valve bodies. V5034; V5055; V5097; VE5000 836 70-6910 Gas Valve Actuators Dimensions in inches (millimeters) B E F C D G A 1 3 D 1/4 INCH NPT DOWNSTREAM TAP AND PLUG 1/4 INCH NPT UPSTREAM TAP AND PLUG (1/4 BSP ON INTERNATIONAL MODELS) 2 1 2 3 [32.5] KNOCKOUT FOR1/2 INCH CONDUIT (4) OCTAGON 3/4 [19.1] BOLT HOLES (8) ON 3-3/4 (95) RADIUS 1 9 32 1 3 16 [30] 9 3 16 [233] 27 32 [21.5] 3 23 32 5 [94.5] 3 [127.0] 19 32 [91] 6 3 4 [171.5] 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-13/16 8-13/16 11-7/32 5-3/4 5-3/4 5-3/4 5-3/4 8-3/8 9-1/4 9-1/4 12-1/2 13-1/8 13-1/8 13-1/8 13-1/8 13-1/4 13-3/4 13-3/4 16-3/16 2-13/16 2-13/16 2-13/16 2-13/16 3-1/2 4-1/2 4-1/2 — 333.4 333.4 333.4 333.4 336.5 349.3 349.3 411.0 DIM A IN. MM DIM B IN. MM DIM C IN. MM DIM D IN. MM DIM E IN. MM DIM F IN. MM DIM G OCTAGON IN. MM IN. MM ALLOW 4 INCHES CLEARANCE FOR ACTUATOR REMOVAL. ADD 1/8 INCH TO DIMENSION FOR MODELS WITH NEMA 4 ENCLOSURE. ADD 1/4 INCH TO DIMENSION A FOR MODELS WITH NEMA 4 ENCLOSURE. M7321 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 208.0 208.0 208.0 208.0 211.1 223.8 223.8 285.0 146.1 146.1 146.1 146.1 212.7 235.0 235.0 317.5 2-1/4 2-1/4 2-1/4 2-1/4 2-3/4 2-3/4 2-3/4 4-5/8 57.2 57.2 57.2 57.2 69.9 69.9 69.9 117.5 4-13/16 4-13/16 4-13/16 4-13/16 7-19/32 7-19/32 7-19/32 — 122.2 122.2 122.2 122.2 192.9 192.9 192.9 — 71.4 71.4 71.4 71.4 88.9 114.3 114.3 — Fluid Actuator Accessories and Parts Material Number Description Used With 133568/U Auxiliary Switch (Adjustable Valve Position) for V4055, V4062 or V9055 V4055; V4062; V9055 133569/U Replacement Pre-ignition Interlock (Proof of Closure) Switch for V4055D, E; V4062D or V9055D V4055; V4062; V9055 203422C/U 4-20 ma Adapter for V9055 V9055 7616BR/U Crank Arm assembly with clip for Damper Arm of V4055, V4062 or V9055 V4055; V4062; V9055 70-6910 837 Commercial/Industrial Combustion Controls Industrial Gas Valves V5055 Industrial Gas Valves Safety shutoff valves used with V4055, V4062 and V9055 fluid power actuators to control gas flow to commercial and industrial burners. • Use with natural or LP gases. • Mount directly in gas supply line. • Include 1/4 in. NPT upstream and downstream taps and plug. • 4 in. models have only flanged connections. • V5055 normally closed valves are rated for final shutoff service safety shutoff. • V5055A, C, D, E Valves are for On-Off service. • V5055B Valve has a characterized guide and in combination with the V4055, V4062, and V9055 Fluid Power Actuators, provides slowopening, hi-lo-off, and modulating functions respectively. • V5055C, E, F Valves have a double seal and are used with V4055D, E Actuators to provide proof-of-closure switch and valve seal overtravel interlock. • V5055D, E, F Valves are for high pressure applications. Operating Temperature Range: -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C) Approvals, Underwriters Laboratories Inc.: When used with V4055A, B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ Approvals, CSA: When used with V4055, V4062, and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Swiss RE: When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 Used With: V9055; V4055; V4062 Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055A1004/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1012/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055A1020/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055A1038/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1046/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1053/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1228/U 4 in. DN100 10200 cfh 288.8 m3/hr Flanged With V4055A, D or V4062 – 3 psi (20.7 kPa); With V4055B or E – 5 psi (340 mbar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1343/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug 838 70-6910 Industrial Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055B1002/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1010/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055B1028/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055B1069/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1077/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1085/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1150/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062 – 3 psi (20.7 kPa); With V4055B or E – 5 psi (340 mbar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1000/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1018/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1026/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055C1034/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1042/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug 70-6910 839 Commercial/Industrial Combustion Controls Industrial Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055C1059/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1109/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062 – 3 psi (20.7 kPa); With V4055B or E – 5 psi (340 mbar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1182/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055D1008/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1016/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1024/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1032/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1040/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1057/U 3 in. DN80 5230 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1065/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055E1005/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055E1013/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055E1021/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055E1039/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug 840 70-6910 Industrial Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055E1047/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055E1054/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055E1062/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055F1003/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Meets Intent of DIN Seat Leakage Requirements 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055F1011/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Meets Intent of DIN Seat Leakage Requirements 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055F1037/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Meets Intent of DIN Seat Leakage Requirements 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug Dimensions in inches (millimeters) B E F C D A 1 1/4 INCH NPT DOWNSTREAM TAP AND PLUG 1 KNOCKOUT FOR1/2 INCH CONDUIT (4) OCTAGON 5 (127) 27/32 (21) 3-23/32 (95) 6-3/4 (172) ALLOW 2 IN. (51 mm) CLEARANCE FOR ACTUATOR REMOVAL. M27268A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 283 283 283 283 286 299 299 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 70 70 70 70 73 86 86 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-13/16 8-13/16 208 208 208 208 211 224 224 5-3/4 5-3/4 5-3/4 5-3/4 8-3/8 9-1/4 9-1/4 146 146 146 146 213 235 235 2-1/4 2-1/4 2-1/4 2-1/4 2-3/4 2-3/4 2-3/4 57 57 57 57 70 70 70 4-7/8 4-7/8 4-7/8 4-7/8 7-19/32 7-19/32 7-19/32 124 124 124 124 193 193 193 2-13/16 2-13/16 2-13/16 2-13/16 3-1/2 4-1/2 4-1/2 71 71 71 71 89 114 114 DIM A IN. MM DIM B IN. MM DIM C IN. MM DIM D IN. MM DIM E IN. MM DIM F IN. MM OCTAGON IN. MM 1-9/32 (33) 1/4 INCH NPT UPSTREAM TAP AND PLUG 70-6910 841 Commercial/Industrial Combustion Controls Industrial Gas Valves OCTAGON H 6-3/4 (171) 1-9/32 (33) A B C D DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J E G F J OCTAGON 5 (127) VALVE SIZE (IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 283 283 283 283 298 298 298 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 70 70 70 70 86 86 86 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-5/16 8-5/16 208 208 208 208 211 211 211 8-1/4 8-1/4 8-1/4 8-1/4 11-3/4 11-3/4 11-3/4 210 210 210 210 298 298 298 IN. MM IN. MM IN. MM 62 62 62 62 91 91 91 5 5 5 5 8 8 8 127 127 127 127 203 203 203 58 58 58 58 113 113 113 23 23 23 23 38 38 38 100 100 100 100 165 165 165 71 71 71 71 114 114 114 3/4 1 1-1/4 1-1/2 2 2-1/2 3 M27581 1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL. 1 2-7/16 2-7/16 2-7/16 2-7/16 3-5/8 3-5/8 3-5/8 2-5/16 2-5/16 2-5/16 2-5/16 4-7/16 4-7/16 4-7/16 7/8 7/8 7/8 7/8 1-1/2 1-1/2 1-1/2 3-15/16 3-15/16 3-15/16 3-15/16 6-1/2 6-1/2 6-1/2 2-13/16 2-13/16 2-13/16 2-13/16 4-1/2 4-1/2 4-1/2 842 70-6910 Industrial Gas Valves V5097 Integrated Valve Train Safety shutoff valves used with V4055, V4062 and V9055 fluid power actuators to control gas flow to commercial and industrial burners. • Use with natural or LP gases. • Mount directly in gas supply line. • Two Valve body types. Small body type for 3/4 in., 1 in., 1-1/4 in., 1-1/2 in., 2 in. pipes. Large body types for 2 in., 2-1/2 in. and 3 in. pipes. • Seven pipe adapter sizes from 3/4 in. to 3 in. have NPT or BSP threaded connections. • Provides three 1/4 in. upstream and two 1/4 in. downstream tap and plug. • CE version provides an additional downstream tap and plug. • Yellow SHUT indicator attached to the valve stem provides an indication of the valve closed position. • V5097A, C, D, E Valves are for on-off service. • V5097B Valve has a characterized guide and in combination with the V4055, V4062 and V9055 Fluid Power Actuators, provides slowopening, HI-LO-OFF, and modulating functions, respectively. • V5097C, E Valves have a double seal and are used with V4055D, E Actuators to provide proof-of-closure switch and valve seal overtravel interlock. • Actuators to provide proof-of-closure switch and valve seal overtravel interlock. • V5097D, E Valves are for high pressure applications. • Two valve body types (small and large) applicable to server pipe size. Operating Temperature Range: -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C) Approvals, Underwriters Laboratories Inc.: When used with V4055A, B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ Approvals, CSA: When used with V4055, V4062, and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Swiss RE: When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061 Approvals, CE: CE #E3070 (Gastec) Comments: Select Proper Pipe Adapter Includes: Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT downstream taps Used With: V9055; V4055; V4062 Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Maximum Operating Differential Pressure Integrated Valve Train Body Size Approvals, Factory Mutual V5097A1004/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Small body When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097A1012/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097B1002/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Small body When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097B1010/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097C1000/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Small body When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24066 V5097C1018/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24066 V5097D1008/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Small body When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 V5097D1016/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 V5097E1005/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Small body When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 V5097E1013/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 70-6910 843 Commercial/Industrial Combustion Controls Industrial Gas Valves Dimensions in inches (millimeters) 6-3/4 (171) 1-9/32 (33) A B C D DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J E G H F J OCTAGON OCTAGON 5 (127) VALVE SIZE (IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 283 283 283 283 298 298 298 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 70 70 70 70 86 86 86 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-5/16 8-5/16 208 208 208 208 211 211 211 8-1/4 8-1/4 8-1/4 8-1/4 11-3/4 11-3/4 11-3/4 210 210 210 210 298 298 298 IN. MM IN. MM IN. MM 62 62 62 62 91 91 91 5 5 5 5 8 8 8 127 127 127 127 203 203 203 58 58 58 58 113 113 113 23 23 23 23 38 38 38 100 100 100 100 165 165 165 71 71 71 71 114 114 114 3/4 1 1-1/4 1-1/2 2 2-1/2 3 M11682B 1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL. 1 2-7/16 2-7/16 2-7/16 2-7/16 3-5/8 3-5/8 3-5/8 2-5/16 2-5/16 2-5/16 2-5/16 4-7/16 4-7/16 4-7/16 7/8 7/8 7/8 7/8 1-1/2 1-1/2 1-1/2 3-15/16 3-15/16 3-15/16 3-15/16 6-1/2 6-1/2 6-1/2 2-13/16 2-13/16 2-13/16 2-13/16 4-1/2 4-1/2 4-1/2 844 70-6910 Industrial Gas Valves Integrated Valve Train Pipe Adapters Material Number Pipe Size (inch) Pipe Size (DN) Connection Type Integrated Valve Train Body Size Description Used With 32000109-001/U 3/4 in. DN20 NPT Small body 3/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-002/U 1 in. DN25 NPT Small body 1 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-003/U 1 1/4 in. DN32 NPT Small body 1 1/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-004/U 1 1/2 in. DN40 NPT Small body 1 1/2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-005/U 2 in. DN50 NPT Small body 2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-006/U 3/4 in. DN20 BSP Small body 3/4 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-007/U 1 in. DN25 BSP Small body 1 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-001/U 2 in. DN50 NPT Large body 2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-002/U 2 1/2 in. DN65 NPT Large body 2 1/2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-003/U 3 in. DN80 NPT Large body 3 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-004/U 2 in. DN50 BSP Large body 2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-005/U 2 1/2 in. DN65 BSP Large body 2 1/2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-006/U 3 in. DN80 BSP Large body 3 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 V5055/5097 Replacement Parts or Accessories Material Number Description Used With 133392A/U O-Ring Assembly for 2 in., 2 1/2 in., and 3 in. V5055 valves V5055/V5097 valves 133393A/U O-Ring Assembly for 1 in., 1 1/4 in., and 1 1/2 in. V5055 valves V5055/V5097 valves 133398AA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055A valves V5055/V5097 valves 133398BA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055B valves V5055/V5097 valves 133398CA/U Replacement Bonnet Assembly, with 137253A replacement Seal Assembly for small body (3/4, 1, 1 1/2 in.) V5055/V5097C. V5055/V5097 valves 133417AA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055A valves V5055/V5097 valves 133417BA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055B valves V5055/V5097 valves 133417CA/U Bonnet Assembly for 2, 2 1/2, or 3 in. V5055C or V5097C valves V5055C/V5097C valves 137253A/U Replacement seal assembly. For 4 inch V5055. V5055 4074EYE/U Bag assembly for V5097 (large body) includes 6 ea bolts, nuts and washers. Large Body V5097 4074EYF/U Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. Small Body V5097 4074EYK/U Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. Small Body V5097 4074EYL/U Bag assembly for V5097 (large body) includes (2) O-rings, (1) grease capsule. Large Body V5097 70-6910 845 Commercial/Industrial Combustion Controls Pilot Gas Valves V4046C; V8046C Pilot Gas Valves Dimensions in inches (millimeters) 1-3/16 (30) DIM. A 1-3/8 (35) 1-5/8 (41) 1-3/4 (45) 2-5/8 (67) 1-3/4 (45) DIM. B 1-1/4 (32) BASIC CENTER 45 BASIC CENTER 8-32 x 1/4 IN.(6) DEEP (2) 1/2-14 NPSM 36 IN. (915) LEADS (2) THREAD SIZE MODEL V4046C, V8046C BODY SIZE THREAD SIZE SMALL SMALL LARGE LARGE 1/8-27 NPT 1/4-18 NPT 1/4-18 NPT 3/8-18 NPT 5/16 3/8 1/2 1/2 8 10 13 13 2-3/4 3 3-1/4 3-1/4 70 76 83 83 DIM. A DIM. B IN MM IN MM M16595A Provide on-off control of natural, LP and manufactured gases to pilot burners in industrial and commercial applications. • Magnetically operated, normally closed. • Provide instantaneous action when energized. • On power failure, valve closes in one second maximum. • Use in any position, directly in pipe line or on support bracket. • Replace the solenoid coil without removing the valve body from the piping connections. • Straight-through valve pattern. • Available in line voltage or low voltage models. Type of Fuel: Air; natural; manufactured; LP Body Pattern: Straight-through Valve Opening Time: 1 sec max Valve Closing Time: 1 sec max Mounting: Directly in pipe or on support bracket Materials: Body – Aluminum Power Consumption: 8 W Operating Temperature Range: -40°F to +125°F (-40°C to +52°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. MH1639, V3, S3 - Guide No. YIOZ Approvals, CSA: Certificate No. 158158-2500006058, Guide No. C3371-03, 83 Approvals, Factory Mutual: Approved: Report No. 17450 Pressure Ratings (psi): 10 psi Pressure Ratings (kPa): 68.9 kPa Material Number Pipe Size (inch) Capacity (cfh) Capacity (m3/hr) Voltage Frequency Electrical Connections Approvals, Swiss RE V4046C1005/U 1/8 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1021/U 1/4 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1047/U 1/4 in. 55 cfh 1.56 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1054/U 3/8 in. 67 cfh 1.90 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1120/U 3/8 in. 67 cfh 1.90 m3/hr 120 Vac 60 Hz Two 10 ft. leadwires and 1/2 in. conduit bushing Acceptable V8046C1006/U 1/8 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing V8046C1014/U 1/4 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing V8046C1022/U 1/4 in. 55 cfh 1.56 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing V8046C1030/U 3/8 in. 67 cfh 1.90 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing 846 70-6910 Solenoid Gas Valves V4295; V8295 Solenoid Gas Valves V4295A/V8295A normally closed and V4295S/V8295S normally open (vent) solenoid gas valves, are suitable for furnaces, ovens, atmospheric burners, commercial water heaters, rooftop make-up air units, power burners, and commercial/industrial boilers. • V8295A, S are used with 24 Vac controllers. • V4295A, S are used with 120 Vac controllers. • Positive close off of gas flow when de-energized. • High valve spring force allows up to 0.7 psi back pressure at valve seat. • No inlet pressure influence at valve seat. • Inlet pressure changes do not affect ability to close valve. • Low operating noise. • Low rush-in current. • Upstream and downstream taps allows tapping and testing pressure points. Type of Fuel: Air; natural; manufactured; mixed; LP Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT Body Pattern: Straight-through, non-offset Valve Opening Time:less than 1 sec Valve Closing Time: less than 1 sec Mounting: Vertical to 90 degrees from vertical Materials: Body – Die-cast aluminum Frequency: 50 Hz; 60 Hz Electrical Connections: Screw terminals Operating Temperature Range: -40°F to +140°F (-40°C to +60°C) Approvals, Swiss RE: Acceptable Approvals, Control Safety Devices: Acceptable Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Voltage Approximate, Dimensions Current Ratings Pressure Ratings (psi) Pressure Ratings (kPa) Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual V4295A1015 1/2 in. DN15 250 cfh 7.1 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1023 3/4 in. DN20 645 cfh 18.3 m3/hr 120 Vac 5 1/4 in. high x 3 7/16 in. wide x 2 3/4 in. deep (133 mm high x 87 mm wide x 70 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1031 1 in. DN25 790 cfh 22.4 m3/hr 120 Vac 5 1/4 in. high x 3 15/16 in. wide x 3 in. deep (133 mm high x 100 mm wide x 76 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1049 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 120 Vac 8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (203 mm high x 151 mm wide x 111 mm deep) 0.34 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1056 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 120 Vac 8 3/8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (213 mm high x 151 mm wide x 111 mm deep) 0.3 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1064 2 in. DN50 3465 cfh 98.1 m3/hr 120 Vac 8 3/8 in. high x 6 11/16 in. wide x 5 3/8 in. deep (213 mm high x 170 mm wide x 137 mm deep) 0.525 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1072 2 1/2 in. DN65 5070 cfh 143.5 m3/ hr 120 Vac 12 3/4 in. high x 9 1/2 in wide x 7 7/8 in. deep (324 mm high x 241 mm wide x 200 mm deep) 0.575 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1080 3 in. DN80 6100 cfh 172.7 m3/ hr 120 Vac 12 3/4 in. high x 9 1/2 in wide x 7 7/8 in. deep (324 mm high x 241 mm wide x 200 mm deep) 0.675 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF 70-6910 847 Commercial/Industrial Combustion Controls Solenoid Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Voltage Approximate, Dimensions Current Ratings Pressure Ratings (psi) Pressure Ratings (kPa) Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual V4295A1098 3/8 in. 210 cfh 5.9 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.16 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1106 1/2 in. DN15 290 cfh 8.2 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.16 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1114 3/4 in. DN20 610 cfh 17.3 m3/hr 120 Vac 3 3/16 in. high x 3 7/16 in. wide x 2 3/4 in. deep (81 mm high x 87 mm wide x 70 mm deep) 0.2 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1122 1 in. DN25 825 cfh 23.4 m3/hr 120 Vac 6 5/16 in. high x 3 15/16 in. wide x 3 in. deep (160 mm high x 100 mm wide x 76 mm deep) 0.2 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1130 1 1/4 in. DN32 1950 cfh 55.2 m3/hr 120 Vac 8 9/16 in. high x 5 15/16 in. wide x 4 3/8 in. deep (217 mm high x 151 mm wide x 111 mm deep) 0.55 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1148/U 1 1/2 in. DN40 2270 cfh 64.3 m3/hr 120 Vac 8 9/16 in. high x 5 15/16 in. wide x 4 3/8 in. deep (217 mm high x 151 mm wide x 111 mm deep) 0.55 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1155 2 in. DN50 3740 cfh 105.9 m3/ hr 120 Vac 9 3/16 in. high x 6 11/16 in. wide x 5 3/8 in. deep (233 mm high x 170 mm wide x 137 mm deep) 0.54 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295S1005 3/4 in. DN20 350 cfh 9.9 m3/hr 120 Vac 5 1/2 in. high x 3 7/16 in. wide x 2 3/4 in. deep (140 mm high x 87 mm wide x 70 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 83 Approved: Report No. J.I.OD6A2. AF V4295S1013 1 in. DN25 420 cfh 11.9 m3/hr 120 Vac 5 1/2 in. high x 3 15/16 in. wide x 3 in. deep (140 mm high x 100 mm wide x 76 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 83 Approved: Report No. J.I.OD6A2. AF V4295S1021 1 1/4 in. DN32 1100 cfh 31.1 m3/hr 120 Vac 8 3/4 in. high x 5 15/16 in. wide x 4 3/8 in. deep (222 mm high x 151 mm wide x 111 mm deep) 0.34 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 83 Approved: Report No. J.I.OD6A2. AF V8295A1016 1/2 in. DN15 250 cfh 7.1 m3/hr 24 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1024 3/4 in. DN20 645 cfh 18.3 m3/hr 24 Vac 5 1/4 in. high x 3 7/16 in. wide x 2 3/4 in. deep (133 mm high x 87 mm wide x 70 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1032 1 in. DN25 790 cfh 22.4 m3/hr 24 Vac 5 1/4 in. high x 3 15/16 in. wide x 3 in. deep (133 mm high x 100 mm wide x 76 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only 848 70-6910 Solenoid Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Voltage Approximate, Dimensions Current Ratings Pressure Ratings (psi) Pressure Ratings (kPa) Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual V8295A1040 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 24 Vac 8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (203 mm high x 151 mm wide x 111 mm deep) 1.6 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1057 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 24 Vac 8 3/8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (213 mm high x 151 mm wide x 111 mm deep) 1.7 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1065 2 in. DN50 3465 cfh 98.1 m3/hr 24 Vac 8 3/8 in. high x 6 11/16 in. wide x 5 3/8 in. deep (213 mm high x 170 mm wide x 137 mm deep) 2.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295S1006 3/4 in. DN20 350 cfh 9.9 m3/hr 24 Vac 5 1/2 in. high x 3 7/16 in. wide x 2 3/4 in. deep (140 mm high x 87 mm wide x 70 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only 70-6910 849 Commercial/Industrial Combustion Controls Solenoid Gas Valves V4297A Solenoid Safety Shut-off Valve for IVT V4297A are normally closed solenoid gas valve. Suitable for use on furnaces, ovens, atmospheric burners, commercial water heaters, rooftop make-up air units, power burners, and commercial/industrial boilers. • V4297A are used with 120 Vac controllers. • Positive close off of gas flow when de-energized. • High valve spring force allows up to 0.7 psi back pressure at valve seat. • No inlet pressure influence at valve seat. • Inlet pressure changes do not affect ability to close valve. • Low operating noise. • Low rush-in current. • Upstream and downstream taps allows tapping and testing pressure points. • For use with the Integrated Valve Train. • Accepts C6097 Pressure Switch mounted directly to flange (upstream pressure tap only). Type of Fuel: Air; natural; manufactured; mixed; LP Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT Body Pattern: Straight-through, non-offset Valve Opening Time: less than 1 sec Valve Closing Time: less than 1 sec Flanges: Required, Order Separately Mounting: Directly bolted to Integrated Valve Train Components Materials: Body – Die-cast aluminum Voltage: 110 Vac; 120 Vac Frequency: 50 Hz; 60 Hz Electrical Connections: Screw terminals Operating Temperature Range: -40°F to +130°F (-40°C to +54°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371- 03, 04, 83 Approvals, Swiss RE: Acceptable Pressure Ratings (psi): 5 psi Pressure Ratings (kPa): 34.5 kPa Replacement Parts: 4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. 4074EYK/U – Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. Dimensions in inches (millimeters) 2 (51) 5 (127) 5-1/2 (140) 5-5/8 (143) 3-3/4 (95) 1-1/2 (38) 2-3/4 (70) 1/2 (13) 5-3/4 (147) 6-1/4 (159) 10-1/4 (260) M23226 TOP VIEW Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions Integrated Valve Train Body Size Current Ratings V4297A1005 3/4 in. to 1 1/4 in. DN20 or DN25 or DN32 650 cfh; 700 cfh; 780 cfh 19.8 m3/hr 9 in. high x 5 3/4 in. wide x 5 5/8 in. deep (229 mm high x 147 mm wide x 143 mm deep) Small body, small flow 0.2 max amps at rated Vac/Hz V4297A1013 3/4 in. to 2 in. DN20 or DN25 or DN32 or DN40 or DN50 1190 cfh; 1460 cfh; 2260 cfh; 2735 cfh; 3060 cfh 10 1/4 in. high x 5 3/4 in. wide x 5 5/8 in. deep (260 mm high x 147 mm wide x 143 mm deep) Small body, large flow 0.5 max amps at rated Vac/Hz 850 70-6910 Solenoid Gas Valves V4297S Normally Open Vent Valve for IVT V4297S are normally open (vent) solenoid gas valves. Suitable for use on furnaces, ovens, atmospheric burners, commercial water heaters, rooftop make-up air units, power burners, and commercial/industrial boilers. • V4297S is used with 120 Vac controllers. • Low operating noise. • Low rush-in current. • Upstream and downstream taps allows tapping and testing pressure points. • For use with the Integrated Valve Train. Type of Fuel: Air; natural; manufactured; mixed; LP Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT Body Pattern: Straight-through, non-offset Valve Opening Time: less than 1 sec Valve Closing Time: less than 1 sec Flanges: Required for Stand Alone Mounting: Directly bolted to Integrated Valve Train Components Materials: Body – Die-cast aluminum Voltage: 110 Vac; 120 Vac Frequency: 50 Hz; 60 Hz Electrical Connections: Screw terminals Operating Temperature Range: -40°F to +145°F (-40°C to +63°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371- 03, 04, 83 Approvals, Swiss RE: Acceptable Pressure Ratings (psi): 5 psi Pressure Ratings (kPa): 34.5 kPa Replacement Parts: 4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. 4074EYK/U – Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. 4074EYL/U – Bag assembly for V5097 (large body) includes (2) O-rings, (1) grease capsule. Dimensions in inches (millimeters) 2-5/8 3 (69) (76) 1-1/2 (38) 5/16 (8) 3/4 (18) 3/4 (18) 2 (51) 5 (127) 8 (203) 1-1/2 3/16 (5) (32) M23252 2 (51) 12-3/8 (314) 3-1/8 (79) 1/2 (13) 4-1/2 (114) 5/8 (16) 1 (25) 1/2 (13) 1-1/4 IN. NPT 1/2 (13) (3 HOLES) 3/8 (10) (3 HOLES) 2-5/8 (69) 9-1/2 (241) 3-1/8 (79) 3/8 (10) 1/2 (13) 1/2 (13) 7/8 (22) 4-1/8 (105) 3-1/8 (79) 5 (127) 3/8 (10) 1/2 (13) 1-1/4 (32) 2 (51) 1-1/2 (32) 3/16 (5) 1-15/16 (49) 2-3/8 (60) M23251 2 (51) 1 IN. NPT Material Number Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions Integrated Valve Train Body Size Current Ratings V4297S1003 DN25 714 cfh 20.2 m3/hr 9 1/2 in. high x 3 1/8 in. wide x 5 in. deep (241 mm high x 79 mm wide x 127 mm deep) Small body 0.2 max amps at rated Vac/Hz V4297S1011 DN32 1115 cfh 31.6 m3/hr 12 3/8 in. high x 5 in. wide x 8 in. deep (314 mm high x 127 mm wide x 203 mm deep) Large body 0.34 max amps at rated Vac/Hz 70-6910 851 Commercial/Industrial Combustion Controls Servo Regulated Gas Valves V4730C; V4734C; V8730C Gas/Air Servo Regulated Gas Valves Body Pattern: Straight flange Valve Opening Time: Dead time maximum: 1 second; First valve – < 1 second; Second valve – reaches 50% of the adjustable outlet pressure within 5 seconds Materials: Body: Aluminum alloy, die-cast Frequency: 50 Hz; 60 Hz Ambient Temperature Range: 5°F to 140°F (-15°C to +60°C) Approvals, Underwriters Laboratories Inc.: File No. MH18476 Approvals, CSA: File: Certificate No: 158158-1227192 Approvals, Others: Gas Appliance Directive: 90.396/EEC, PIN: 0063AT1198, Low Voltage Directive: 73/23/EEC, Electro Magnetic Compatibility Directive: 89/336/EEC Maximum Safe Operating Pressure (psi): 0.5 psi (CSA approved), 1.45 psi for 120V; 1 psi for 24V (UL approved) Maximum Operating Pressure (mbar): 200 mbar (UL approved) 100 mbar for 120V; 69 mbar for 24V (UL approved), 35 mbar (CSA approved) Comments: The minimum load for which the system can be used is 14-17% of the reference load, which equals a minimum pressure differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas control. Coil Insulation Solenoid Valves: Class H insulation system Current Ratings: V1 Current Rating – 0.16A; V2 Current Rating – 0.16A; V1 + V2 Current Rating – 0.32A Material Number Pipe Size (inch) Capacity (kW) Capacity (kBtuh) Voltage Electrical Connections Pipe Connection Includes Max. Capacity with Strainer (cfh) V4730C1006-0000 1/2 in. Natural Gas 0.64 sp.gr – 22-150 KW Natural Gas 0.64 sp.gr – 73- 512 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-001 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 221 cfh V4730C1014-0000 3/4 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-002 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V4730C1022-0000 1 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-003 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V4730C1030-0000 1 1/4 in. Natural Gas 0.64 sp.gr – 55-382 KW when used with VMU335, 71-500KW Natural Gas 0.64 sp.gr – 185- 1300 kBtuh when used with VMU335,245- 1710 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-004 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1300 cfh 852 70-6910 Servo Regulated Gas Valves Material Number Pipe Size (inch) Capacity (kW) Capacity (kBtuh) Voltage Electrical Connections Pipe Connection Includes Max. Capacity with Strainer (cfh) V4734C1002-0000 1 1/4 in. Natural Gas 0.64 sp.gr – 97-680 KW when used with VMU680 Natural Gas 0.64 sp.gr – 326- 2287 kBtuh when used with VMU680 120 Vac (+10%, -15%) Mesh screen filter and 32006652-004 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) V8730C1007-0000 1/2 in. Natural Gas 0.64 sp.gr – 22-150 KW Natural Gas 0.64 sp.gr – 73- 512 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-001 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 221 cfh V8730C1015-0000 3/4 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-002 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V8730C1023-0000 1 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-003 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V8730C1031-0000 1 1/4 in. Natural Gas 0.64 sp.gr – 55-382 KW when used with VMU335, 71-500 KW Natural Gas 0.64 sp.gr – 185- 1300 kBtuh when used with VMU335, 245-1710 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-004 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1300 cfh