Skip to main content

ECC or Buildings Branch | Flame Safeguard part 1

This is honeywells catalog of parts.

Product Selection Matrix
PRODUCT SELECTION MATRIX FOR EC7820 PROGRAMMER RELAY MODULES:
M15516G
SELECT A
SUBBASE
SELECT A
PURGE
CARD
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
220-240 VAC 50/60 HZ
EC7820A1026
EC7820A1034
DESCRIPTION
ONE IGNITION ATTEMPT
FIVE IGNITION ATTEMPTS
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1029
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE - CE APPROVAL
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4,
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
WITH RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7061A, F, M**
C7061A, F, M**
C7076A, F
SELECT
A FLAME
AMPLIFIER
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012 A,C.
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.
1.)
2.)
3.)
4.)
5.)
70-6910 737
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR EC/RM7830 PROGRAMMER RELAY MODULES:
M15517H
SELECT A
SUBBASE
SELECT A
PURGE
CARD
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
220-240 VAC 50/60 HZ
EC7830A1033
EC7830A1041
EC7830A1066
120VAC 50/60 HZ
RM7830A1003
RM7830A1029
RM7830A1011
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DESCRIPTION
POST-PURGE 2 SECONDS
POST-PURGE 30 SECONDS
POST-PURGE 15 SECONDS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1029
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE - CE APPROVAL
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7061A, F, M**
C7061A, F, M**
C7076A, F
SELECT
A FLAME
AMPLIFIER
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012 A,C.
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.
1.)
2.)
3.)
4.)
5.)
738 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR EC/RM7850 PROGRAMMER RELAY MODULES:
M15519G
SELECT A
SUBBASE
SELECT A
PURGE
CARD
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
220-240 VAC 50/60 HZ
EC7850A1064
EC7850A1072
EC7850A1080
EC7850A1122
120VAC 50/60 HZ
RM7850A1001
RM7850A1027
RM7850A1019
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
2 SECOND FFRT
1 SECOND FFRT
2 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DESCRIPTION
DYNAMIC AIR DAMPER CHECK
POST-PURGE 2 SECONDS
POST-PURGE 30 SECONDS
POST-PURGE 15 SECONDS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1029
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE - CE APPROVAL
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7061A, F, M**
C7061A, F, M**
C7076A, F
SELECT
A FLAME
AMPLIFIER
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.
1.)
2.)
3.)
4.)
5.)
70-6910 739
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR EC/RM7823 FLAME SWITCH RELAY MODULES:
M15520F
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
220-240 VAC 50/60 HZ
EC7823A1004
120VAC 50/60 HZ
RM7823A1016
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION ***
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E,F**
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E,F
C7915
C7915
C7061A, F, M**
C7061A, F, M**
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.
740 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7824A 24VDC PRIMARY CONTROL RELAY MODULES:
M15521D
SELECT A
SUBBASE
SELECT
A FLAME
AMPLIFIER
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
RM7824A1006 24VDC
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
R7824C1002
R7851B1000
R7851B1018
R7852A1001
R7852B1009
DESCRIPTION
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
CHECKING
DYNAMIC SELF-CHECK
AMPLICHECK®
AMPLICHECK®
NONE
AMPLICHECK®
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
C7024E, F
C7927, C7962
C7927, C7962
C7915
C7915
1.)
2.)
3.)
4.)
70-6910 741
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7885 MANUAL START PRIMARY RELAY MODULES:
M15522F
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
120VAC 50/60 HZ
RM7885A1015
DESCRIPTION
SEMI AUTOMATIC PRIMARY
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION***
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E,F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
742 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7888A SPECIAL FUNCTION PRIMARY CONTROL RELAY MODULES:
M15523F
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
120VAC 50/60 HZ
RM7888A1019
RM7888A1027
DESCRIPTION
INDUSTRIAL PRIMARY CONTROL (COMPONENT UL APPROVED)
INDUSTRIAL PRIMARY CONTROL (COMPONENT UL APPROVED)
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
70-6910 743
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR EC/RM7890 ON/OFF PRIMARY CONTROL RELAY MODULES:
M15524G
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
220-240 VAC 50/60 HZ
EC7890A1011
EC7890B1010
120VAC 50/60 HZ
RM7890A1015
RM7890A1031
RM7890A1056
RM7890A1064‡
RM7890B1014
RM7890B1030
RM7890B1048
RM7890B1055++
RM7890C1005
RM7890D1004
DESCRIPTION
30 SECOND PFEP
FOR VALVE PROVING APPLICATIONS
WITH SHUTTER DRIVE
WITH SHUTTER DRIVE AND FULL PFEP
WITH SHUTTER DRIVE - FOR VALVE PROVING APPLICATIONS
WITH SHUTTER DRIVE
STANDING PILOT APPLICATIONS WITH FLAME RODS ONLY
INFRARED HEATER ONLY 15 OR 30 PREF
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
S7800A1142
S7800A1167
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
ENGLISH (REQUIRED TO PROGRAM VP TIMINGS)
SPANISH (REQUIRED TO PROGRAM VP TIMINGS)
O.S. NO.
S7810A1009
S7810M1003
S7810M1029
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
MODBUS MODULE - CE APPROVED
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION***
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F**
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M**
C7061A, F, M**
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.
*** FFRT FOR CE APPROVED CONTROLS 1 SEC. OR 2 SEC.
‡ CE APPROVED
++ NORTH AMERICAN AND CE APPROVED
744 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR EC/RM7895 ON/OFF WITH PURGE PRIMARY RELAY MODULES:
M15525F
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
220-240 VAC 50/60 HZ
EC7895A1010
EC7895C1000
120VAC 50/60 HZ
RM7895A1014
RM7895A1048
RM7895B1013
RM7895C1012
RM7895C1020
RM7895D1011
RM7895E1002
DESCRIPTION
EARLY SPARK TERMINATION
DYNAMIC AIRFLOW SWITCH CHECK
EARLY SPARK TERMINATION
DYNAMIC AIRFLOW SWITCH CHECK
INFRARED HEATER APPLICATIONS, 15/30 SECOND PFEP
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
INTERRUPTED PILOT
INTERMITTENT PILOT
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7851A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION***
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F**
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M**
C7061A, F, M**
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.
70-6910 745
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7896 ON/OFF WITH PRE- AND POST-PURGE PRIMARY RELAY MODULES:
M13908B
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
120VAC 50/60 HZ
RM7896A1012
RM7896B1011
RM7896C1010
RM7896D1019
RM7896D1027
DESCRIPTION
DYNAMIC AIRFLOW SWITCH CHECK
DYNAMIC AIRFLOW SWITCH CHECK
5 SEC EARLY SPARK TERMINATION, DYNAMIC AIRFLOW SWITCH CHECK AND
60 SEC POST-PURGE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
INTERRUPTED PILOT
INTERMITTENT PILOT
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7851A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION***
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
746 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7897 ON/OFF WITH PRE- AND PROGRAMMABLE POST-PURGE
PRIMARY RELAY MODULES:
M15526H
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
DESCRIPTION
INTERMITTENT/INTERRUPTED PILOT AND PROOF OF CLOSURE
INTERRUPTED PILOT WITH DELAYED MV2 AND PROOF OF CLOSURE
INTERRUPTED PILOT WITH DELAYED MV2 AND PROOF OF CLOSURE 5 SEC MFEP
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
S7800A1142
S7800A1167
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
ENGLISH (REQUIRED TO SET POST PURGE TIME)
SPANISH (REQUIRED TO SET POST PURGE TIME)
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
120 VAC 50/60 HZ
RM7897A1002
RM7897C1000
RM7897C1018
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E,F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
70-6910 747
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7898 ON/OFF WITH PRE- AND PROGRAMMABLE POST-PURGE PRIMARY
RELAY MODULES FOR VALVE PROVING APPLICATIONS:
M23254C
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
DESCRIPTION
INTERMITTENT/INTERRUPTED PILOT AND PROOF OF CLOSURE
INTERMITTENT/INTERRUPTED PILOT WITH EARLY SPARK TERMINATION AND PROOF OF CLOSURE
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
S7800A1142
S7800A1167
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
ENGLISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS)
SPANISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS)
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
120 VAC 50/60 HZ
RM7898A1000
RM7898A1018
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E,F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
748 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7838A MANUAL START WITH PURGE INDUSTRIAL PRIMARY RELAY MODULE:
M15527F
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
DESCRIPTION
INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
120 VAC 50/60 HZ
RM7838A1014
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
70-6910 749
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7838B MANUAL START INDUSTRIAL PROGRAMMER RELAY MODULE:
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
DESCRIPTION
SEMI-AUTOMATIC PROGRAMMER WITH:
S7800A1001 KEYBOARD DISPLAY STANDARD
S7800A1142 KEYBOARD DISPLAY STANDARD - HAS VALVE PROVING FEATURE
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
M15528F
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E,F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
120 VAC 50/60 HZ
RM7838B1013*
RM7838B1021*
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* ALARM SOUNDS UNTIL FLAME SENSED
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
750 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR RM7838C MANUAL START INDUSTRIAL PROGRAMMER RELAY MODULE:
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
DESCRIPTION
SEMI-AUTOMATIC PROGRAMMER WITH:
S7800A1001 KEYBOARD DISPLAY STANDARD
S7800A1142 KEYBOARD DISPLAY STANDARD - DEVICE HAS VALVE PROVING FEATURE
S7800A1001 KEYBOARD DISPLAY STANDARD
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
M18830F
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
S7800A1142
S7800A1167
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
ENGLISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS)
SPANISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS)
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E,E
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E,F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT A
PURGE
CARD
O.S. NO.
ST7800C1003
ST7800C1011
ST7800C1029
ST7800C1037
ST7800C1045
ST7800C1052
DESCRIPTION
TIMING: 7 SECOND
TIMING: 20 SECOND
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 8 MINUTE
TIMING: 10 MINUTE
O.S. NO.
ST7800C1086
ST7800C1102
ST7800C1128
ST7800C1136
ST7800C1144
DESCRIPTION
TIMING: 16 MINUTE
TIMING: 20 MINUTE
TIMING: 24 MINUTE
TIMING: 30 MINUTE
TIMING: 45 MINUTE
120 VAC 50/60 HZ
RM7838C1004*
RM7838C1012*
RM7838C1020*+
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* ALARM OUTPUT - LOCKOUT ONLY
+NORTH AMERICAN AND CE APPROVED
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
70-6910 751
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR UL/CSA RM78XXG,M PROGRAMMER RELAY MODULE:
M15529F
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
S7800A1142
S7800A1167
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGEUESE LANGUAGE
ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE)
SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE)
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
120VAC 50/60 HZ
RM7800G1018
RM7840G1014
RM7840G1022
RM7800M1011
RM7840M1017
DESCRIPTION
MODULATING BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULE STANDARD
MODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE
MODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE - FOR VALVE PROVING
ON-OFF BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULE STANDARD
ON-OFF BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
752 70-6910
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE:
M34645
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
S7800A1142
S7800A1167
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE)
SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE)
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
120VAC 50/60 HZ
RM7845A1001
DESCRIPTION
WITHOUT KEYBOARD DISPLAY (LESS IGNITION AND 15 SECOND MFEP PILOT TERMINALS)
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
70-6910 753
Commercial/Industrial
Combustion Controls
Product Selection Matrix
PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE:
M15530G
SELECT A
SUBBASE
SELECT
OPTIONAL
COMPONENTS
KEYBOARD
DISPLAY
MODULE
COMMUNICATIONS
MISCELLANEOUS
SELECT A
RELAY
MODULE
O.S. NO.
Q7800A1005
Q7800B1003
Q7800B1011
DESCRIPTION
PANEL MOUNT
BURNER/WALL MOUNT
BURNER/WALL MOUNT WITH 3 KNOCKOUTS
O.S. NO.
R7847A1025
R7847A1033
R7847A1074
R7847A1082
R7847B1023
R7847B1031
R7847B1064
R7847B1072
R7847C1005
R7849A1015
R7849A1023
R7849B1013
R7849B1021
R7851B1000
R7851B1018
R7851C1008
R7852A1001
R7852B1009
R7861A1026
R7861A1034
R7886A1001
DESCRIPTION
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
3.0 SECOND FFRT
0.8 SECOND FFRT
3.0 SECOND FFRT
CHECKING
NONE
NONE
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
NONE
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
AMPLICHECK®
DYNAMIC SELF-CHECK
NONE
AMPLICHECK®
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
DYNAMIC SELF-CHECK
O.S. NO.
S7800A1001
S7800A1035
S7800A1043
S7800A1050
S7800A1068
S7800A1118
S7800A1126
S7800A1142
S7800A1167
DESCRIPTION
ENGLISH LANGUAGE
FRENCH LANGUAGE
GERMAN LANGUAGE
ITALIAN LANGUAGE
SPANISH LANGUAGE
KATAKANA (JAPANESE) LANGUAGE
PORTUGUESE LANGUAGE
ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE)
SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE)
O.S. NO.
S7810A1009
S7810M1003
DESCRIPTION
DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED)
MODBUS MODULE
O.S. NO.
S7820A1007
S7830A1005
203541
203765
221729
50023821-001
204718B
50023821-002
205321B
221818A
221818C
DESCRIPTION
REMOTE RESET MODULE
EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
DATA CONTROLBUS CONNECTOR, 5-WIRE
REMOTE DISPLAY MOUNTING BRACKET
DUST COVER, RELAY MODULE
KEYBOARD DISPLAY MODULE COVER, NEMA 4
KEYBOARD DISPLAY MODULE COVER, CLEAR
KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
FLUSH DISPLAY MOUNTING KIT
EXTENSION CABLE, DISPLAY 5FT (1524MM)
EXTENSION CABLE, DISPLAY 10FT (3048MM)
USE WITH
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
FLAME ROD
FLAME ROD
FLAME ROD*
FLAME ROD*, C7012A, C
C7012E, F
C7027, C7035
C7027, C7035
C7027, C7035
C7027, C7035
C7927, C7962
C7927, C7962
C7961E, F
C7915
C7915
C7061A, F, M
C7061A, F, M
C7076A, D
SELECT A
PURGE
CARD
O.S. NO.
ST7800A1005
ST7800A1013
ST7800A1021
ST7800A1039
ST7800A1047
ST7800A1054
ST7800A1062
DESCRIPTION
TIMING: 2 SECOND
TIMING: 7 SECOND
TIMING: 10 SECOND
TIMING: 30 SECOND
TIMING: 40 SECOND
TIMING: 60 SECOND
TIMING: 90 SECOND
O.S. NO.
ST7800A1070
ST7800A1088
ST7800A1096
ST7800A1104
ST7800A1112
ST7800A1120
ST7800A1138
ST7800A1146
DESCRIPTION
TIMING: 2.5 MINUTE
TIMING: 4 MINUTE
TIMING: 6 MINUTE
TIMING: 9 MINUTE
TIMING: 12 MINUTE
TIMING: 15 MINUTE
TIMING: 22 MINUTE
TIMING: 30 MINUTE
120VAC 50/60 HZ
RM7800E1010
RM7840E1016
RM7800L1012
RM7840L1018
RM7800L1053
RM7840L1026
RM7800L1087
RM7840L1075
DESCRIPTION
ENERGY SAVING PURGE, S7800A1001 KEYBOARD DISPLAY STANDARD
ENERGY SAVING PURGE WITHOUT KEYBOARD DISPLAY
S7800A1001 KEYBOARD DISPLAY STANDARD
WITHOUT KEYBOARD DISPLAY
INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD
INTERMITTENT PILOT WITHOUT KEYBOARD DISPLAY
S7800A1142 KEYBOARD DISPLAY STANDARD - WITH VALVE PROVING FEATURE
WITHOUT KEYBOARD DISPLAY - WITH VALVE PROVING FEATURE
SELECT
A FLAME
AMPLIFIER
1.)
2.)
3.)
4.)
5.)
* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C.
754 70-6910
Microprocessor Burner Controls
EC7820 Primary Control Meeting European Community Timings
Integrated burner control for automatically fired gas, oil, or
combination, single burner atmospheric with fan applications. Has
automatic burner sequencing, flame supervising system status
indication, system or self-diagnostics, and troubleshooting.
• Access for external electrical voltage checks.
• Application flexibility and communication interface capability.
• Five LEDs provide sequence information.
• Five function Run/Test Switch. Interchangeable plug-in amplifiers.
• Local or remote annunciation of operation and fault information
(optional).
• Non-volatile memory retains history files and lockout status after loss
of power.
• Compatible with existing Honeywell flame detectors.
Application: Primary Control
Interlocks: Lockout
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: 5 sec
Early Spark Termination: Yes, 5 sec
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A
Plug-in Purge Timer Card.
Frequency: 60 Hz (±10%), 50 Hz
AirFlow Check: User selectable
Second Stage Pilot Valve: Intermittent
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Approvals, Gastec/European: GASTEC: CE-63AP3070/1, Approved
to EN298.
Dimensions in inches (millimeters)
5
5
BURNER CONTROL
5 1/2
M12821
1
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
Material Number Voltage Pilot Type Flame Establishing Period
- Main
Flame Establishing Period
- Pilot
Comments
EC7820A1026/U 220 to 240 Vac (+10,
-15%)
interrupted 5 sec, or 8 sec, or
Intermittent
5 sec or 10 sec 1 ignition attempt, Includes Modulation w/ Fan
Output
EC7820A1034/U 220 to 240 Vac (+10,
-15%)
interrupted 5 sec, or 8 sec, or
Intermittent
5 sec or 10 sec 5 ignition attempts, Includes Modulation w/ Fan
Output
70-6910 755
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
EC7830; EC7850; RM7830; RM7850 Programming Control Meeting
European Community Timings
Microprocessor-based integrated burner control for full
modulation applications. Provides automatic burner sequencing,
flame supervision, system status indication, system or selfdiagnostics,
and troubleshooting.
• Access for external electrical voltage checks.
• Application flexibility and communication interface capability.
• Five LEDs provide sequence information.
• Five function Run/Test Switch.
• Interchangeable plug-in amplifiers.
• Local or remote annunciation of operation and fault information
(optional).
• Non-volatile memory retains history files and lockout status after loss
of power.
• Compatible with existing Honeywell flame detectors.
Application: Programming Control
Flame Establishing Period - Main: 3 sec, or 5 sec, or Intermittent
Flame Establishing Period - Pilot: 3 sec or 5 sec
Interlocks: Lockout
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
Early Spark Termination: Yes, 5 sec
Required Components: Q7800A,B Universal Wiring Subbases.
R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A
Plug-in Purge Timer Card.
AirFlow Check: User selectable
Second Stage Pilot Valve: Intermittent
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: EC7830, EC7850, RM7830-Report No.
1V9AO.AF; RM7850-Report No. J.I. OYOA9.AF
Approvals, Gastec/European: GASTEC: CE-63AP3070/1, Approved
to EN298.
Dimensions in inches (millimeters)
5
(127)
5 (127)
BURNER CONTROL
1
5-1/4 (133)
1 REMOVE ONLY FOR TERMINAL TEST ACCESS. M15532A
6-3/32 (155)
1
Material Number Voltage Frequency PostPurge Comments
EC7830A1033/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec On/Off Power Burner
EC7830A1041/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec On/Off Power Burner
EC7830A1066/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 15 sec On/Off Power Burner
EC7850A1064/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec LHL-LF & HF Proven; Dynamic damper check
EC7850A1072/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec LHL-LF & HF Proven
EC7850A1080/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec LHL-LF & HF Proven
EC7850A1122/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 15 sec LHL-LF & HF Proven
EC7850A1148/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec LHL-LF & HF Proven
RM7830A1003/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 2 sec On/Off Power Burner
RM7830A1011/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 15 sec On/Off Power Burner
RM7830A1029/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 30 sec On/Off Power Burner
RM7850A1001/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 2 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low
Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC).
RM7850A1019/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 15 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low
Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC).
RM7850A1027/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 30 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low
Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC).
756 70-6910
Microprocessor Burner Controls
RM7800 Programmers
Microprocessor-based integrated burner control for automatically
fired gas, oil, coal or combination fuel single burner applications.
Provides safety, functional capability and features beyond
conventional controls.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and trouble
shooting.
• Access for external electrical voltage checks.
• Application flexibility and communication interface capability.
• Five LEDs provide sequence information.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information
(optional).
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Compatible with existing Honeywell flame detectors.
• Includes Keyboard Display Module.
Application: Programming Control
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: 15 sec
Early Spark Termination: Yes, 5 sec
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Frequency: 50 Hz; 60 Hz (±10%)
AirFlow Check: User selectable
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Dimensions in inches (millimeters)
M15518B
BURNER CONTROL
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
1
6-3/32 (155)
MODULE WITH SUBBASE
Material Number Voltage Flame Establishing Period
- Main
Flame Establishing
Period - Pilot
Second Stage
Pilot Valve
Interlocks Comments
RM7800E1010/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800 Display, LHL-LF & HF
Proven
RM7800G1018/U 120 Vac (+10, -15%) 10 sec, or 15 sec, or 30 sec,
or Intermittent
4 sec or 10 sec selectable Running Includes S7800 Display, LHL-LF Proven
RM7800L1012/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800 Display, LHL-LF & HF
Proven
RM7800L1053/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Intermittent Lockout Includes S7800 Display, LHL-LF & HF
Proven
RM7800M1011/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Intermittent Running Includes S7800 Display, On/Off-LF
proven
70-6910 757
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7800 Programmers with VPS
Integrated burner control for gas, oil, coal or combination fuel
single burner uses. With Valve Proving Feature. RM7800L comes
standard with S7800A1142 Keyboard Display.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and trouble
shooting.
• Access for external electrical voltage checks.
• Application flexibility and communication interface capability.
• Five LEDs provide sequence information. Power LED blinks fault
code on Lockout.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information
(optional).
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Compatible with existing Honeywell flame detectors.
• RM7800 comes with S7800A1142 Keyboard Display Module.
• Keyboard required to setup Valve Proving Feature and change post
purge time.
Application: Programming Control w/VPS
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: programmed with S7800A1142 display
Early Spark Termination: Yes, 5 sec
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Frequency: 50 Hz; 60 Hz (±10%)
AirFlow Check: User selectable
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Dimensions in inches (millimeters)
M15518B
BURNER CONTROL
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
1
6-3/32 (155)
MODULE WITH SUBBASE
Material Number Voltage Flame Establishing
Period - Main
Flame Establishing
Period - Pilot
Second Stage
Pilot Valve
Interlocks Comments
RM7800L1087/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800A1142 Display, LHL-LF & HF Proven
758 70-6910
Microprocessor Burner Controls
RM7823; EC7823 Flame Switch
Dimensions in inches (millimeters)
POWER
FLAME
ALARM
RESET
5
(127)
5 (127)
M2649
BURNER CONTROL
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
Microprocessor-based integrated flame switch for detecting a
flame using rectification, ultraviolet (UV) or infrared (IR) source.
Provides level of safety, functional capability and features beyond
conventional controls.
• Can be fitted with any 7800 Series Amplifier to provide relay action
from two single pole, double throw (SPDT) relays when flame is
present or not present. RM7823A and EC7823 are a flame detector
relays only.
• Suitable primary control must be used to provide safe-start check,
safety lockout, load switching and other functions required in flame
safeguard systems.
• Three LEDs to indicate power, flame and alarm.
• Access for external electrical voltage checks.
• Nonvolatile memory.
• Shutter drive output.
• Compatible with existing Honeywell flame detectors.
Application: Flame Switch
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier.
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 13 oz (0.8 kg)
Approvals, Swiss RE: Acceptable
Comments: two SPDT outputs
Material Number Voltage Frequency Approvals, Underwriters
Laboratories Inc.
Approvals, CSA Approvals, FCC Approvals, Factory
Mutual
EC7823A1004/U 220 to 240 Vac
(+10, -15%)
60 Hz (±10%), 50 Hz Report No. OY0A9.AF.
RM7823A1016/U 120 Vac (+10,
-15%)
50 Hz; 60 Hz (±10%) Component Recognized,
File No. MP268; Guide
No. MCCZ.
Certified, File No.
LR95329-3.
FCC Part 15, Class B,
Emissions.
Report No. OX4A5.AF.
70-6910 759
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7824 On-Off Primary Control
Dimensions in inches (millimeters)
5
(127)
5 (127)
M5872
BURNER CONTROL
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
24 Vdc microprocessor-based integrated burner control for
automatically fired gas, oil or combination fuel single burner
applications. Provides level of safety, functional capability and
features beyond the capacity of conventional controls.
• For use with R7824C Amplifier with C7024E, F Flame Detectors;
R7848A, B with C7015A Flame Detectors; R7851B with C7927,
C7962 Flame Detectors; or R7852A, B with C7915 Flame Detectors.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self diagnostics and
troubleshooting.
• Five LEDs provide sequence information.
• Selectable recycle or lockout on loss of flame.
• Shutter drive output for use with dynamic self-check flame detectors.
• Access for external electrical voltage checks.
• Plug-in flame amplifier.
• Nonvolatile memory retains history files and lockout status after loss
of power.
Application: Primary Control 24 Vdc
Required Components: Q7800A, B Universal Wiring Subbases.
R7824 or R7848 Flame Signal Amplifier.
Pilot Type: intermittent
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 13 oz (0.8 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot
RM7824A1006/U 24 Vdc (+10, -15%) Intermittent 4 sec or 10 sec
760 70-6910
Microprocessor Burner Controls
RM7838A Manual Start Industrial Primary Control with Purge
Microprocessor-based integrated burner control for industrial
semi-automatically fired gas, oil, coal or combination fuel single
burner applications. Provides level of safety, functional capability
and features beyond conventional controls.
• Functions include purge, burner pilot startup, flame supervision,
system status indication, system or self diagnosis and
troubleshooting.
• Delays admission of fuel to combustion chamber until pilot flame
has been proven and then monitors the flame through the run period
while providing system status indication.
• Includes Keyboard Display Module.
• Five LEDs provide sequence information.
• Intermittent pilot valve.
• Interchangeable plug-in flame amplifier.
• Access for external electrical voltage checks.
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Selectable pilot flame establishing period.
• Provides application flexibility and optional communication interface
capability.
• Compatible with existing Honeywell flame detectors.
Application: Semi Automatic Primary Control with Purge
Interlocks: Running
PrePurge: Determined by ST7800A Purge Timer Card
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: intermittent
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Control Safety Devices: Acceptable: CSD-1
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Dimensions in inches (millimeters)
M15518B
BURNER CONTROL
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
1
6-3/32 (155)
MODULE WITH SUBBASE
Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Comments
RM7838A1014/U 120 Vac (+10, -15%) Intermittent 4 sec or 10 sec Includes S7800 Display
70-6910 761
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7838B, C Manual Start Industrial Programmers
Microprocessor-based integrated burner control for industrial
semi-automatically fired gas, oil, coal or combination fuel single
burner applications. Provides level of safety, functional capability
and features beyond conventional controls.
• Functions include purge, burner pilot startup, flame supervision,
system status indication, system or self diagnosis and
troubleshooting.
• Delays admission of fuel to combustion chamber until pilot flame
has been proven and then monitors the flame through the run period
while providing system status indication.
• Includes Keyboard Display Module.
• Five LEDs provide sequence information.
• Intermittent pilot valve.
• Interchangeable plug-in flame amplifier.
• Access for external electrical voltage checks.
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Selectable pilot flame establishing period.
• Provides application flexibility and optional communication interface
capability.
• Compatible with existing Honeywell flame detectors.
Application: Semi Automatic Programming Control
Interlocks: Lockout
Preignition: Yes
Early Spark Termination: Yes, 5 sec
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Control Safety Devices: Acceptable: CSD-1
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Dimensions in inches (millimeters)
M15518B
BURNER CONTROL
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
1
6-3/32 (155)
MODULE WITH SUBBASE
Material Number Voltage Flame Establishing
Period - Main
Flame Establishing
Period - Pilot
PrePurge Required Components Approvals,
Gastec/European
Comments
RM7838B1013/U 120 Vac
(+10, -15%)
10 sec or Intermittent 4 sec or 10 sec Determined by
ST7800A Purge
Timer Card
Q7800A, B Universal Wiring
Subbases. R7847, R7848, R7849,
R7851, R7852, R7861, or R7886
Flame Signal Amplifier. ST7800A
Plug-in Purge Timer Card.
Includes
S7800 Display
RM7838C1004/U 120 Vac
(+10, -15%)
10 sec or Intermittent 4 sec or 10 sec Determined by
ST7800C Purge
Timer Card
Q7800A, B Universal Wiring
Subbases. R7847, R7848, R7849,
R7851, R7852, R7861, or R7886
Flame Signal Amplifier. ST7800C
Plug-in Purge Timer Card.
Includes
S7800 Display
RM7838C1020/U 120 Vac
(+10, -15%)
10 sec or Intermittent 4 sec or 10 sec Determined by
ST7800C Purge
Timer Card
Q7800A, B Universal Wiring
Subbases. R7847, R7848, R7849,
R7851, R7852, R7861, or R7886
Flame Signal Amplifier. ST7800C
Plug-in Purge Timer Card.
Gastec EN268
Report 1156791
Includes
S7800 Display
762 70-6910
Microprocessor Burner Controls
RM7838B, C Manual Start Industrial Programmers with VPS
Integrated burner control for industrial semi-automatically fired
gas, oil, coal or combination fuel single burner applications.
Includes Valve Proving Feature with S7800A1142 Keyboard
Display.
• Functions include purge, burner pilot startup, flame supervision,
system status indication, system or self diagnosis and
troubleshooting.
• Delays admission of fuel to combustion chamber until pilot flame
has been proven and then monitors the flame through the run period
while providing system status indication.
• Includes S7800A1142 Keyboard Display Module.
• Five LEDs provide sequence information.
• Intermittent pilot valve.
• Interchangeable plug-in flame amplifier.
• Access for external electrical voltage checks.
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Selectable pilot flame establishing period.
• Provides application flexibility and optional communication interface
capability.
• Compatible with existing Honeywell flame detectors.
• With Valve Proving Feature and Programmable Post Purge Time.
• Power LED blinks a fault code on system lockout.
Application: Semi Automatic Programming Control w/VPS
Interlocks: Lockout
Preignition: Yes
PostPurge: programmed with S7800A1142 display
Early Spark Termination: Yes, 5 sec
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, Control Safety Devices: Acceptable: CSD-1
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Dimensions in inches (millimeters)
M15518B
BURNER CONTROL
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
1
6-3/32 (155)
MODULE WITH SUBBASE
Material Number Voltage Flame Establishing
Period - Main
Flame Establishing
Period - Pilot
PrePurge Required Components Comments
RM7838B1021/U 120 Vac
(+10, -15%)
10 sec or Intermittent 4 sec or 10 sec Determined by
ST7800A Purge Timer
Card
Q7800A, B Universal Wiring
Subbases. R7847, R7848, R7849,
R7851, R7852, R7861, or R7886
Flame Signal Amplifier. ST7800A
Plug-in Purge Timer Card.
Includes programmable
VPS (Valve Proving
Switch) check feature
and blinking LED fault
annunciation
RM7838C1012/U 120 Vac
(+10, -15%)
10 sec or Intermittent 4 sec or 10 sec Determined by
ST7800C Purge Timer
Card
Q7800A, B Universal Wiring
Subbases. R7847, R7848, R7849,
R7851, R7852, R7861, or R7886
Flame Signal Amplifier. ST7800C
Plug-in Purge Timer Card.
Includes programmable
VPS (Valve Proving
Switch) check feature
and blinking LED fault
annunciation
70-6910 763
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7840 Programmers
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Microprocessor-based integrated burner control for automatically
fired gas, oil, coal or combination fuel single burner applications.
Provides safety, functional capability and features beyond
conventional controls.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and
troubleshooting.
• Access for external electrical voltage checks.
• Application flexibility and communication interface capability.
• Five LEDs provide sequence information.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of RM7840 operation and fault
information.
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Compatible with existing Honeywell flame detectors.
Application: Programming Control
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: 15 sec
Early Spark Termination: Yes, 5 sec
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz; 60 Hz (±10%)
AirFlow Check: User selectable
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 13 oz (0.8 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Control Safety Devices: Acceptable: CSD-1
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Material Number Interlocks Second Stage Pilot Valve Flame Establishing Period
- Main
Flame Establishing Period
- Pilot
Comments
RM7840E1016/U Lockout Interrupted 10 sec or 15 sec 4 sec or 10 sec LHL-LF & HF Proven
RM7840G1014/U Running selectable 10 sec, or 15 sec, or 30 sec,
or Intermittent
4 sec or 10 sec LHL-LF Proven
RM7840L1018/U Lockout Interrupted 10 sec or 15 sec 4 sec or 10 sec LHL-LF & HF Proven
RM7840L1026/U Lockout Intermittent 10 sec or Intermittent 4 sec or 10 sec LHL-LF & HF Proven
RM7840M1017/U Running Intermittent 10 sec or Intermittent 4 sec or 10 sec On/Off-LF Proven
764 70-6910
Microprocessor Burner Controls
RM7840 Programmers with VPS
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Integrated burner control for gas, oil, coal or combination fuel
single burner uses. Provides safety, functional capability and
features beyond normal controls. With Valve Proving Feature.
Requires S7800A1142 Keyboard Display.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and trouble
shooting.
• Access for external electrical voltage checks.
• Application flexibility and communication interface capability.
• Five LEDs provide sequence information. Power LED blinks fault
code on Lockout.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information
(optional).
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Compatible with existing Honeywell flame detectors.
• RM7800 comes with S7800A1142 Keyboard Display Module.
• Keyboard required to setup Valve Proving Feature and change post
purge time.
Application: Programming Control w/VPS
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: programmed with S7800A1142 display
Early Spark Termination: Yes, 5 sec
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Frequency: 50 Hz; 60 Hz (±10%)
AirFlow Check: User selectable
Second Stage Pilot Valve: selectable
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, FCC: FCC Part 15, Class B, Emissions.
Material Number Voltage Flame Establishing
Period - Main
Flame Establishing
Period - Pilot
Interlocks Comments Approvals, Underwriters
Laboratories Inc.
Approvals, Factory
Mutual
EC7840L1014/U 220 to 240 Vac
(+10, -15%)
10 sec or 15 sec 4 sec or 10 sec Lockout Requires S7800A1142
Display, LHL-LF & HF
Proven
RM7840G1022/U 120 Vac (+10,
-15%)
10 sec, 15 sec, 30
sec, or Intermittent
4 sec or 10 sec Running Requires S7800A1142
Display, LHL-LF Proven
Component Recognized,
File No. MP268; Guide No.
MCCZ.
Report No. 1V9AO.AF.
RM7840L1075/U 120 Vac (+10,
-15%)
10 sec or 15 sec 4 sec or 10 sec Lockout Requires S7800A1142
Display, LHL-LF & HF
Proven
Component Recognized,
File No. MP268; Guide No.
MCCZ.
Report No. 1V9AO.AF.
70-6910 765
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7845 Programmers
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Microprocessor-based integrated burner control for automatically
fired gas, oil, coal or combination fuel single burner applications.
Provides safety, functional capability and features beyond
conventional controls.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and
troubleshooting.
• Access for external electrical voltage checks.
• Application flexibility and communication interface capability.
• Five LEDs provide sequence information.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of RM7840 operation and fault
information.
• Nonvolatile memory retains history files and lockout status after loss
of power.
• Compatible with existing Honeywell flame detectors.
Application: Programming Control
Interlocks: Lockout
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: 15 sec
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz; 60 Hz (±10%)
AirFlow Check: User selectable
Pilot Type: interrupted
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Weight lb. (kg): 1 lb 13 oz (0.8 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Control Safety Devices: Acceptable: CSD-1
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments
RM7845A1001/U 10 sec 4 sec or 10 sec LHL-LF & HF Proven
RM7885; EC7885 Manual Start Industrial Primary Control
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Microprocessor-based integrated burner control for industrial
semi-automatically fired gas, oil, coal, or combination fuel single
burner applications. Provides level of safety, functional capability
and features beyond conventional controls.
• Functions include flame supervision, system status indication,
system or self-diagnostics and troubleshooting.
• Adaptable to continuous firing, high-low or modulating firing rate for
semi-automatic burner sequencing.
• Operates with the following: Torch-ignited main burner or torchignited
pilot using S445A Start-Stop Station, or conventional knee or
foot operated station.
• Direct-ignition oil burner or electrically ignited pilot, using S445A
Start-Stop Station.
• Five LEDs provide sequence information.
• Nonvolatile memory.
• Flame signal check during standby.
• Shutter drive output.
• Compatible with existing Honeywell flame detectors.
• Terminal provided for external alarm to sound on flame failure.
Application: Semi Automatic Primary Control
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier.
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: intermittent
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Weight lb. (kg): 1 lb 13 oz (0.8 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot
RM7885A1015/U 120 Vac (+10, -15%) Intermittent 15 min
766 70-6910
Microprocessor Burner Controls
RM7888 PLC Adaptable Primary Control
Dimensions in inches (millimeters)
BURNER CONTROL
POWER
PILOT
FLAME
MAIN
ALARM
RESET
SCROLL MODE
SAVE
5
(127)
5 (127)
M9494
5-1/4 (133)
1 REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
Integrated burner control for industrial process semi-automatically
fired gas, oil, coal, or combination fuels for single and multiple
burner applications. PLC Adaptable.
• Functions include automatic burner startup sequencing, five user
selectable run sequences, four line-voltage sequence control
inputs, flame supervision, system status indication, system or selfdiagnostics
and troubleshooting.
• Requires a relay module, subbase, and amplifier for operation.
• Options include PC interface, keyboard display module, DATA
CONTROLBUS™ MODULE, remote display mounting, first-out
expanded annunciator, and COMBUSTION SYSTEM MANAGER™
software.
• Use with master system control which determines purge timing and
confirms air supply and air flow.
• Nonvolatile memory retains history files and sequencing status after
power loss.
• Optional remote reset capability.
• Five LEDs provide sequence information.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information.
Application: Primary Control - PLC Adaptable
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: selectable
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 10 oz (0.7 kg)
Approvals, CSA: Certified
Approvals, Factory Mutual: Approved.
Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments
RM7888A1019/U 15 sec 4 sec Selectable sequences
RM7888A1027/U 15 sec 10 sec For 10 sec DSI applications, selectable
sequences
70-6910 767
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7890 On-Off Primary Control with VPS
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Integrated on/off primary burner control for automatically fired
gas, oil or combination fuel single burner applications. Contains
Valve Proving Feature. Requires S7800A1142 Display to program
VPS feature.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self diagnostics and
troubleshooting.
• Subbase and amplifier are required for operation.
• Power LED blinks Fault Code on lockout.
• Options include PC interface, keyboard display module, DATA
CONTROLBUS™ MODULE, remote display module, first-out
expanded annunciator, and COMBUSTION SYSTEM MANAGER™
software.
• Five LEDs provide sequence information.
• Interchangeable plug-in flame amplifiers.
• Optional local or remote annunciation of operation and fault
information.
• Nonvolatile memory retains history files and sequencing status after
power loss.
• Optional remote reset capability.
• Optional report generation.
• Selectable relight or lockout on loss of flame.
• Contains Valve Proving Feature - require S7800A1142 Keyboard
Display (not provided) to set up.
Application: On-Off Primary Control w/VPS
Preignition: Yes
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: intermittent
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 13 oz (0.8 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments
RM7890A1056/U Intermittent 4 sec or 10 sec Includes programmable VPS (Valve Proving Switch) check feature
and blinking LED fault annunciation
RM7890B1048/U Intermittent 4 sec or 10 sec Includes Shutter Drive Capability, VPS (Valve Proving Switch)
check and blinking LED fault annunciation
768 70-6910
Microprocessor Burner Controls
RM7890; EC7890 On-Off Primary Controls
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Microprocessor-based integrated primary burner control for
automatically fired gas, oil or combination fuel single burner
applications. Provides level of safety, functional capability and
features beyond conventional controls.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self diagnostics and
troubleshooting.
• Subbase and amplifier are required for operation.
• Options include PC interface, keyboard display module, DATA
CONTROLBUS™ MODULE, remote display module, first-out
expanded annunciator, and COMBUSTION SYSTEM MANAGER™
software.
• Five LEDs provide sequence information.
• Interchangeable plug-in flame amplifiers.
• Optional local or remote annunciation of operation and fault
information.
• Nonvolatile memory retains history files and sequencing status after
power loss.
• Optional remote reset capability.
• Optional report generation.
• Selectable relight or lockout on loss of flame.
Application: On-Off Primary Control
Flames Establishing Period - Main: Intermittent
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier.
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: intermittent
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 13 oz (0.8 kg)
Approvals, Swiss RE: Acceptable
Material Number Voltage Flame
Establishing
Period - Pilot
Approvals,
Underwriters
Laboratories Inc.
Approvals, CSA Approvals, Factory
Mutual
Approvals, Gastec/
European
Comments
EC7890A1011/U 220 to 240 Vac
(+10, -15%)
4 sec or 10 sec Report No. 1D0A1.AF
EC7890B1010/U 220 to 240 Vac
(+10, -15%)
4 sec or 10 sec Report No. 1D0A1.AF Includes Shutter
Drive Capability
EC7890B1028/U 220 to 240 Vac
(+10, -15%)
4 sec or 10 sec Report No. 1V9AO.AF. Includes Shutter
Drive Capability
RM7890A1015/U 120 Vac
(+10, -15%)
4 sec or 10 sec Component Recognized,
File No. MP268; Guide
No. MCCZ.
Certified, File No.
LR95329-3.
Report No. OX4A5.AF.
RM7890A1031/U 120 Vac
(+10, -15%)
30 sec fixed Component Recognized,
File No. MP268; Guide
No. MCCZ.
Certified, File No.
LR95329-3.
Report No. OX4A5.AF.
RM7890A1064/U 120 Vac
(+10, -15%)
4 sec or 10 sec Report No. 1D0A1.AF GASTEC: CE-63AP3070/1,
Approved to EN298.
RM7890B1014/U 120 Vac
(+10, -15%)
4 sec or 10 sec Component Recognized,
File No. MP268; Guide
No. MCCZ.
Certified, File No.
LR95329-3.
Report No. OX4A5.AF. Includes Shutter
Drive Capability
RM7890B1030/U 120 Vac
(+10, -15%)
Fixed 4 sec or
10 sec PFEP
Component Recognized,
File No. MP268; Guide
No. MCCZ.
Certified, File No.
LR95329-3.
Report No. OX4A5.AF. Includes Shutter
Drive Capability,
Alarm sounds when
Reset pushed.
RM7890B1055/U 120 Vac
(+10, -15%)
4 sec or 10 sec Component Recognized,
File No. MP268; Guide
No. MCCZ.
Certified, File No.
LR95329-3.
Report No. OX4A5.AF. Gastec EN268 Report
1156791
Includes Shutter
Drive Capability
RM7890D1004/U 120 Vac (+10,
-15%)
15 sec or 30
sec
Component Recognized,
File No. MP268; Guide
No. MCCZ.
Certified, File No.
LR95329-3.
Report No. OX4A5.AF. Higher Flame Sensor
Voltage for Infra Red
Heater Applications
70-6910 769
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7895; EC7895 On-Off Primary Control with Prepurge
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Microprocessor-based integrated primary burner control for
automatically fired gas, oil, or combination fuel single burner
applications. Provides level of safety, functional capability and
features beyond conventional controls.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self diagnostics and
troubleshooting.
• Subbase, amplifier, and prepurge timer are required for operation.
• Options include PC interface, keyboard display module, DATA
CONTROLBUS™ MODULE, remote display module, first-out
expanded annunciator, and COMBUSTION SYSTEM MANAGER™
software.
• Five LEDs provide sequence information.
• Interchangeable plug-in flame amplifiers.
• Optional local or remote annunciation of operation and fault
information.
• Nonvolatile memory retains history files and sequencing status after
power loss.
• Optional remote reset capability.
• Optional report generation. Selectable relight or lockout on loss of
flame.
• Airflow switch check.
Application: On-Off Primary Control with Prepurge
Interlocks: Selectable
PrePurge: Determined by ST7800A Purge Timer Card
Required Components: Q7800 Universal Wiring Subbases, Flame
Signal Amplifier and ST7800A Plug-in Purge Timer Card
Frequency: 50 Hz; 60 Hz (±10%)
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 15 oz (0.9 kg)
Approvals, Swiss RE: Acceptable
Used With: 7800 Series Amplifiers (Except RM7895E1002/U uses
R7847 ONLY)
Material Number Voltage Pilot Type AirFlow
Check
Delayed
Main
Valve
Flame
Establishing
Period -
Main
Flame
Establishing
Period -
Pilot
Approvals,
Underwriters
Laboratories Inc.
Approvals,
CSA
Approvals,
Control
Safety
Devices
Approvals,
Factory
Mutual
Comments
EC7895A1010/U 220 to
240 Vac
(+10, -15%)
intermittent No Intermittent 4 sec or
10 sec
Report No.
1D0A1.AF
EC7895C1000/U 220 to
240 Vac
(+10, -15%)
interrupted Yes 10 sec 4 sec or
10 sec
Report No.
1D0A1.AF
RM7895A1014/U 120 Vac
(+10, -15%)
intermittent No Intermittent 4 sec or
10 sec
Component
Recognized,
File No. MP268;
Guide No. MCCZ.
Certified,
File No.
LR95329-3.
Acceptable:
CSD-1
Report No.
OX4A5.AF
RM7895A1048/U 120 Vac
(+10, -15%)
intermittent No Intermittent 4 sec or
10 sec
Component
Recognized,
File No. MP268;
Guide No. MCCZ.
Certified,
File No.
LR95329-3.
Acceptable:
CSD-1
Report No.
OX4A5.AF
Includes ignition
cut-out during
PFEP and special
sequence for early
spark termination
RM7895B1013/U 120 Vac
(+10, -15%)
intermittent Dynamic No Intermittent 4 sec to
10 sec
Component
Recognized,
File No. MP268;
Guide No. MCCZ.
Certified,
File No.
LR95329-3.
Acceptable:
CSD-1
Report No.
OX4A5.AF
RM7895C1012/U 120 Vac
(+10, -15%)
interrupted Yes 10 sec 4 sec or
10 sec
Component
Recognized,
File No. MP268;
Guide No. MCCZ.
Certified,
File No.
LR95329-3.
Acceptable:
CSD-1
Report No.
OX4A5.AF
RM7895C1020/U 120 Vac
(+10, -15%)
interrupted Yes 10 sec 10 sec Component
Recognized,
File No. MP268;
Guide No. MCCZ.
Certified,
File No.
LR95329-3.
Acceptable:
CSD-1
Report No.
OX4A5.AF
Includes ignition
cut-out during
PFEP and special
sequence for early
spark termination
RM7895D1011/U 120 Vac
(+10, -15%)
interrupted Dynamic Yes 10 sec 4 sec or
10 sec
Component
Recognized,
File No. MP268;
Guide No. MCCZ.
Certified,
File No.
LR95329-3.
Acceptable:
CSD-1
Report No.
OX4A5.AF
RM7895E1002/U 120 Vac
(+10, -15%)
intermittent No Intermittent 15 sec or
30 sec
Component
Recognized,
File No. MP268;
Guide No. MCCZ.
Certified,
File No.
LR95329-3.
Acceptable:
CSD-1
Report No.
OX4A5.AF
Higher Flame
Sensor Voltage for
Infra Red Heater
Applications
770 70-6910
Microprocessor Burner Controls
RM7896 On-Off Primary Control with Pre- and Post-Purge
Dimensions in inches (millimeters)
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M5003B
(133)
BURNER CONTROL
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4
1
Microprocessor-based integrated full-function primary burner
control for automatically fired gas, oil, or combination fuel single
burner applications. Provides level of safety, functional capability
and features beyond conventional controls.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and
troubleshooting.
• Subbase, amplifier and purge card are required for operation.
• Options include PC interface, keyboard display module, DATA
CONTROLBUS™ MODULE, remote display module, first-out
expanded annunciator, and COMBUSTION SYSTEM MANAGER™
software.
• 15 second postpurge.
• Five LEDs provide sequence information.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information.
• Nonvolatile memory retains history files and sequencing status after
power loss.
• Optional remote reset capability.
• Optional report generation.
• Selectable recycle or lockout on loss of airflow or flame.
• Shutter drive output.
• Airflow switch check.
• Delayed main valve.
Application: On-Off Primary Control with Pre- and Post-purge
Interlocks: Selectable
PrePurge: Determined by ST7800A Purge Timer Card
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz; 60 Hz (±10%)
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 15 oz (0.9 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Material Number Pilot Type AirFlow Check Flame Establishing
Period - Main
Flame Establishing
Period - Pilot
Delayed Main
Valve
PostPurge Comments
RM7896A1012/U intermittent Intermittent 4 sec or 10 sec No 15 sec Includes Pre- and Post-Purge.
RM7896C1010/U interrupted 10 sec 4 sec or 10 sec Yes 15 sec Includes Pre- and Post-Purge.
RM7896D1019/U interrupted Dynamic 10 sec 4 sec or 10 sec Yes 15 sec Includes Pre- and Post-Purge.
RM7896D1027/U interrupted Dynamic 10 sec 4 sec or 10 sec Yes 60 sec Blinking Fault code LED, early spark
termination when flame sensed, pre- and
post-purge
70-6910 771
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
RM7897 Automatic Primary Control with Programmable Post-Purge
Microprocessor-based integrated full-function primary burner
control for automatically fired gas, oil, or combination fuel
single burner applications. Programmable Post-Purge. Requires
S7800A1142 Display to program post-purge feature.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and
troubleshooting.
• Subbase, amplifier and purge card are required for operation.
• Options include PC interface, keyboard display module, DATA
CONTROLBUS™ MODULE, remote display module, first-out
expanded annunciator, and COMBUSTION SYSTEM MANAGER™
software.
• Five LEDs provide sequence information. Power LED blinks fault
code on Safety Shutdown.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information.
• Nonvolatile memory retains history files and sequencing status after
power loss.
• Optional remote reset capability.
• Optional report generation.
• Selectable recycle or lockout on loss of airflow or flame.
• Shutter drive output.
• Airflow switch check.
• Delayed main valve.
• Programmable post-purge using S7800A1142 Keyboard Display (not
provided).
Application: On-Off Primary Control with Pre- and Programmable
Post-purge
Flame Establishing Period - Pilot: 4 sec or 10 sec
Interlocks: Selectable
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: programmed with S7800A1142 display
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Frequency: 50 Hz; 60 Hz (±10%)
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 15 oz (0.9 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Control Safety Devices: Acceptable: CSD-1
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Material Number Voltage Pilot Type Delayed Main Valve Comments Used With
RM7897A1002/U 120 Vac (+10, -15%) selectable Includes blinking LED fault annunciation feature 7800 Series Amplifiers
RM7897C1000/U 120 Vac (+10, -15%) selectable Yes Includes blinking LED fault annunciation feature 7800 Series Amplifiers
772 70-6910
Microprocessor Burner Controls
RM7898 On-Off Primary Control with VPS
Integrated full-function primary burner control for gas, oil,
or combination fuel single burner applications. Include
Programmable Post-Purge and Valve Proving Feature. Requires
S7800A1142 Display to program VPS and post-purge features.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and
troubleshooting.
• Subbase, amplifier and purge card are required for operation.
• Options include PC interface, keyboard display module, DATA
CONTROLBUS™ MODULE, remote display module, first-out
expanded annunciator, and COMBUSTION SYSTEM MANAGER™
software.
• Programmable post-purge.
• Five LEDs provide sequence information. Power LED Blinks Fault
code on safety shutdown.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault information.
• Nonvolatile memory retains history files and sequencing status after
power loss.
• Optional remote reset capability.
• Optional report generation.
• Selectable recycle or lockout on loss of airflow or flame.
• Shutter drive output.
• Airflow switch check.
• Programmable post-purge and Valve Proving feature with
S7800A1142 Keyboard Display (not supplied).
Application: On-Off Primary Control w/VPS
Flame Establishing Period - Pilot: 4 sec or 10 sec
Interlocks: Selectable
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: programmed with S7800A1142 display
Required Components: Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
Signal Amplifier. ST7800A Plug-in Purge Timer Card.
Frequency: 50 Hz; 60 Hz (±10%)
Pilot Type: selectable
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 15 oz (0.9 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Pending
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. OX4A5.AF.
Material Number Voltage Early Spark Terminations Comments Used With
RM7898A1000/U 120 Vac (+10, -15%) Includes blinking LED fault annunciation feature 7800 Series Amplifiers
RM7898A1018/U 120 Vac (+10, -15%) Special Sequence Includes blinking LED fault annunciation feature,
with early spark termination
7800 Series Amplifiers
70-6910 773
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
R7120M Fireye M Series Replacement Control
The Honeywell R7120M Burner Control Modules are
microprocessor-based integrated burner controls. It is a plug in
replacement of Fireye M series controls for automatically fired
gas, oil or combination fuel on/off single burner applications.
• Functions provided by the R7120M include automatic burner
sequencing, flame supervision, system status indication, system or
self-diagnostics and troubleshooting.
• Plug in replacement for Fireye M series controls using the existing
Fireye wiring subbase.
• Require ST7800 Purge Timer and appropriate R78XX Amplifier to
complete the replacement.
Application: Replacement Primary Control for Fireye M Series -
Intermittent Pilot
Interlocks: Running
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: programmed with S7800A1142 display
Required Components: R7847, R7848, R7849, R7851, R7852,
R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge
Timer Card.
Frequency: 50 Hz; 60 Hz
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +135°F (-40°C
to +57°C)
Approximate, Dimensions: 7 in. wide x 6 5/32 in. high x 5 3/4 in. deep
(177 mm wide x 156 mm high x 146 mm deep)
Weight lb. (kg): 3 lb 1 oz (1.4 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Material Number Voltage Pilot Type AirFlow Check Flame Establishing Period
- Main
Flame Establishing Period
- Pilot
Comments
R7120M1001/U 120 Vac (+10, -15%) intermittent User selectable Intermittent 4 sec or 10 sec On/Off
R7120M1019/U 120 Vac (+10, -15%) interrupted User selectable 10 sec 4 sec or 10 sec On/Off
774 70-6910
Microprocessor Burner Controls
R7140 Programmers
Dimensions in inches (millimeters)
5-3/4 (146)
1-1/4
(32)
RESET
POWER
PILOT
FLAME
MAIN
ALARM
S _ +
5
(127)
5 (127)
7 (177)
6-5/32
(156)
BURNER CONTROL
M22604A
The Honeywell R7140G, L, M Burner Control Modules are
microprocessor-based integrated burner control for automatically
fired gas, oil or combination fuel single burner applications.
• Functions provided by the R7140G, L, M include automatic burner
sequencing, flame supervision, system status indication, system or
self-diagnostics and troubleshooting.
• Upgrade replacement for BC7000 or R4140 legacy Programmer
controls.
• Require ST7800 Purge Timer and appropriate R78XX Amplifier to
complete the replacement.
Application: Upgrade Replacement Programming Control for R4140
or BC7000
Preignition: Yes
PrePurge: Determined by ST7800A Purge Timer Card
PostPurge: 15 sec
Early Spark Termination: Yes, 5 sec
Required Components: R7847, R7848, R7849, R7851, R7852,
R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge
Timer Card.
Voltage: 120 Vac (+10, -15%)
Frequency: 50 Hz; 60 Hz (±10%)
AirFlow Check: User selectable
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 7 in. wide x 6 5/32 in. high x 5 3/4 in. deep
(177 mm wide x 156 mm high x 146 mm deep)
Weight lb. (kg): 3 lb 1 oz (1.4 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Material Number Pilot Type Flame Establishing Period
- Main
Flame Establishing Period
- Pilot
Second Stage
Pilot Valve
Interlocks Comments
R7140G1000/U Interrupted or
Intermittent
10 sec, or 15 sec, or 30 sec,
or Intermittent
4 sec or 10 sec selectable Running LHL-LF Proven
R7140G2008/U Interrupted or
Intermittent
10 sec, or 15 sec, or 30 sec,
or Intermittent
4 sec or 10 sec Running LHL-LF Proven
R7140L1009/U interrupted 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout LHL-LF & HF Proven
R7140L2007/U interrupted 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout LHL-LF & HF Proven
R7140M1007/U Interrupted or
Intermittent
10 sec or Intermittent 4 sec or 10 sec Intermittent Running On/Off-LF Proven
70-6910 775
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
Q7800 22 Terminal Universal Wiring Subbases
Burner, panel or wall mount subbases for 7800 SERIES relay
modules and S7830A Expanded Annunciator.
• Makes electrical connections for 7800 SERIES relay modules or
S7830A Expanded Annunciator through bifurcated contacts.
• Provides terminals for field wiring.
• Twenty-two terminals.
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approvals, CSA: Certified, File No. LR95329-3.
Material Number Application Approximate, Dimensions Weight lb. (kg) Approvals, Underwriters
Laboratories Inc.
Comments Used
With
Q7800A1005/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in.
deep (126 mm wide x 126 mm high x 36 mm
deep)
7 oz (0.20 kg) Component Recognized,
File No. MP268; Guide No.
MCCZ2.
Panel mount
Q7800B1003/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in.
deep (126 mm wide x 126 mm high x 36 mm
deep)
1 lb 3 oz (0.54 kg) Component Recognized,
File No. MP268; Guide No.
MCCZ.
Burner/wall mount 2
knockouts each end
Q7800B1011/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 3 in. deep
(126 mm wide x 126 mm high x 76 mm deep)
1 lb 3 oz (0.54 kg) Component Recognized,
File No. MP268; Guide No.
MCCZ.
Burner/wall mount 3
knockouts each end
Q7800F1004/U Wiring Adapter
Subbase
5 in. high x 5 in. wide x 1 3/4 in. deep (127 mm
high x 127 mm wide x 44 mm deep)
15 oz (0.43 kg) Component Recognized,
File No. MP268; Guide No.
MCCZ2.
Burner/wall mount
adapter subbase for
RA890
RM7890
Q7800F1012/U Wiring Adapter
Subbase
5 in. high x 5 in. wide x 1 3/4 in. deep (127 mm
high x 127 mm wide x 44 mm deep)
15 oz (0.43 kg) Component Recognized,
File No. MP268; Guide No.
MCCZ2.
Burner/wall mount
adapter subbase for
R4795
RM7895
Q7800A dimensions in inches (millimeters)
12
13
14
15
16
17
18
19
20
21
22
G
L2(N)
3
4
5
6
7
8
9
10
F
USE NO. 6 MOUNTING
SCREWS (4)
M1968D
1 OPTIONAL TERMINAL TEST ACCESS COVER.
4-31/32
(126)
2-1/2
(64)
1-11/32
(34)
1-11/32
(34)
2-9/32
(58)
4-31/32
(126)
1-13/32
(36)
1
Q7800F dimensions in inches (millimeters)
12
13
14
15
16
17
18
19
20
21
22
G
L2(N)
3
4
5
6
7
8
9
10
F (11)
5 (127)
5
(127)
M5648A
1-3/4 (44)
1/4 (6)
776 70-6910
Microprocessor Burner Controls
Q7800B1003 dimensions in inches (millimeters)
12
13
14
15
16
17
18
19
20
21
22
G
L2(N)
3
4
5
6
7
8
9
10
F
7/8 in. DIA. KNOCKOUTS (7)
FOR 1/2 in. CONDUIT
USE NO. 6 MOUNTING SCREWS (4)
1 (25)
1 (25)
M1966B
REMOVE ONLY FOR
TERMINAL TEST ACCESS.
1
1
2-1/8 (54)
2-1/4
(64)
1-11/32
(34)
1-11/32
(34)
1-13/32
(36)
4-31/32
(126)
4-31/32
(126)
1-5/8
(41)
27/32 (21)
2-9/32
(58)
23/32 (18)
3/4 (19)
2-1/8
(54)
2-7/32
(56)
23/32 (18)
1/2 (12)
Q7800B1011 dimensions in inches (millimeters)
12
13
14
15
16
17
18
19
20
21
22
G
L2(N)
3
4
5
6
7
8
9
10
F
7/8 in. (22) KNOCKOUTS (9)
FOR 1/2 in. CONDUIT
USE NO. 6 MOUNTING SCREWS (4)
1 (25)
1 (25)
M9883
REMOVE ONLY FOR
TERMINAL TEST ACCESS.
1
1
2-1/8 (54)
2-1/4
(64)
1-11/32
(34)
1-11/32 (34)
1-13/32
(36)
4-31/32
(126)
4-31/32 (126)
1-5/8
(41)
27/32 (21)
2-9/32 (58)
23/32 (18)
3/4 (19)
3/4 (19)
2-1/8 (54)
3 (76)
23/32 (18)
3/4 (19)
3/4 (19)
70-6910 777
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
S7800 Keyboard Display Module
Dimensions in inches (millimeters)
2 -1 /3 2
(5 2 )
BURNER CONTROL
29/32
(23)
19/32
(15)
1-1/4
(32)
1-1/32
(26)
5/32
(4)
5/16
(8)
M22870
1/2
(13)
7/16 (11)
1-5/16
(49) 2-7/16 (62)
29/32
(23)
5/32 (4)
15/32
(12) 3-7/8 (99)
5/16
13/ (8)
32
(11)
BACK
ENTER Edit: - +
4-27/32 (123)
4-3/32 (104)
2-3/4
(69)
Provides current status of burner sequence, timing information,
hold information and lockout information, as well as selectable or
preemptive messages.
• Application flexibility.
• First-out annunciation and system diagnostics provided by 2 row by
20 column Vacuum Fluorescent Display (VFD).
• S7800A1001 offers “Call Service” (Business Card) programmable
message displayed when system lockout occurs.
• S7800A1001 series 5 and greater has selectable ModBus Feature.
• Local or remote annunciation of operation and fault information.
• First out expanded annunciation with 24 limit and interlock LEDs
enhances keyboard display module information.
• Remote reset.
Application: Keyboard Display
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x
29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep)
Weight lb. (kg): 4 oz (0.11 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Material Number Voltage Comments
S7800A1001/U 13 Vdc peak fullwave rectified (+20/-15%). English Language
S7800A1035/U 13 Vdc peak fullwave rectified (+20/-15%). French Language
S7800A1043/U 13 Vdc peak fullwave rectified (+20/-15%). German Language
S7800A1050/U 13 Vdc peak fullwave rectified (+20/-15%). Italian Language
S7800A1068/U 13 Vdc peak fullwave rectified (+20/-15%). Spanish Language
S7800A1118/U 13 Vdc peak fullwave rectified (+20/-15%). Japanese Language
S7800A1126/U 13 Vdc peak fullwave rectified (+20/-15%). Portuguese Language
778 70-6910
Microprocessor Burner Controls
S7800 Keyboard Display Module for VP Programming
Dimensions in inches (millimeters)
2 -1 /3 2
(5 2 )
BURNER CONTROL
29/32
(23)
19/32
(15)
1-1/4
(32)
1-1/32
(26)
5/32
(4)
5/16
(8)
M22870
1/2
(13)
7/16 (11)
1-5/16
(49) 2-7/16 (62)
29/32
(23)
5/32 (4)
15/32
(12) 3-7/8 (99)
5/16
13/ (8)
32
(11)
BACK
ENTER Edit: - +
4-27/32 (123)
4-3/32 (104)
2-3/4
(69)
Provides current status of burner sequence, timing information,
hold information and lockout information, as well as selectable or
preemptive messages.
• Application flexibility.
• First-out annunciation and system diagnostics provided by 2 row by
20 column Vacuum Fluorescent Display (VFD).
• “Call Service” (Business Card) programmable message displayed
when system lockout occurs.
• Local or remote annunciation of operation and fault information.
• First out expanded annunciation with 24 limit and interlock LEDs
enhances keyboard display module information. Display can be
Programmed to customize the expanded annunciator messages to
the system.
• Required to program Valve Proving and Post Purge feature on
selected 7800 Series devices.
• Can be setup for ModBus Communication.
• Provides burner controller data.
• Remote reset.
Application: Keyboard Display for VP setup
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x
29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep)
Weight lb. (kg): 4 oz (0.11 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Material Number Voltage Comments
S7800A1142/U 13 Vdc peak fullwave rectified (+20/-15%). English Language, Capable of displaying special “Call Service” messages, allows setup of
S7830A1005 Expanded Annunciator messages, used for VPS programming, and programming
Post Purge on select 7800 Devices
S7800A1167/U 13 Vdc peak fullwave rectified (+20/-15%). Spanish Language with Valve Proving, Post-purge, “Call Service”, and Expanded Annunciator
programming ability
70-6910 779
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
S7810A Data ControlBus™ Module
Dimensions in inches (millimeters)
M1986A
BURNER CONTROL
2-3/4
(69)
29/32
(23)
5/32
(4)
4-27/32
(123)
Supports remote mounting of S7800 Keyboard Display Module,
personal computer communications interface and remote reset.
• Use with remotely mounted S7800 Keyboard Display Module.
• Installs directly on the front of 7800 SERIES Relay Modules.
• Provides communications bus interface and remote reset.
Application: ControlBus™ Module
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 4 27/32 in. wide x 3 11/32 in. high x
29/32 in. deep (123 mm wide x 84 mm high x 23 mm deep)
Weight lb. (kg): 4 oz (0.11 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ2.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Material Number Voltage Comments
S7810A1009/U 13 Vdc peak fullwave rectified (+20/-15%). Includes 203541 5-wire Connector
S7810M ModBus Module
Dimensions in inches (millimeters)
1-1/8 (29)
M11349B
7/16 (11)
2-3/4
(69)
5/32
(4)
4-27/32 (123) 29/32 (23)
BURNER CONTROL
MODE
S7810M ModBus Module operates as ModBus RTU slave device.
• Provides ability to remotely mount the S7800 Keyboard Display
Module.
• Installs directly on the front of 7800 SERIES Relay Modules.
• Provides ModBus communications bus interface.
• Remote reset.
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x
29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep)
Weight lb. (kg): 4 oz (0.11 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ2.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Material Number Voltage Application Comments Approvals, Gastec/European
S7810M1003/U 13 Vdc peak fullwave rectified
(+20/-15%).
ControlBus™ Module-MODBUS Includes 208727 8 pin electrical
connector
S7810M1029/U 13 Vdc peak fullwave rectified
(+20/-15%).
ControlBus™ Module-MODBUS - CE
Certified (no reset allowed)
Includes 208727 8 pin electrical
connector
Gastec EN268 Report 1156791
780 70-6910
Microprocessor Burner Controls
S7820 Remote Reset Module
Dimensions in inches (millimeters)
M1986A
BURNER CONTROL
2-3/4
(69)
29/32
(23)
5/32
(4)
4-27/32
(123)
Serves as link between remote reset pushbutton and relay
module. Allows 7800 SERIES relay module to be reset from a
remote location.
• Reset button can be installed up to 1000 feet away.
• Installs directly on the front of 7800 SERIES relay module.
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x
29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep)
Weight lb. (kg): 3 oz (0.09 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ2.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Material Number Application Comments
S7820A1007/U Remote Reset Module Includes 203541 5-wire Connector
70-6910 781
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
S7830 First Out Expanded Annunciator
Microprocessor-based expanded annunciator to support the 7800
SERIES relay modules for first-out annunciation, sequencing,
system or self-diagnostics and troubleshooting.
• Twenty-six status LEDs.
• Front panel LED array-arranged to indicate flow of line-voltage
through string of limits, controls and interlocks.
• Selectable current and first-out LED array display status.
• Twenty-one monitored contact points.
• Access for external electrical voltage checks.
Required Components: 7800 Series Relay Modules and Q7800A, B
Subbases
Frequency: 50 Hz; 60 Hz (±10%)
Vibration: 0.5 G environment
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
(127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
x 155 mm deep with Q7800B Subbase)
Weight lb. (kg): 1 lb 6 oz (0.62 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MH17367; Guide No. MJAT.
Approvals, CSA: Certified, File No. LR95329.
Approvals, FCC: FCC Part 15, Class B, Emissions.
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Report No. 1V9AO.AF.
Dimensions in inches (millimeters)
5 (127) 5-5/16 (135)
5
(127)
EXPANDED ANNUNCIATOR
M5182
Proof of Closure
Preignition Interlocks
L1
Burner Switch Power
Operating Control
Auxiliary Limit 1
Auxiliary Limit 2
Low Water Cutoff
High Limit
Atomizing Limit 3
Oil Select
High Oil Pressure
Low Oil Pressure
High Oil Temperature
Low Oil Temperature
Select
Atomizing Switch
Gas Select
High Gas Pressure
Low Gas Pressure
System Lockout
First Out
Current
Airflow Switch
Auxiliary Interlock 4
Auxiliary Interlock 5
Reset Interlocks
a b c
Fuel Selection
22 21 20 19 18 17 16 15 14 13 12
Material Number Voltage Application
S7830A1005/U 120 Vac (+10, -15%) Expanded Annunciator
782 70-6910
Microprocessor Burner Controls
ST7800 Plug In Purge Timer
Provides the prepurge timing for select 7800 SERIES relay
modules. ST7800C used with the RM7838C only.
Approvals, Underwriters Laboratories Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ2.
Approvals, CSA: Certified, File No. LR95329-3.
Approvals, Factory Mutual: Approved: Report No. 2X0A1.AF.
Material Number PrePurge Application
ST7800A1005/U 2 seconds Purge Timer
ST7800A1013/U 7 seconds Purge Timer
ST7800A1021/U 10 seconds Purge Timer
ST7800A1039/U 30 seconds Purge Timer
ST7800A1047/U 40 seconds Purge Timer
ST7800A1054/U 60 seconds Purge Timer
ST7800A1062/U 90 seconds Purge Timer
ST7800A1070/U 2.5 minutes Purge Timer
ST7800A1088/U 4.0 minutes Purge Timer
ST7800A1096/U 6.0 minutes Purge Timer
ST7800A1104/U 9.0 minutes Purge Timer
ST7800A1112/U 12.0 minutes Purge Timer
ST7800A1120/U 15.0 minutes Purge Timer
ST7800A1138/U 22.0 minutes Purge Timer
ST7800A1146/U 30.0 minutes Purge Timer
ST7800C1003/U 7 seconds Purge Timer for RM7838C Only
ST7800C1011/U 20 seconds Purge Timer for RM7838C Only
ST7800C1029/U 4.0 minutes Purge Timer for RM7838C Only
ST7800C1037/U 6.0 minutes Purge Timer for RM7838C Only
ST7800C1045/U 8.0 minutes Purge Timer for RM7838C Only
ST7800C1052/U 10.0 minutes Purge Timer for RM7838C Only
ST7800C1086/U 16.0 minutes Purge Timer for RM7838C Only
ST7800C1102/U 20.0 minutes Purge Timer for RM7838C Only
ST7800C1128/U 24.0 minutes Purge Timer for RM7838C Only
ST7800C1136/U 30.0 minutes Purge Timer for RM7838C Only
70-6910 783
Commercial/Industrial
Combustion Controls
Microprocessor Burner Controls
7800 Series Accessories or Parts
Application: Accessory or Replacement Part
Material Number Comments Used With
203541/U S7800 Display
203765/U Includes 203541 5-wire Connector S7800 Display
204718A/U Includes 203541 5-wire Connector S7800 Display
204718B/U Includes 203541 5-wire Connector S7800 Display
204718C/U Includes 203541 5-wire Connector S7800 Display
205321B/U Includes 203541 5-wire Connector S7800 Display
206311/U Carrying Case for S7800 Display S7800 Display
208727/U S7810B, S7810M
221729A/U 7800 Relay Modules
221818A/U S7800 Display
221818C/U S7800 Display
50023821-001/U Includes 203541 5-wire Connector S7800 Display
50023821-002/U Includes 203541 5-wire Connector S7800 Display
784 70-6910
SOLA Controllers
SOLA™ Hydronic Control
Dimensions in inches (millimeters)
M27583
9-21/64
(237) MAX
[2] 8-21/32
(220)
6-21/64 (161)
[2] 5-19/64 (135)
[4] Ø 3/16 (5) MAX
2-19/32 (66)
The R7910A SOLA HC is a hydronic boiler control system that
provides heat control, flame supervision, circulation pump
control, fan control, boiler control, and electric ignition function. It
will also provide boiler status and error reporting.
• Frost Protection, Slow Start, Anti-condensate, Boiler Delta-T, Stack
Limit, Boiler Limit, DHW Limit, Outlet T-Rise Limit
• Primary Flame Safeguard Control
• Internal or external spark generator.
• Analog NTC Sensor Inputs (10 kohm or 12 kohm).
• Other Analog Inputs
• PID Load Control
• Digital Inputs
• Digital Outputs
• Analog Outputs
• Algorithm Prioritization
• Two Temperature Loops of Control (CH and DHW)
• High Limit Control-CH, DHW, & Stack (Meets UL 353) using dual
10 kohm NTC sensors.
• Fifteen Item Fault Code History including equipment status at time of
lockout
• Fifteen Item Alert Code Status including equipment status at time of
internal alerts
• 24 Vac Device Power
• 24 or 120 Vac Digital I/O models available.
• Flame Signal test jacks (Vdc)
• Three Status LEDs.
• UV or Flame rod Flame Sensing.
Application: Hydronic
Frequency: 50-60 Hz ± 5%
Approximate, Dimensions: 9 21/64 in. x 6 21/64 in. x 2 19/32 in.
(237 mm x 161 mm x 66 mm)
Comments: Includes Programmable features
Approvals, Control Safety Devices: Acceptable
Approvals, FCC: Part 15, Class B Emissions
Material Number Enclosure
Rating
Firing Rate Switch Flame Sensor Type Modulation Output Voltage Approvals, Underwriters
Laboratories Inc.
R7910A1001/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA);
Yes (0-10 Vdc)
24 Vac Operating; 24 Vac
Load
UL, cUL: Component
Recognized: File Number
MH20613 (MCCZ)
R7910A1019/U NEMA 1/IP 40 High Fire Switch; Low
Fire Switch
FR/UV Yes (PWM); Yes (4-20 mA);
Yes (0-10 Vdc)
24 Vac Operating; 120
Vac Load
UL, cUL: Component
Recognized: File Number
MH20613 (MCCZ)
R7910A1027/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA);
Yes (0-10 Vdc)
24 Vac Operating; 120
Vac Load
UL, cUL: Component
Recognized: File Number
MH20613 (MCCZ)
R7910A1084/U NEMA 1/IP 40 FR Yes (PWM); Yes (4-20 mA);
Yes (0-10 Vdc)
24 Vac Operating; 24 Vac
Load
UL, cUL: Component
Recognized: File Number
MH20613 (MCCZ)
R7910A1118/U NEMA I/IP 40 FR, High Energy Spark Yes (PWM) 24 Vac Operating; 24 Vac
Load
UL, cUL Component File
No. MH20613 (MCCZ)
70-6910 785
Commercial/Industrial
Combustion Controls
SOLA Controllers
SOLA™ Steam Control
Dimensions in inches (millimeters)
[2] 5-19/64 (135)
9-21/64
(237) MAX
[4] Ø 3/16 (5) MAX
2-19/32 (66)
6-21/64 (161)
[2] 8-21/32
(220)
M27063
The R7911A SOLA SC is a steam boiler control system that
provides heat control, flame supervision, fan control, boiler
control, and electric ignition function. It will also provide boiler
status and error reporting.
• Slow Start, Stack Limit, Boiler Limit
• Primary Flame Safeguard Control
• Internal or external spark generator.
• Analog Stack Temp NTC Sensor Inputs (10kohm or 12kohm).
• Other Analog Inputs
• PID Load Control
• Digital Inputs
• Digital Outputs
• Analog Outputs
• Algorithm Prioritization
• High Limit Control - Stack (Meets UL 353) using dual 10 kohm NTC
sensors.
• Fifteen Item Fault Code History including equipment status at time of
lockout
• Fifteen Item Alert Code Status including equipment status at time of
internal alerts
• 24 Vac Device Power
• 24 or 120 Vac Digital I/O models available.
• Flame Signal test jacks (Vdc)
• Three Status LEDs.
• UV or Flame rod Flame Sensing.
Application: Steam
Frequency: 50-60 Hz ± 5%
Approximate, Dimensions: 9 21/64 in. x 6 21/64 in. x 2 19/32 in.
(237 mm x 161 mm x 66 mm)
Comments: Includes Programmable features
Approvals, Control Safety Devices: Acceptable
Approvals, FCC: Part 15, Class B Emissions
Approvals, Underwriters Laboratories Inc.: UL, cUL: Component
Recognized: File Number MH20613 (MCCZ)
Material Number Enclosure Rating Firing Rate Switch Flame Sensor Type Modulation Output Voltage
R7911A1000/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load
R7911A1026/U NEMA 1/IP 40 High Fire Switch; Low
Fire Switch
FR/UV No (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load
786 70-6910
SOLA Controllers
S7910 SOLA™ Keyboard Display
Dimensions in inches (millimeters)
NOTE: STICKS OUT BACK 1/4 INCH (6). M27094
2-45/64
(69)
1-1/2
(38)
2-9/32
(58)
4-3/4 (121)
5-21/32 (144)
4-1/16
(103)
4X Ø 3/16 (5) ± 1/64 (0)
The S7910 Local Keyboard display interface provides setpoint and
control adjustments to parameters of the R7910 SOLA Hydronic
Control. The S7910 includes four function buttons, and all data is
displayed on an LCD with backlight.
• Burner control state, sequence
• Rate control manual adjustment
• Lockout code
• Alert and Hold Reason
• CH, CH TOD, DHW, and DHW TOD setpoints
• Communication interface with R7910.
• First out and system status and diagnostics provided through the
LCD.
• Local communication of operation and fault information.
• Control DHW, Inlet, Outlet, Delta T (Outlet-Inlet), and Stack
Temperatures
• Set-up
• Diagnostics
• Blue, includes (future feature: TOD), only “talks” to Commercial
R7910A, Flame Signal Vdc, pilot hold function, screw mounting
Ambient Temperature Range: 32°F to 120°F (0°C to 49°C)
Shipping and Storage Temperature Range: -60°F to +150°F (-51°C
to +66°C)
Approximate, Dimensions: 4-1/6 in. high x 5-21/32 in. wide (103 mm
high x 144 mm wide)
Operating Humidity Range (% RH): 85% relative humidity
continuous, noncondensing
Weight: 4 oz (124 g)
Approvals, FCC: Part 15, Class B emissions.
Approvals, Underwriters Laboratories Inc.: UL, cUL: Component
Recognized: File Number MH20613 (MCCZ)
Material Number Electrical Ratings Vibration Description Used With
S7910A1008/U 24 VAC powered from R7910A 0.5 G environment Keyboard Display Module R7910
70-6910 787
Commercial/Industrial
Combustion Controls
SOLA Controllers
S7999D SOLA™ System Operator Interface
The S7999D can be used to monitor an individual boiler and also
used for multiple boiler applications in a lead/lag arrangement.
It consists of 2 RS485 ports and a USB port. The S7999D display
can be flush front or mounted behind in a panel cutout. Wiring
connections are through a removable 8-pin wiring connector.
• Individual boiler status, configuration, history and diagnostics
• Allows configuration and monitoring of the Sola Controls (R7910
Hydronic Controls or R7911 Steam Control) burner control sequence,
flame signal, diagnostics, historical files, and faults
• Allows switching view between multiple boilers and lead-lag master/
slaves
• Real-time data trending analysis and transferring saved trend data to
Excel spreadsheet
• 7” 800 x 480, 24 bit high resolution color LCD touch screen for clarity
• Audio output with integral speaker for sound output.
• Adjustable backlight control
• Real time clock with coin-cell battery back-up (CR2032)
• Volume control
• Screen Capture function to capture screen images
• USB port for file transfers and software updates
• 2 RS-485 (COM1 & 2) ports for Modbus™ interface to Sola controls
and BAS Gateway.
• Windows® CE 6.0 Operating System
• 8-pin connector, back-up battery and mounting hardware are
provided
Application: Interface Display
Frequency: 50-60 Hz ± 5%
Ambient Temperature Range: 14°F to 122°F (-10°C to 50°C)
Shipping and Storage Temperature Range: -13°F to 155°F (-25°C to
60°C)
Approximate, Dimensions: 9-13/32 in. wide x 6-21/32 in. high x
1-9/16 in. deep (239 mm wide x 169 mm high x 40 mm deep)
Operating Humidity Range (% RH): 85% RH continuous, noncondensing
Comments: Black Plastic Border
Approvals, FCC: FCC Part 15, Class A digital device
Approvals, Canadian Underwriters Inc.: Component Recognized:
File Number MH20613 (MCCZ)
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File Number MH20613 (MCCZ)
Material Number Voltage Description Used With
S7999D1006/U 24 Vac System Operator Interface with Black Plastic Border R7910/R7911
788 70-6910
SOLA Controllers
PM7910 Program Module
The PM7910 Program Module is an optional plug-in for the R7910
SOLA HC and R7911 Sola SC. From the system level the S7999
System Operator Interface can direct the R7910/R7911 to transfer
or retrieve parameter information with the Program Module.
• Can be removed or installed while the R7910 or R7911 is powered.
• Facilitate multiple controller setups.
• Backup and restore the R7910 programmable data including:
— Non-safety parameter values — Parameter Control Blocks
(information on how the parameter values may be modified.)
Material Number Application Comments
PM7910A1013/U Support backup and restore Indicator LEDs - One (Status LED) Blinking LED indicated the Program Module is
properly seated and powered from the R7910/R7911
SOLA™ Accessories or Parts
Application: Single element sensor with 6" leadwire with socket.
Material Number Application
32003971-002/U 10K Ohm Single element sensor with 6" Leadwire with Socket
32003971-003/U 10K Ohm Single element sensor with 42" leadwires, includes wire nuts (2), #8 mounting screws (3), anchors (2), sensor clip (1), tie strap (2)
50001464-006/U 10K Ohm Dual Element Sensor with 6" leadwires with Female Socket
50001464-007/U 10K Ohm Dual Element Sensor with 42" leadwires without connector
50032893-001/U Bag of connectors for R7910 and R7911 Controllers
70-6910 789
Commercial/Industrial
Combustion Controls
ControLinks Fuel Air Control System
R7999A ControLinks™ Fuel Air Controller
1-15/16
(48)
5-3/16
(131)
7-3/16
(182)
2-13/16
(71)
3 (76)
INSTALLED
ON Q7999
M16548C
R7999
Q7999
1 DDL PORT (RS485).
1
Uses microprocessor-based technology to control the ML7999
Universal Parallel Positioning Actuators. This represents a value
added replacement of mechanical cam and linkage assembly
controlling the relationship between fuel, airflow and flue gas
recirculation (if used) on a power burner. The ControLinks Fuel
Air Control System consists of the R7999 Fuel Air Controller,
Q7999 Wiring Subbase, ML7999 Universal Parallel Positioning
Actuator and ZM7999 Configuration Software. The R7999, with
one communications port, provides communications capabilities
similar to those found in the 7800 SERIES controls.
• Fast burner setup via PC or laptop
• Fuel, air, FGR profile download capability
• Two independent fuel profiles with or without FGR
• 7 to 24 point profiles
• Programmable behaviors of all actuators during Purge and Standby
• Programmable behavior of non-selected fuel actuator
• Independent light off and minimum modulation positions
• Wide power voltage input range (100 to 120 Vac, 50/60 Hz
Auto/Manual input)
• Manual mode firing rate input
• Pluggable controller to wiring subbase
• Multipurpose communications port
• Field-configurable device
• Integrated boiler shock protection algorithms: Water temperature low
fire hold
• Stack temperature low fire hold. FGR and low fire hold
• Selectable FGR hold based on stack temperature
• Programmable behavior of FGR actuator during purge
• Maximum modulation limit capability
• Remote reset input
• Automated actuator endpoint seeking process
• CSD-1 and NFPA acceptable
Voltage: 100 to 120 Vac
Vibration: 0.0 to 0.5g continuous
Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
to +60°C)
Approvals, Underwriters Laboratories Inc.: Listed: Report No.
MH17367
Operating Humidity Range (% RH): 90% RH maximum, noncondensing
Replacement Parts:
32002515-001/U – 3 pin electrical connector, for R7999
Material Number Frequency Description
R7999A1005/U 50 Hz; 60 Hz Fuel Air Ratio Controller, 100 to 120 Vac, 50/60 Hz.
790 70-6910
ControLinks Fuel Air Control System
S7999 ControLinks™ System Display
With the S7999. Each burner control, fuel/air ratio control,
expanded annunciator other Modbus devices present on the
burner system can be viewed individually to determine its status.
• Color (7" diagonal). Touch Screen User Interface
• Flush Mounting
• Allows setup and monitoring of R7999 ControLinks
• Two RS485 and one USB communication ports
• Screen saver, contrast control and volume control
• Modbus communication allows monitoring up to 99 different controls
• Allows Programmable Expanded Annunciator terminal naming
• Allows R7999 ControLinks EEPROM backup and restore
• Battery backup prevents losing date and time
Application: Interface Display
Temperature Range: Ambient - 14°F to 122°F (Ambient - -10°C to
50°C)
Shipping and Storage Temperature Range: -13°F to 155°F (-25°C to
60°C)
Approvals, Underwriters Laboratories Inc.: Component Listed
Approvals, FCC: FCC Part 15, Class A digital device
Used With: R7999
Operating Humidity Range (% RH): 85% RH continuous, noncondensing
Material Number Voltage Description
S7999D1048/U 24 Vac S7999D System Display for R7999 ControLinks Configuration and System Monitoring
Q7999A ControLinks™ Fuel Air Control Wiring Subbase
Provides terminals for field wiring for the R7999A ControLinks™
Fuel Air Controller. Terminals on the R7999A, B Controller engage
the Q7999 contacts to make electrical connections. The Q7999A
Subbase is panel-mounted.
• Quick-mount wiring subbase for R7999A, B Fuel Air Ratio
Controllers.
• Allows wiring of control system before installation of controller.
• Panel-mounted.
• NEMA 1 enclosure.
Vibration: 0.0 to 0.5g continuous
Shipping and Storage Temperature Range: -40°F to +150°F (-40°C
to +65°C)
Approvals, Underwriters Laboratories Inc.: Listed: Report No.
MH17367
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Weight oz. (k): 10 oz (0.28 kg)
Material Number Voltage Frequency Description
Q7999A1006/U 100 to 120 Vac 50 Hz; 60 Hz Fuel Air Ratio Controller Wiring Subbase
Q7999A1014/U 100 to 120 Vac 50 Hz; 60 Hz Fuel Air Ratio Controller Wiring Subbase
70-6910 791
Commercial/Industrial
Combustion Controls
ControLinks Fuel Air Control System
ML7999A Universal Parallel-Positioning Actuator
ML7294 Non-Spring Return Direct Coupled Actuators control
dampers or valves in HVAC applications. The ML7294 Non-Spring
Return DCA accepts a current or voltage signal from an electronic
controller to position a damper or valve.
• Password protected using eight-digit hexadecimal identification
signal
• Separate wiring compartment between line voltage power wiring and
low voltage control
• Couples directly to a 1/2-in. shaft with no additional parts required;
couples directly to 5/16-in. and 3/8-in. shafts using self-centering
shaft reduction accessories
• Shaft coupler assembly available for shafts larger than 1/2-in.
• Bracket accessory kit available for mounting to Honeywell V51
butterfly gas valves
• Visual indication of actuator position
• NEMA 2
• IF54 with weatherproof kit
Vibration: 0.0 to 0.5g continuous
Shipping and Storage Temperature Range: -40°F to +150°F (-40°C
to +65°C)
Approvals, Underwriters Laboratories Inc.: Meets UL873
Approvals, CSA: Certified
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Approvals, CE: Certified
Material Number Voltage Frequency Description
ML7999A2001/U 15 VA, 100 to 240 Vac 50 Hz; 60 Hz Universal Parallel-Positioning Actuator. Medium torque electronic actuator with a precision feedback
potentiometer and integral power supply capable of direct line voltage connection. Must be used
with a Series 2 R7999.
ML7999B Universal Direct Coupled Actuator
Dimensions in inches (millimeters)
4 (102) 7/8 (22)
1-7/8 (47)
1/2
(13)
3-1/2 (89)
1-5/8
(41)
5-1/2
(140)
6
(153)
M16466
1/4-28
unF
Honeywell ML7999B universal direct coupled actuator provides
100 lb-in. torque, 4 to 20 mA control input to control combustion
air dampers and modulation valves. Includes precision drive shaft
control and integral power supply.
• Separate wiring compartment between line voltage power wiring and
low voltage control
• Programmable actuator stroke against 4-20 mA input
• Couples directly to 1/2-in. shaft with no additional parts required;
couples directly to 5/16- and 3/8-in. shafts using available selfcentering
shaft reduction accessories
• Shaft coupler assembly available for shafts larger than 1/2-in.
• Bracket accessory kit available for mounting to Honeywell V51
butterfly gas valves
• Visual indication of actuator position
• NEMA 2
• IF54 with weatherproof kit
Vibration: 0.0 to 0.5g continuous
Shipping and Storage Temperature Range: -40°F to +150°F (-40°C
to +65°C)
Approvals, Underwriters Laboratories Inc.: Meets UL873
Approvals, CSA: Certified
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Approvals, CE: Certified
Accessories:
32002935-001/U – Weatherproofing kit for actuator, ML7999
ControLinks (NEMA 3).
Material Number Voltage Frequency Description
ML7999B1002/U 15 VA, 100 to 240 Vac 50 Hz; 60 Hz Universal Parallel-Positioning Actuator. Medium torque electronic actuator with a precision feedback
potentiometer and integral power supply capable of direct line voltage connection.
792 70-6910
ControLinks Fuel Air Control System
ML7999 Accessories
Material Number Description
201391/U Shaft Adapter for 3/8 in. round or square valve shaft
32002935-001/U Weatherproofing kit for actuator, ML7999 ControLinks (NEMA 3).
32003167-001/U Shaft Adapter for 5/16 in. round or square shaft
32003168-001/U Shaft Adapter for 3/4 in. round shaft only
32003168-002/U Shaft Adapter for 5/8 in. round shaft only
32003168-003/U Shaft Adapter for 9/16 in. round shaft only
32003396-002/U V51E Mounting Kit for ML7999 Actuator (2-1/2, 3 & 4 in. valves). Includes angle bracket, mounting bracket, screws, nuts and washers, and
instructions.
50036542-001/U Auxiliary Switch Mounting Plate for ML7999B for 201052A or 201052B Auxiliary switch assembly
ZM7999A ControLinks Fuel Air Control System Configuration
Software
The ZM7999 Software Configuration Tool reduces burner setup
time by letting you create an R7999 Controlinks burner modulation
curve. The software assists you through the commissioning
process and when it’s complete, you can monitor the system realtime.
• Minimum Hardware Requirements: PC or laptop with a Pentium©
processor.
• Windows® 95 or Windows® 98.
• 16 MB of RAM.
• 1G hard drive with 100 MB of free memory.
• 4X (or higher) CD-ROM drive.
• Mouse.
• Super VGA color monitor (800 x 600 resolution suggested).
Material Number Description Used With
ZM7999A1006/U Configuration Software R7999
ControLinks Accessories
Material Number Description Used With
32002515-001/U 3 pin electrical connector, for R7999 R7999
50020034-001/U 9 pin electrical connector, for S7999B S7999B
70-6910 793
Commercial/Industrial
Combustion Controls
Network Interface Communications
QM4520A Data Acquisition Module
The QM4520A RS-232 to RS485 Converter allows a PC to
communicate with multiple devices on a single bus, over greater
distances.
• Mount on DIN rail, panel or in a piggyback stack.
• Uses unregulated power between +10 Vdc and +30 Vdc.
• Transmit data on single twisted pair (RS-485).
• Plug-in screw terminal blocks assure simple installation,
maintenance and modification.
• Clean and reliable communications assured by noise-suppressing
special circuitry.
• RS-485 communications reduce the number of required cables,
connectors and conditioners.
• Modules can be remotely mounted up to 4,000 ft (1.2 km) away.
Electrical Connections: Plug-in screw terminal block.
Ambient Temperature Range: 32°F to 158°F (0°C to 70°C)
Voltage: Unregulated +10 Vdc to +30 Vdc - Power supply not provided.
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Approximate, Dimensions: 2 11/32 in. x 4 13/16 in. x 1 3/16 in.
(60 mm x 122 mm x 30 mm)
Material Number Connection Type Description Used With
QM4520A1004/U RS-232 (4-wire: TX, RX, RTS, GND) (Null modem may be required.) RS-232 to RS-485 Converter ZM7850 or ZM7999 software
794 70-6910
Flame Amplifiers
7800 SERIES and R7140 Flame Signal Amplifiers
Solid state plug-in amplifiers that respond to flame detector inputs
to indicate the presence of flame when used with 7800 SERIES
relay modules.
• Flame failure response time of 0.8 or 3.0 seconds (1.0 or 2.0 for CE
approved devices).
• Flame signal strength ranges from 0.0 to 5.0 Vdc.
• Plug into 7800 relay module through printed circuit board edge
connector keyed for proper orientation.
• Flame signal test jacks to measure amplifier flame signal voltage.
• Color-coded labels identify flame detection type.
• Dynamic Self-Check Amplifier test the detectors and all electronic
components in the flame detection system.
• Ampli-check tests the amplifier and 7800 SERIES Relay.
• None (standard) is just tested at normal system startup.
• 7800 SERIES relay module locks out on safety shutdown with flame
detection system failure.
• Compatible with existing Honeywell flame detectors (order
separately).
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. LR95329-3
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 1V9A0.AF
Material
Number
Type Flame Failure
Response Time
(sec)
Self Checking Use With Primary Safety
Control
Use With Flame Sensor Comments
R7824C1002/U Ultraviolet 3.0 sec Dynamic Self-Check RM7824 C7024E, F Flame Detector Color: Green
R7847A1025/U Rectification 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005,
C7007, C7008, C7009, Q179
Color: Green
R7847A1033/U Rectification 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005,
C7007, C7008, C7009, Q179; Gas, oil, coal:
Ultraviolet Flame Sensor C7012A, C
Color: Green
R7847A1074/U Rectification 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9,
Q179 for impedance matching for leadwire runs >
50' or Ultraviolet Flame Sensor C7012A, C
Color: Green
R7847A1082/U Rectification 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9,
Q179 for impedance matching for leadwire runs >
50' or Ultraviolet Flame Sensor C7012A, C
Color: Green
R7847B1023/U Rectification 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005,
C7007, C7008, C7009, Q179
Color: Green
R7847B1031/U Rectification 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005,
C7007, C7008, C7009, Q179; Gas, oil, coal:
Ultraviolet Flame Sensor C7012A, C
Color: Green
R7847B1064/U Rectification 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9,
Q179 for impedance matching for leadwire runs >
50' or Ultraviolet Flame Sensor C7012A, C
Color: Green
R7847B1072/U Rectification 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9,
Q179 for impedance matching for leadwire runs >
50' or Ultraviolet Flame Sensor C7012A, C
Color: Green
R7847C1005/U Rectification 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7012E, F Color: Green
R7848A1008/U Infrared 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7015 Color: Red
R7848B1006/U Infrared 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7015 Color: Red
R7849A1015/U Ultraviolet 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple
R7849A1023/U Ultraviolet 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple
R7849B1013/U Ultraviolet 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple
R7849B1021/U Ultraviolet 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple
R7851B1000/U Optical 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil, Coal: Optical (UV, Visible Light) C7927,
C7962
Color: White
R7851B1018/U Optical 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil, Coal: Optical (UV, Visible Light) C7927,
C7962
Color: White
R7851C1008/U Optical 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Optical (UV only) C7961E, F Color: White
R7852A1001/U Infrared 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7915 Color: Red/White
R7852B1009/U Infrared 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7915 Color: Red/White
R7861A1026/U Ultraviolet 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7061 Color: Purple
R7861A1034/U Ultraviolet 0.8 sec or 1.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7061 Color: Purple
R7886A1001/U Ultraviolet 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Adjustable Sensitivity Ultraviolet
Flame Sensor C7076
Color: Blue
70-6910 795
Commercial/Industrial
Combustion Controls
Flame Amplifiers
R7247; R7248; R7249; R7476 Flame Amplifiers
Solid state plug-in units respond to flame detector signal and
indicate presence of flame.
• Use with BC7000; R4140; R4075C, D, E; R4138C, D Flame
Safeguard controls and appropriate flame detector and FSP5075A1,
FSP5075A3 Flame Amplifier Modules.
Use With Primary Safety Control: R4140; BC7000; R4075C, D, E;
R4138C, D; FSP5075
Approvals, Factory Mutual: Approved: Report No. 24181.01
Material
Number
Type Flame Failure
Response
Time (sec)
Self Checking Use With Flame
Sensor
Approvals,
Underwriters
Laboratories
Inc.
Approvals,
CSA
Approvals,
Control Safety
Devices
Approvals,
Swiss RE
Comments
R7247B1003/U Rectification 2 to 4 sec Ampli-Check Gas: Rectifying
Flame Rods
C7004, C7005,
C7007, C7008,
C7009, Q179;
Gas, oil, coal:
Ultraviolet
Flame Sensor
C7012A, C
Listed: File No.
MP268, Guide
No. MCCZ2
Certified: File
No. LR1620,
Guide No.
140-A-2
Acceptable
(CSD-1)
Acceptable Color: Green
R7247C1001/U Rectification 2 to 4 sec Dynamic
Self-Check
Gas, oil, coal:
Ultraviolet
Flame Sensor
C7012E, F
Listed: File No.
MP268, Guide
No. MCCZ2
Certified: File
No. LR1620,
Guide No.
140-A-2
Acceptable
(CSD-1)
Acceptable Color: Green
R7248A1004/U Infrared 2 to 4 sec None (standard) Gas, oil, coal:
Infrared (lead
sulfide) C7015
Listed: File No.
MP268, Guide
No. MCCZ
Certified: File
No. LR1620,
Guide No.
140-A-2 (gas),
300-I-0.2 (oil)
Acceptable
(CSD-1)
Acceptable Color: Red
R7249A1003/U Ultraviolet 2 to 4 sec None (standard) Gas, oil, coal:
Ultraviolet
(Minipeeper)
C7027, C7035
Listed: File No.
MP268, Guide
No. MCCZ2
Certified: File
No. LR1620,
Guide No.
140-A-2
Acceptable
(CSD-1)
Acceptable Color: Purple
R7476A1007/U Ultraviolet 2 to 4 sec Dynamic
Self-Check
Gas, oil, coal:
Adjustable
Sensitivity
Ultraviolet Flame
Sensor C7076
Listed: File No.
MP268, Guide
No. MCCZ
Certified: File
No. LR1620,
Guide No.
140-A-2 (gas),
300-I-0.2 (oil)
Color: Blue
R7476A1015/U Ultraviolet 2 sec max. Dynamic Self-
Check
Gas, oil, coal:
Adjustable
Sensitivity
Ultraviolet Flame
Sensor C7076
Listed: File No.
MP268, Guide
No. MCCZ
Certified: File
No. LR1620,
Guide No.
140-A-2 (gas),
300-I-0.2 (oil)
Color: Blue
Flame Amplifier Accessories
Material Number Description Used With
32005301-001/U T Filter for Rectification Applications R7847, R7247
796 70-6910
Flame Rods and Flame Rod Holders
C7007 Flame Rod Holder
Used to apply flame rod in gas-fired system controlled by
rectification type flame safeguard control.
• Use with pressurized fire boxes.
• Hold flame rods firmly over the pilot or burner with a chuck and
setscrew arrangement.
• Provide electrical connection through a terminal screw.
• Allow ventilation to cool the unit or to minimize soot deposit through
a 1/2 in.
• NPT tapping.
• Mount easily with sleeve or thread type mounting adapters, and a
straight or angle body.
Type: Flame Rod
Application: Gas fired pilot or gas fired system.
Approximate, Dimensions: 1 15/16 in. high x 2 3/16 in. diameter x 3
3/16 in. long (49 mm high x 56 mm diameter x 81 mm long)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. L95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Material Number Electrical Connections Mounting Required Components Comments Used With
C7007A1001/U Terminal screw 1/2 in.-14 NPT male 102709A -12 in. Flame Rod; 102709B -18 in.
Flame Rod; 102709C -24 in. Flame Rod;
102709D -36 in. Flame Rod; or 102709E -48 in.
Flame Rod
Holder only, order Kanthal
flame rod separately.
Flame Amplifiers: R7247A,
B, R7847A, B, R7257,
R7289
C7008 Flame Rod Holder
Miniature “spark plug” type flame rod holder with threaded base,
snap-on cover and Kanthal A-1 Flame Rod.
• Use with Honeywell Flame Safeguard controls requiring rectificationtype
flame detection.
• Use only with gas.
• Install with or without cover.
• Comes in several different lengths and can be cut to exact desired
length.
• Uses Rajah electrical connector.
Type: Flame Rod
Application: Gas fired pilot or gas fired system.
Approximate, Dimensions: Holder: 7/8 in. diameter x 3 3/4 in. long
(Holder: 22 mm diameter x 95 mm long)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. L95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Material Number Electrical Connections Mounting Includes Used With
C7008A1000/U Rajah electrical connector 1/4 in. NPT male 6" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289
C7008A1018/U Rajah electrical connector 1/4 in. NPT male 12" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289
C7008A1026/U Rajah electrical connector 1/4 in. NPT male 18" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289
C7008A1034/U Rajah electrical connector 1/4 in. NPT male 24" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289
C7008A1174/U Rajah electrical connector 1/4 in. NPT male 12" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289
C7008A1182/U Rajah electrical connector 1/4 in. NPT male 24" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289
70-6910 797
Commercial/Industrial
Combustion Controls
Flame Rods and Flame Rod Holders
C7009 Flame Rod Holder
Subminiature “spark plug” type flame rod holder with flame rod.
• Use on industrial flame-retention gas burner nozzles.
• Works with Honeywell Flame Safeguard controls requiring
rectification type flame detector.
• Mounts in areas with limited space because flame rod can be cut to
desired length.
• Uses Rajah electrical connector.
Type: Flame Rod
Application: Gas fired pilot or gas fired system.
Approximate, Dimensions: Holder: 3/8 in. diameter x 2 3/8 in. long
(Holder: 10 mm diameter x 60 mm long)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. L95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Material Number Electrical Connections Mounting Includes Comments Used With
C7009A1009/U Rajah electrical
connector
1/8 in. NPT male Flame rod and holder 4 in. (102 mm) flame rod Flame Amplifiers: R7247A, B, R7847A, B,
R7257, R7289
C7009A1025/U Rajah electrical
connector
1/8 in. NPT male Flame rod and holder 12 in. (305 mm) flame rod Flame Amplifiers: R7247A, B, R7847A, B,
R7257, R7289
Flame Rod Detector Accessories or Parts
Material Number Description
102709B/U Kanthal Flame Rod - 18 in. (.182" diameter) for C7004B, C7007A, C7011A
102709C/U Kanthal Flame Rod - 24 in. (.182" diameter) for C7004B, C7007A, C7011A
102709D/U Kanthal Flame Rod - 36 in. (.182" diameter) for C7004B, C7007A, C7011A
105478A/U Kanthal Flame Rod - 6 in. (.182" diameter-threaded 6-32) for C7008
105478B/U Kanthal Flame Rod - 12 in. (.182" diameter-threaded 6-32) for C7008
105478C/U Kanthal Flame Rod - 18 in. (.182" diameter-threaded 6-32) for C7008
105478D/U Kanthal Flame Rod - 24 in. (.182" diameter-threaded 6-32) for C7008
798 70-6910
Flame Detectors
C7012 Solid State Purple Peeper® Ultraviolet Flame Detector
Solid state electronic flame detectors for use with Honeywell
Flame Safeguard controls and amplifiers. Sense ultraviolet
radiation produced by combustion of gas, oil, coal or other fuels.
• Mount horizontally, vertically or at any angle in between.
• Provide quick electrical hookup with threaded conduit fitting and
color-coded leadwires.
• Reduced nuisance shutdowns by wiring two in parallel.
• C7012E1278 5 pin Brad Harrison type (formally 41307N) mating
connector not supplied nor available through Honeywell.
• C7012A, E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7012C, F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper
Application: Gas, Oil or Coal fired burners
Lead Length: 96 in. (2438 mm)
Power Consumption: 2.5 W
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 14740.01
Material
Number
Frequency Weight NEMA
Rating
Electrical
Connections
Mounting Electrical
Ratings
Ambient
Temperature
Range
Approvals,
Underwriters
Laboratories Inc.
Approvals,
Others
Includes Used With
C7012A1145/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, R7847A,
R7257; Flame
Amplifiers: R7247A,
B; R7847A, B; R7257
C7012A1152/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
1 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1160/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
1 in. NPT 120 Vac -40°F to
+175°F
(-40°C to
+79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1186/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 208 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1194/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 240 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012A1202/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 100 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, R7847A,
R7257
C7012A1210/U 50 Hz;
60 Hz
4.25 lb
(1.9 kg)
NEMA 4 4 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast
case and
cover
Flame Amplifiers:
R7247A, R7847A,
R7257
C7012C1042/U 50 Hz;
60 Hz
14.5 lb
(6.6 kg)
Explosion
Proof
4 NEC Class
1 Colorcoded
lead
wires.
1 in. NPT 120 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
E34649, Guide
No. ZTSZ
Flame Amplifiers:
R7247A, B; R7847A,
B; R7257
C7012G1019/U 50 Hz 4.25 lb
(1.9 kg)
NEMA 4 5 NEC Class
1 Colorcoded
lead
wires.
3/4 in. NPT 220 Vac 25°F to
175°F (-4°C
to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Meets DIN
Standards
Cast
case and
cover
Flame Amplifiers:
R7247C, R7847C
70-6910 799
Commercial/Industrial
Combustion Controls
Flame Detectors
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
800 70-6910
Flame Detectors
C7012 Solid State Purple Peeper® Ultraviolet Flame Detector
(Self-Checking)
Solid state electronic flame detectors for use with Honeywell
Flame Safeguard controls and amplifiers. Sense ultraviolet
radiation produced by combustion of gas, oil, coal or other fuels.
• Mount horizontally, vertically or at any angle in between.
• Provide quick electrical hookup with threaded conduit fitting and
color-coded leadwires.
• Reduced nuisance shutdowns by wiring two in parallel.
• C7012E1278 5 pin Brad Harrison type (formally 41307N) mating
connector not supplied nor available through Honeywell.
• C7012A, E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7012C, F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper, Self-Checking
Application: Gas, Oil or Coal fired burners
Lead Length: 96 in. (2438 mm)
Power Consumption: 7.0 W
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 14740.01
Used With: Flame Amplifiers: R7247C, R7847C
Material
Number
Frequency Weight NEMA
Rating
Electrical
Connections
Mounting Electrical
Ratings
Ambient
Temperature
Range
Approvals,
Underwriters
Laboratories Inc.
Approvals,
Others
Includes
C7012E1104/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1112/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
1 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1120/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
1 in. NPT 120 Vac -40°F to +175°F
(-40°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1146/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 208 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover,
with Hot refractory
tube
C7012E1153/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 240 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012E1187/U 50 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 220 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
DIN (Europe) Cast case and cover
C7012E1195/U 50 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 110 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
BGC (Europe) Cast case and cover
C7012E1203/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 6 NEC Class 1
Color-coded
lead wires.
3/4 in. NPT 240 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
BGC (Europe) Cast case and cover
C7012E1278/U 50 Hz; 60 Hz 4.25 lb
(1.9 kg)
NEMA 4 Brad Harrison
type number
41310
connector
1 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
MP268, Guide
No. MCCZ
Cast case and cover
C7012F1052/U 50 Hz; 60 Hz 14.5 lb
(6.6 kg)
Explosion
Proof
6 NEC Class 1
Color-coded
lead wires.
1 in. NPT 120 Vac -20°F to +175°F
(-20°C to +79°C)
Listed: File No.
E34649, Guide
No. ZTSZ
Explosion-proof, two
piece, violet, cast
aluminum enclosure
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
70-6910 801
Commercial/Industrial
Combustion Controls
Flame Detectors
C7024 Solid State Purple Peeper® Ultraviolet Flame Detector
24 Vdc solid state electronic flame detectors for sensing the
ultraviolet radiation emitted by the combustion of most carbon
containing fuels, such as natural gas, LP gases, and oil.
• Use with R7824C Dynamic Self-Check Flame Signal Amplifier.
• Circuitry provides low power consumption and high reliability.
• Mount horizontally, vertically or at any angle in between.
• Field-replaceable UV radiation sensing tube and quartz viewing
window.
• Quick electrical installation with threaded conduit fitting and colorcoded
leadwires.
• Reduce nuisance shutdowns by wiring two in parallel.
• Oscillating shutter interrupts UV radiation using the R7824C
amplifier.
• C7024E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7024F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper, Self-Checking
Application: Coal fired burners; Gas fired burners; Oil fired burners
Lead Length: 96 in. (2438 mm)
Electrical Connections: Six NEC CLASS 1 color-coded leaders
Electrical Ratings: 24 Vdc
Power Consumption: 7.8 W maximum.
Ambient Temperature Range: -20°F to +175°F (-20°C to +79°C)
Approvals, CSA: Certified: Master Report LR95329-3
Used With: Flame Amplifiers: R7824C
Accessories:
190971G/U – 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
Material Number NEMA Rating Mounting Approximate, Dimensions Weight Approvals, Underwriters
Laboratories Inc.
Includes Comments
C7024E1001/U NEMA 4 3/4 in. NPT 5 1/4 in. diameter (includes
mounting flange) x 7 7/32 in.
long (133 mm diameter (includes
mounting flange) x 183 mm long)
4.25 lb (1.9 kg) Component Recognized: File
No. MP268
Cast case and
cover
Flame Amplifiers:
R7824C
C7024F1009/U Explosion
Proof
1 in. NPT 8 in. diameter x 12 in. long (203 mm
diameter x 305 mm long)
14.5 lb (6.6 kg) Component Recognized: For
use in hazardous locations;
Class 1 Groups C and D; Class
2, Groups E, F and G; File no.
E34649
Flame Amplifiers:
R7824C
802 70-6910
Flame Detectors
C7027; C7044 Minipeeper Ultraviolet Flame Detector
Compact Flame Detector for use with flame safeguard controls
with ultraviolet amplifiers.
• Use with Honeywell Flame Safeguard primary safety controls and
burners requiring ultraviolet flame detection.
• C7027 mounts on a 1/2 in. sighting pipe by using an integral collar.
• Detectors can be wired in parallel for difficult sighting applications.
• C7027 seals against pressures up to 5 psi (34.5 kPa) when correctly
installed.
• Allows for blast tube mounting due to compact size.
• C7044 mounts with a two screw bracket.
• The C7044 UV sensor tube is enclosed in a stainless steel housing.
• C7044 has the capability of side or end viewing in flame monitoring
applications.
Type: Ultraviolet, Minipeeper
Electrical Connections: 2 NEC Class 1 leadwires
Vibration: 0.5 G max
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259,
R7290
Material Number Application Lead Length Mounting Ambient
Temperature Range
Approvals,
Others
Includes Comments
C7027A1023/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
Detects ultraviolet
radiation in flames
C7027A1031/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
Detects ultraviolet
radiation in flames
C7027A1049/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1056/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
DIN (Europe) Detects ultraviolet
radiation in flames
C7027A1064/U Coal fired burners; Gas fired
burners; Oil fired burners
288 in. (7315
mm)
Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1072/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1080/U Coal fired burners; Gas fired
burners; Oil fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
136733 Heat Block
and 390427B bushing
Detects ultraviolet
radiation in flames
C7027A1114/U Coal fired burners; Gas fired
burners; Oil fired burners
44 in. (1118 mm) Integral nut for 1/2
in. sighting pipe.
0°F to 215°F
(-18°C to +102°C)
installed 22" flexible
conduit
Detects ultraviolet
radiation in flames
C7027A1122/U Oil fired burners; Gas fired
burners; Coal fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to 215°F
(-40°C to 102°C)
1/2 in. NPT threaded
spud connector.
Detects ultraviolet
radiation in flames
C7027A1130/U Gas fired burners; Oil fired
burners; Coal fired burners
96 in. (2438 mm) Integral nut for 1/2
in. sighting pipe.
-40°F to +215°F
(-40°C to +102°C)
Detects ultraviolet
radiation in flames
C7044A1006/U Coal fired burners; Gas fired
burners; Oil fired burners
72 in. (1829 mm) Mounting Bracket
provided
0°F to 215°F
(-18°C to +102°C)
Mounting bracket Detects ultraviolet
radiation in flames
- Side Viewing
Dimensiions in inches (millimeters)
COLLAR WITH 1/2-14 NPSM
INTERNAL THREADS
4 (102) 8 FOOT (2.44 METER)
LEADWIRES (2)
M1943G
C7027A1064 HAS 24 FOOT (7.32 METER) LEADWIRES. C7027A1114 HAS
44 IN. (1.118 M) LEADWIRES WITH 22 IN. (558 MM) FLEXIBLE CONDUIT.
1
2
2
3-1/2 (89)
1-1/16
(27)
1
MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL
THREADS) INSTEAD OF CLAMP TYPE CONNECTOR.
6 FOOT
[1.83 METER]
LEAD
WIRES (2)
3-5/8 (92)
1/2
(13)
1-27/64
(36)
3/8
(10)
7/8
(22)
9/16
(14)
M1944D
MOUNTING
BRACKET
70-6910 803
Commercial/Industrial
Combustion Controls
Flame Detectors
C7035 Minipeeper Ultraviolet Flame Detector
Dimensiions in inches (millimeters)
1/2-14 NPSM
INTERNAL THREADS
COLLAR WITH 2 (51) 2
1 - 11-1/2 NPSM
INTERNAL
THREADS
1
1 DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL MOUNTING THREADS.
DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL MOUNTING THREADS.
C7035A1056 HAS 12 FOOT (3.66 METER) LEADWIRES.
2
3
INSERTION DEPTH
6 FOOT
[1.83 METER]
LEADWIRES (2) 3
M1945E
2-5/8 (67)
1-1/2
(38)
31/32
(25)
4-1/8 (105)
1-3/16
(30)
Compact flame detector for use with flame safeguard controls
with ultraviolet amplifiers.
• Use with Honeywell Flame Safeguard primary safety controls and
burners requiring ultraviolet flame detection.
• Mounts on a 1 in. sighting pipe by using an integral collar.
• Protects the sensing tube with a shield.
• Meets outdoor rain tight requirements of Underwriters Laboratories
Inc., NEMA 4 and NEMA 4X.
• Wires in parallel for difficult sighting applications.
• Seals against pressures as high as 5 psi (34.5 kPa) when correctly
installed.
• Field-replaceable ultraviolet sensing tube.
Type: Ultraviolet, Minipeeper
NEMA Ratings: NEMA 3 and NEMA 4
Electrical Connections: 2 NEC Class 1 leadwires
Vibration: 0.5 G max
Mounting: Integral nut for 1 in. sighting pipe.
Approximate, Dimensions: 1 1/2 in. diameter x 4 1/8 in. long (38 mm
diameter x 105 mm long)
Weight: 6 oz (0.17 kg)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Comments: Detects ultraviolet radiation in flames
Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259,
R7290
Material Number Application Lead Length Ambient Temperature Range Approvals, Others Includes
C7035A1023/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C)
C7035A1031/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C)
C7035A1049/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) DIN (Europe)
C7035A1056/U Coal fired burners; Gas fired burners; Oil fired burners 144 in. (3658 mm) -40°F to +250°F (-40°C to +121°C)
C7035A1064/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C)
C7035A1080/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) 600F leads
C7035A1098/U Oil fired burners; Gas fired burners; Coal fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C)
804 70-6910
Flame Detectors
C7061 Dynamic Self-Check Ultraviolet Flame Detector
Dynamic self-checking flame detector used with R7861 Dynamic
Self-check Amplifiers for sensing the ultraviolet radiation
generated by the combustion of gas, oil, or other fuels.
• Oscillating shutter interrupts ultraviolet radiation reaching the UV
sensor to provide the UV sensor tube checking function.
• Can be mounted horizontally, vertically or at any angle in between.
• The detector requires faceplate alignment and has integral
locating reference points to assure proper operation of the shutter
mechanism.
• Field replaceable ultraviolet sensing tube and quartz viewing window.
• Models with threaded conduit fitting and color-coded leadwires allow
rapid electrical installation.
• C7061A1038 or A1046 5 pin Brad Harrison type (formally 41307N)
mating connector not supplied nor available through Honeywell.
• Two detectors can be wired in parallel to reduce nuisance shutdowns
in difficult flame sighting applications.
• Protective heat block built into mounting flange.
• -40°F (-40°C) rated ultraviolet sensing tube is supplied.
• C7061E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7061F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Purple Peeper, Self-Checking
Application: Gas fired burners; Oil fired burners
Comments: Dynamic self-checking flame detector
Used With: Flame Amplifiers: R7861
Approvals, Underwriters Laboratories Inc.: C7061A, M-Listed:
File No. MP268, Guide No. MCCZ; C7061F-Recognized: For use in
hazardous locations, Class 1 Groups C and D; class 2, Groups E, F
and G; File no. E34649
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 14740.01
Material
Number
NEMA Rating Lead Length Electrical Connections Mounting Electrical Ratings Frequency Ambient
Temperature Range
Approvals,
Others
C7061A1004/U NEMA 4 77 in.
(1981 mm)
PVC jacketed cable 3/4 in. NPT 120 Vac 50 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1012/U NEMA 4 96 in.
(2438 mm)
Color-coded leadwires 3/4 in. NPT 120 Vac 51 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1020/U NEMA 4 Terminal block 3/4 in. NPT 120 or 230 Vac 52 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1038/U NEMA 4 Brad Harrison type
number 41310 connector
3/4 in. NPT 120 Vac 53 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1046/U NEMA 4 Brad Harrison type
number 41310 connector
1 in. NPT 120 Vac 54 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061A1053/U NEMA 4 96 in.
(2438 mm)
Color-coded leadwires 1 in. NPT 120 Vac 55 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061F1003 Explosion Proof Terminal block 1 in. NPT 120 or 230 Vac 56 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
CE and conforms
to EEXD IIc
C7061F2001/U Explosion Proof 96 in.
(2438 mm)
Color-coded leadwires 1 in. NPT 120 Vac 57 Hz; 60 Hz -40°F to +175°F
(-40°C to +79°C)
C7061M1008/U NEMA 4 96 in.
(2438 mm)
Color-coded leadwires 1 in. NPT 120 Vac 58 Hz; 60 Hz -4°F to +175°F
(-20°C to +79°C)
C7061M1016/U NEMA 4 Brad Harrison type
number 41310 connector
1 in. NPT 120 Vac 59 Hz; 60 Hz -4°F to +175°F
(-20°C to +79°C)
Dimensions for C7061A in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
Dimensions for C7061F in inches (millimeters)
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
70-6910 805
Commercial/Industrial
Combustion Controls
Flame Detectors
Dimensions for C7061M in inches (millimeters)
M29114A
2-9/64 (55)
13/16 (21)
2-21/32
(68)
3-15/32
(88)
1-33/64
(39)
PARALLEL
PIPETHREAD
1-11/2 NPSM
33/64
(13)
2-9/64
(55)
1-35/64
(40)
CONDUIT TUBE CONNECTION
PORT 1/2 NPSM
806 70-6910
Flame Detectors
C7076 Adjustable Sensitivity Ultraviolet Flame Detector
Solid state dynamic self check flame detectors for use with
BC7000, R4140 or FSP5075 with R7476 Amplifier and 7800 SERIES
with R7886 Amplifier.
• Use Honeywell Flame Safeguard primary safety controls requiring
adjustable sensitivity ultraviolet flame detection.
• Detect ultraviolet radiation from flames.
• Include dual sensitivity adjustment.
• C7076A meets NEMA 4 standards with viewing window rated to 20
psi.
• C7076D has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Adjustable Sensitivity
Application: Gas fired burners; Oil fired burners
Electrical Connections: Terminal block
Vibration: 0.5 G max
Mounting: 1 in. NPT
Power Consumption: 7.0 W
Ambient Temperature Range: -40°F to +160°F (-40°C to +71°C)
Approvals, CSA: Certified: Master Report LR1620
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. FM26980
Comments: Dynamic self-checking flame detector with adjustable
sensitivity
Used With: Flame Amplifiers: R7476, R7886
Replacement Parts:
190971F/U – 100 Vac Coil and Shutter Assembly for C7076A, D
190998A/U – Aspiration assembly for C7076A
191002R/U – 120 Vac Plug in Electronics less UV Sensing Tube for
C7076D
191050/U – Quartz Viewing Window for C7076
191053/U – UV Sensing Tube for C7076
Dimensiions in inches (millimeters)
C7076A
C7076D M20749A
2-1/4
(57)
2-1/4
(57)
2-9/32
(58)
5-25/32 (147)
5-25/32
(147)
1-27/32
(47)
7-13/16 (198)
15/16
(24)
25/32 (20)
1-9/16 (40)
11-13/16 (300)
3/4 (19)
1-5/8
(19)
2-21/32
(68)
7-19/32
(194)
3/8 INCH NPT
1 (25)
29/32 (22) OPENING FOR
1/2-INCH CONDUIT
7-13/32 (188)
10-1/4 (261)
1-1/16
(27)
4
(102)
4 (102)
4-25/32 (122)
1 INCH NPT
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1
1
6-23/32
(171)
1-31/32 (50)
3-15/16 (100)
5/16-18 UNC (3 PLCS)
X 0.47 (12) DEEP
Material Number NEMA Rating Electrical
Ratings
Frequency Approximate, Dimensions Weight Approvals, Underwriters
Laboratories Inc.
Approvals,
Others
C7076A1007/U NEMA 4 120 Vac 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep
(102 mm high x 102 mm wide x 261 mm deep)
6.6 lb
(3 kg)
Listed: File No. MP268, Guide
No. MCCZ
C7076A1015/U NEMA 4 100 Vac 50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep
(102 mm high x 102 mm wide x 261 mm deep)
6.6 lb
(3 kg)
Listed: File No. MP268, Guide
No. MCCZ
C7076A1031/U NEMA 4 220 Vac;
240 Vac
50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep
(102 mm high x 102 mm wide x 261 mm deep)
6.6 lb
(3 kg)
Listed: File No. MP268, Guide
No. MCCZ
C7076D1027/U NEMA 7 120 Vac 60 Hz 6 5/8 in. high x 6 3/16 in. wide x 11 3/4 in. deep
(168 mm high x 158 mm wide x 300 mm deep)
17.6 lb
(8 kg)
Listed: File No. E34649, Guide
No. ZTSZ
Explosion
Proof
70-6910 807
Commercial/Industrial
Combustion Controls
Flame Detectors
C7927 Solid State Ultraviolet Flame Detector
Dimensiions in inches (millimeters)
8 FT (2.44 M)
1 (25)
C7927A1016 M24714
3-3/4
(95)
3-1/4
(82)
The Solid State Ultraviolet Flame Detectors, sense ultraviolet
radiation emitted by combustion flames. The flame detectors are
used with Honeywell flame safeguard controls to provide flame
supervision for gas, oil, or combination gas-oil burners.
• Properly installed the flame detectors are pressure rated for 5 psi.
• Flame detector is used with only the R7851B Flame Amplifier and
the 7800 SERIES controls.
• Has an integral collar threaded (internal 1/2-14 NPSM) for mounting
on a one-half inch sight pipe.
Type: Ultraviolet, Minipeeper
Application: Gas, Oil, or combination burners-intermittent operation
only (burner cycled at least once each 24 hours).
NEMA Rating: NEMA 1
Electrical Connections: 2 NEC Class 1 leadwires
Mounting: 1/2 in. NPT pipe mounting
Approximate, Dimensions: 1 in. diameter x 3 3/4 in. long (25 mm
diameter x 95 mm long)
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MP268
Approvals, CSA: Report 158158
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 3011020
Comments: Detects ultraviolet radiation in flames
Material Number Lead Length Ambient Temperature Range Used With
C7927A1016/U 96 in. (2438 mm) -40°F to +200°F (-40°C to +93°C) Flame Amplifiers: R7851B
808 70-6910
Flame Detectors
C7961 Dynamic Self-checking Solid State Ultraviolet Flame Detector
A self-checking flame detector using a solid state UV sensor to
detect ultraviolet radiation in flames for supervision of gas, oil or
combination gas-oil burners.
• Designed for use with 7800 series controls with the R7851C flame
amp.
• Oscillating shutter interrupts ultraviolet radiation reaching the UV
sensor to provide the solid state UV sensor checking function.
• Can be mounted horizontally, vertically or at any angle in between.
• The detector requires faceplate alignment and has integral
locating reference points to assure proper operation of the shutter
mechanism.
• Models available with threaded conduit fitting and color-coded
leadwires allow rapid electrical installation.
• C7961E1022 or E1030 5 pin Brad Harrison type (formally 41307N)
mating connector not supplied nor available through Honeywell.
• Incorporates UV sensor tube checking feature; used with
R7851C1008 Dynamic Self-check Amplifiers.
• Protective heat block built into mounting flange.
• -40°F (-40°C) rated ultraviolet sensing cell is supplied.
• C7961E meets NEMA 4 standards with viewing window rated to
20 psi.
• C7961F has an explosion-proof housing for use in hazardous
atmospheres with a viewing window rated to 100 psi.
Type: Ultraviolet, Self-Checking
Application: Gas, Oil or other fuels
Electrical Ratings: 120 Vac (-15% +10%)
Frequency: 50 Hz; 60 Hz
Ambient Temperature Range: -40°F to +175°F (-40°C to +80°C)
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MP268
Comments: Detects ultraviolet radiation generated by combustion of
gas, oil, or other fuels
Approvals, Swiss RE: Acceptable
Used With: R7851C Dynamic Self-Check Amplifier
Dimensiions in inches (millimeters)
MOUNTING FLANGE
1/2–14 NPSM
LEADWIRES
FACEPLATE
3/4–14 NPT
M10167D
3-3/4
(95)
7-7/32
(183)
5-1/8
(130)
3-7/16
(87)
5-1/4 (133)
1
1
2
2
C7061A1046, C7061A1053: INCH NPT
C7061A1038 AND C7061A1046: TYPE CONNECTOR.
M1963A
FACEPLATE
PIPE
UNION
8
(203)
DIA.
1/2-14 NPT
LEADWIRES
9 (229)
2
(51)
5
(127)
1-11 1/2 NPT
2-1/16
1-1/2 (52)
(38)
5/16-18 UNC-2B BY
7/16 (11) DEEP
MOUNTING HOLES (2)
2 (51)
1 (25)
3
(76)
Material
Number
NEMA
Rating
Lead
Length
Electrical
Connections
Mounting Approximate, Dimensions Weight Approvals,
CSA
Approvals,
Factory Mutual
Includes
C7961E1006/U NEMA 4 96 in.
(2438 mm)
NEC Class 1
color-coded
3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961E1014/U NEMA 4 96 in.
(2438 mm)
NEC Class 1
color-coded
1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961E1022/U NEMA 4 5 pin Brad
Harrison
Type
Connector
1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961E1030/U NEMA 4 5 pin Brad
Harrison
Type
Connector
3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter
including mounting flange) x 7 7/32 in.
long (95 mm diameter (133 mm diameter
including mounting flange) x 183 mm
long)
2.6 lb
(1.2 kg)
Certified:
Pending
Pending Quartz Viewing
Window rated for
20 psi (138 kPa)
C7961F1004/U Explosion
Proof
96 in.
(2438 mm)
NEC Class 1
color-coded
1 in. NPT 8 in. diameter x 12 in. long (203 mm
diameter x 305 mm long)
14.5 lb
(6.6 kg)
Approved:
Report No.
14740.01
Quartz Viewing
Window rated for
100 psi
70-6910 809
Commercial/Industrial
Combustion Controls
Flame Detectors
C7915 Infrared Flame Detector
The C7915 Combination mount Lead Sulfide cell senses infrared
radiation from gas, oil, and coal or dual-fuel flames.
• Used for combination or dual-fuel applications.
• Detects pilot and main flame.
• Mounts quickly and easily on a standard 3/4 in. sighting pipe.
• Works where flame rod or rectifying photocell mounts are difficult to
apply.
Type: Infrared (Lead Sulfide)
Application: Used for combination or dual-fuel applications
Electrical Connections: Two no. 18 AWG wires
Mounting: 3/4 in. NPT
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: Master Report LR95329-1
Approvals, Swiss RE: Acceptable
Approvals, Factory Mutual: Approved: Report No. 24181.03
Comments: Infrared (Lead Sulfide) Flame Detector
Replacement Parts:
32007255-001/U – Lead Sulfide Cell for C7915
50019469-001/U – Magnifying Lens Assembly for C7915A
Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With
C7915A1010/U 30 in. (762 mm) 1 1/4 in. diameter x 2 1/4 in. long
(32 mm diameter x 58 mm long)
-20°F to 125°F operating range
(-18°C to 52°C operating range)
With magnifying lens,
32007255-001 Cell
Flame Amplifiers: R7852
C7915A1028/U 48 in. (1219 mm) 1 1/4 in. diameter x 2 1/4 in. long
(32 mm diameter x 58 mm long)
-20°F to 125°F operating range
(-18°C to 52°C operating range)
With magnifying lens,
32007255-001 Cell, Orifice, heat
block, and reducer bushing
Flame Amplifiers: R7852
C7915A1036/U 96 in. (2438 mm) 1 1/4 in. diameter x 2 1/4 in. long
(32 mm diameter x 58 mm long)
-20°F to 125°F operating range
(-18°C to 52°C operating range)
With magnifying lens,
32007255-001 Cell
Flame Amplifiers: R7852
C7962 Visible Light Flame Detector
Dimensiions in inches (millimeters)
4 FOOT (1.2 METER)
LEADWIRES (2)
M20912
3-1/4 (82)
3-3/4 (95)
1
(25)
C7962B
The C7962B Visible Light Flame Detector detects the visible light
emitted by fuel oil combustion flames. The C7962B Detector is
used with Honeywell Flame Safeguard controls to provide fuel oil
flame supervision in commercial and industrial burners.
• Used with 7800 SERIES Flame Safeguard controls.
• Used with R7851B Flame Amplifier.
• Has an integral collar threaded (internal 1/2-14 NPSM) for mounting
on 1/2 inch sight pipe.
Type: Visible Light Flame Detector
Application: Commercial, industrial oil burners
NEMA Ratings: NEMA 1
Electrical Connections: 2 NEC Class 1 leadwires
Vibration: 0.5 G max
Mounting: 1/2 in NPT pipe mounting
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MP268
Approvals, CSA: Report 158158
Approvals, Swiss RE: Acceptable
Accessories:
32007439-001/U – Mounting Bracket and screws for C7962B (3/8 in.
NPT to 1/2 in. NPT)
Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With
C7962B1002/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm
diameter x 95 mm long)
-40°F to +160°F (-40°C to +71°C) Flame Amplifiers:
R7851B
C7962B1010/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm
diameter x 95 mm long)
-40°F to +160°F (-40°C to +71°C) 32007439-001
Mounting Bracket and
screws
Flame Amplifiers:
R7851B
810 70-6910
Flame Detectors
Optical Flame Detector Accessories or Parts
Material Number Description Used With
105172C/U Pressure Seal-off Adapter (3/4 NPT) w/UV Quartz window for C7012, C7024, C7027, C7061 C7012, C7024, C7027, C7061;
C7024; C7012; C7061
110634A/U Magnifying Lens Assembly for C7015A C7015
113228/U UV Sensing Tube (-20°F to 175°F) for C7012; C7024 C7012; C7024
114372/U Bulk Pack -20 PSI window for C7012E, F; C7024; C7061 C7024; C7012; C7061
114638/U Rubber Washer (Red) for C7012A, E; C7024A; C7061A; C7961A C7012; C7061; C7024
120739/U Flange Gasket for C7012, C7024, C7061 C7024; C7012; C7061
120930/1662/F Cover for C7012A,G, C7024E, C7061A, C7961E C7012A,G, C7024E, C7061A,
C7961E; C7012
120934-520/U Mounting Flange (3/4") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A,
C7961E
122748/U 50 PSI Quartz Window for C7012, C7061 C7012; C7061; C7024
124198/U Mounting Flange (1") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A,
C7961E
129464M/U UV Power Tube (0°F to 250°F) for C7035 C7035
129464N/U UV Power Tube (-40°F to 250°F) for C7035, C7061 C7061; C7035
129811B/U Socket Assembly w/NPT threads C7035
190971B/U 120 Vac Coil and Shutter Assembly for C7012E, F, C7061A, F C7012E, F; C7061A, F
190971D/F 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E
190971D/U 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E
190971F/U 100 Vac Coil and Shutter Assembly for C7076A, D C7076A, D
190971G/U 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961 C7024;C7961
190998A/U Aspiration assembly for C7076A C7076A
190999/U Grommet for C7076 Sensors C7076
191002D/U 220/240 Vac Plug in Electronics less UV Sensing Tube for C7076A C7076A
191002R/U 120 Vac Plug in Electronics less UV Sensing Tube for C7076D C7076D
191050/U Quartz Viewing Window for C7076 C7076
191053/U UV Sensing Tube for C7076 C7076
191054/U Housing Gasket for C7076 C7076
191203/0767/U Hinge for C7076A C7076
191284/U Aluminum Shield for C7035 C7035
191702/U Electronics less UV sensing tube for C7012F (120 Vac) C7012F
32004080-001/U 120 Vac Electronics less UV Sensing Tube and Shutter for C7012C C7012C
32004080-002/U 24 Vdc Plug in Electronics less UV Sensing Tube for C7024F C7024F
32007255-001/U Lead Sulfide Cell for C7915 C7915
32007439-001/U Mounting Bracket and screws for C7962B (3/8 in. NPT to 1/2 in. NPT) C7962B
390427B/U Envelope with Reducer bushing (1/2" to 3/8" NPT) C7027; C7015
50019469-001/U Magnifying Lens Assembly for C7915A C7915; C7015
70-6910 811
Commercial/Industrial
Combustion Controls
Pilot Burners
Q179A, B Flame Rectifier Gas Pilots
Q179A, B Gas Pilot Burner Assemblies use the flame rectification
principle to prove the flame. Q179A, B are used in conjunction
with a suitable electronic flame safeguard control on industrial or
commercial gas and gas pilot ignited oil burners.
• Q179A is a gas pilot assembly (with a flame electrode rod) and
ignition electrode, making it suitable for applications requiring an
interrupted or intermittent electrically ignited gas pilot burner.
• Q179B has only the flame electrode and is suitable for use in
continuous pilot applications.
• Primary aerated type burner is equipped with stainless steel fins that
provide the proper flame rod area to ground area ratio for maximum
flame signal and flame stabilization.
• Stainless steel electrode(s) are mounted in ceramic insulators, which
permit electrode adjustment.
• Rajah connectors facilitate disconnecting (A1126 has terminal
screws).
• Bracket permits side or end mounting.
Type of Gas: Natural gas; Gas consumption – 2.0 cfh (0.06 m3/hr)
Aeration: Primary
Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm
compression coupling
Mounting: side or end mount
Approximate, Dimensions: 4 5/8 in. high x 1 11/16 in. wide x 3 in.
deep (118 mm high x 43 mm wide x 76 mm deep)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2
Approvals, Factory Mutual: Approved: Report No. 22961
Material Number Application Orifice Wiring Terminal Type Tip Style Includes Used With
Q179A1001/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah I Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1035/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree right
hand
Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1050/U For Intermittent or
Interrupted Ignition
0.028 in. dia. (0.711 mm dia.) Rajah T Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1076/U For Intermittent or
Interrupted Ignition
0.028 in. dia. (0.711 mm dia.) Rajah 45 degree Y Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1092/U For Intermittent or
Interrupted Ignition
0.028 in. dia. (0.711 mm dia.) Rajah 45 degree T Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1118/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left
hand
Flame electrode and
ignition electrode
Q624 or other suitable
ignition transformer.
Q179A1126/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Screw Terminal I Flame electrode and
ignition electrode
with screw terminal
connections
Q624 or other suitable
ignition transformer.
Q179A1183/U For Intermittent or
Interrupted Ignition
0.025 in. dia. (0.635 mm dia.) Rajah I Ignition Electrode Only Q624 or other suitable
ignition transformer.
Q179B1042/U For Continuous
(Standing) pilot
0.025 in. dia. (0.635 mm dia.) Rajah T Flame electrode
Q179B1109/U For Continuous
(Standing) pilot
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left
hand
Flame electrode
Q179B1117/U For Continuous
(Standing) pilot
0.025 in. dia. (0.635 mm dia.) Rajah 45 degree I Flame electrode
812 70-6910
Pilot Burners
Q179C, D Miniature Rectifier Pilots
Q179C, D Gas Pilot Burner Assemblies use the flame rectification
principle to prove the flame. Q179C, D are used in conjunction
with a suitable electronic flame safeguard control on industrial or
commercial gas and gas pilot ignited oil burners.
• Q179C is a gas pilot assembly (with a flame electrode rod) and
ignition electrode, making it suitable for applications requiring an
interrupted or intermittent electrically ignited gas pilot burner.
• Q179D has only the flame electrode and is suitable for use in
continuous pilot applications.
• Primary aerated type burner is equipped with stainless steel fins that
provide the proper flame rod area to ground area ratio for maximum
flame signal and flame stabilization.
• Stainless steel electrode(s) are mounted in ceramic insulators, which
permit electrode adjustment.
• Rajah connectors facilitate disconnecting.
Aeration: Primary
Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm
compression coupling
Wiring Terminal Type: Rajah
Approvals, Underwriters Laboratories Inc.: Component Recognized:
File No. MH9928, Guide No. MCUR2
Approvals, CSA: Certified: Master Report LR95329-1
Material
Number
Application Mounting Tip Style Orifice Approximate, Dimensions Includes Used With Type of
Gas
Q179C1009/U For Intermittent or
Interrupted Ignition
Dual Wing-
Rear
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1025/U For Intermittent or
Interrupted Ignition
Single Wing-
Rear
L 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1033/U For Intermittent or
Interrupted Ignition
Dual Wing-
Left Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1041/U For Intermittent or
Interrupted Ignition
Dual Wing-
Right Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1058/U For Intermittent or
Interrupted Ignition
Single Wing-
Left Side
L 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1066/U For Intermittent or
Interrupted Ignition
Single Wing-
Right Side
K 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
Natural
Q179C1090/U For Intermittent or
Interrupted Ignition
Dual Wing-
Rear
D 0.016 in. dia.
(0.40 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and ignition
electrode
Q624 or other suitable
ignition transformer.
LP
Q179D1008/U For Continuous
(Standing) pilot
Dual Wing-
Rear
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 2 7/16 in. wide
x 1 in. deep (79 mm high x
62 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
Q179D1016/U For Continuous
(Standing) pilot
Dual Wing-
Left Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
Q179D1024/U For Continuous
(Standing) pilot
Dual Wing-
Right Side
D 0.026 in. dia.
(0.66 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
Q179D1057/U For Continuous
(Standing) pilot
Single Wing-
Left Side
L 0.024 in. dia.
(0.60 mm dia.)
3 1/8 in. high x 3 1/32 in. wide
x 1 in. deep (79 mm high x
77 mm wide x 25 mm deep)
Flame electrode
and thermocouple
adapter
Q340 Thermocouple
or Q313A Thermopile
Generator.
Natural
70-6910 813
Commercial/Industrial
Combustion Controls
Pilot Burners
C7005 Flame Rectifier Pilots
Gas Pilot Burner Assemblies include a flame rod to prove the pilot
flame. The assemblies are used with a suitable flame safeguard
control on industrial or commercial gas burners or oil burners
with gas pilots.
• Used with Honeywell controls using the flame rectification principle.
• C7005A is for continuous pilot applications.
• It includes an insulated flame rod, properly positioned relative to
the flame retention type nozzle. C7005B is similar to C7005A, but
includes an ignition electrode suitable for automatic, electric-spark
ignition, gas pilot applications.
• Individually mounted flame rod and ignition electrode in ceramic
insulators allow the head assembly to fit inside a 3-inch pipe.
• Stainless steel fins on the flame retention type pilot head provide
the correct ratio of flame rod area to ground area for maximum flame
signal, and are beneficial in stabilizing the pilot flame.
• Pilot flame retention nozzle and mixing tube are threaded internally,
1/2-14 NPT and 3/8-18 NPT, respectively, and can be assembled
with standard pipe fittings.
• Pilot can be installed in vertical, horizontal, or inclined position.
• Rajah connectors facilitate electrical connections.
Connection Type: 1/2 in. NPT male thread Gas Fitting
Wiring Terminal Type: Rajah
Approximate, Dimensions: 3 in. diameter x 3 1/2 in. deep (76 mm
diameter x 343 mm deep)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2
Approvals, Factory Mutual: Approved: Report No. 24181.04
Approvals, Swiss RE: Acceptable
Material Number Application Orifice Includes Used With Type of Gas
C7005A1037/U For Continuous (Standing) pilot 0.052 in. dia. Natural
C7005B1035/U For automatic electrically ignited pilot 0.052 in. dia. Ignition electrode Q624 or other suitable ignition transformer. Natural
C7005B1050/U For automatic electrically ignited pilot 0.028 in. dia. (0.711 mm dia.) Ignition electrode Q624 or other suitable ignition transformer. LP
Commercial Pilot Burners Parts or Accessories
Material Number Description Used With
100204B/U This Natural Gas Venturi Mixing Tube is used for C7005A and B C7005A, C7005B
101738/U This Insulator for Flame rod or Igniter is used with C7005A and B C7005A, C7005B
101738A/U This Ignition Assembly, including; electrode, bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B
101738B/U This Flame Rod Assembly, including; Kanthal Electrode, Bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B
101739/U This 4 in. Kanthal Ignition Electrode is used for C7005A and B C7005A, C7005B
101741/0020/U This 7/8 in. long Rajah Connector, with plug end, is used for C7005A and B C7005A, C7005B
101742/0021/U This Electrode Mounting Clip is used for C7005A and B C7005A, C7005B
101743/U This Mounting Bracket is used for C7005A and B C7005A, C7005B
103534/U This 8 in. Kanthal flame electrode is used with C7005A and C7005B C7005A, C7005B
104312/U This Rajah Connector for Flame Electrode is used with Q179A and B Q179A, Q179B
131065/U 131065 Adapts Q340 Thermal Couple to Q179B with 102462. Sold in custom packs Q179A, Q179B
133451A/U This T Port or LH 90 degree Flame Rod and Insulator, is used for Q179A and B Q179A, Q179B
37356/520/U This Rajah connector for ignition electrodes is used with Q179A, Q179B, Q179C, or Q179D Q179A, Q179B, Q179C, Q179D
388146KD/U This 0.016 in. diameter, LP Gas Spud Orifice, is used for Q179C and D. Sold in bulk packs Q179C, Q179D
395390-13/U This LP gas, 0.013 in. diameter Orifice, is used for Q179A and B Q179A, Q179B
395390-28/U This Natural gas, 0.028 in. diameter Orifice, is used for Q179A and B Q179A, Q179B
R1061012/U This Ignition cable or Flame Rod Cable is rated at 350°F, 20,000 volts R.M.S. and used with C7005B, Q179A and Q179C C7005B, Q179A, Q179C
R1298020/U This Cable Flame Rod Lead, is rated at 400°F, 600 volts R.M.S., and used with Q179 Q179
814 70-6910
Ignition Transformers
Q624 Solid State Ignition Transformer
Used to ignite pilots on commercial or industrial gas burners.
• Ignite gas pilots with spark gaps up to 1/4 in. (6.5 mm).
• Reliable light off with 15,000 peak voltage.
• Prevent detection of the ignition spark when properly applied in a
flame detection system with the C7027, C7035 or C7044 Minipeeper
Ultraviolet Flame Detector.
• For use only in interrupted ignition applications.
• Mount in same space used by conventional ignition transformer.
• Light weight, 3 lbs. (1.4 kg) versus 8-1/2 lbs. (3.9 kg) for standard
transformers.
Temperature Range: -40°F to +125°F
Approximate, Dimensions: 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep
(171.5 mm high x 108 mm wide x 76 mm deep)
Weight lb. (kg): 3 lb (1.4 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized
Approvals, CSA: Certified: File No. LR95329
Operating Humidity Range (% RH): 95% RH
Accessories:
32004766-001/U – 24 inch Ignition Cable for Q624 and Q652
32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652
32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
32004766-004/U – 60 inch Ignition Cable with straight boots
32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot
32004766-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-001/U – 24 inch Ignition Cable for Q624 and Q652
50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652
50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
50060793-004/U – 60 inch Ignition Cable with straight boots
50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot
50060793-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-007/U – 36 inch ignition cable w/90 degree boot on one end
only
50060793-008/U – Ignition Cable w/90 degree boot on one end only
50060793-009/U – Ignition Cable w/90 degree boot on one end only
50060793-010/U – Ignition Cable w/90 degree boot on one end only
50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end
used with Q624 and Q652
50060793-012/U – 36 inch Ignition Cable with 90 degree boot and
1/4 in. spad terminal used with Q624 and Q652
Dimensions in inches (millimeters)
TERMINAL
BOARD
MOUNTING
PLATE
HIGH VOLTAGE
ELECTRODE
COVER SCREW
KNOCKOUT FOR
1/2 INCH CONDUIT
1-1/4
(32)
13/16
(20.5)
5-1/4 (133.5)
19/64
(7)
4-1/4
(108)
1-1/4
(32)
3 (76)
M20858
5-15/16 (151)
6-3/4 (171.5)
Material Number Application Voltage Frequency
Q624A1014/U Gas Ignition Transformer 120 Vac 50 Hz; 60 Hz
70-6910 815
Commercial/Industrial
Combustion Controls
Ignition Transformers
Q652 Solid State Spark Generator
Used to ignite gas burners in commercial and industrial
applications.
• Lightweight, 1 lb. (0.4 kg).
• Include single high voltage electrode for gas applications.
• For use with gas pilots with electrode spacings between 0.029 and
0.125 in.
• Secondary Peak Voltage: 14Kv rms at 21Khz.
• Mount in same space used by conventional ignition transformer.
• For use only in interrupted ignition applications.
• Prevent detection of the ignition spark when properly applied in a
flame detection system with the C7027, C7035 or C7044 Minipeeper
Ultraviolet Flame Detector.
Temperature Range: 14°F to 113°F
Approximate, Dimensions: 4 15/32 in. high x 2 15/16 in. wide x 2 9/32
in. deep (101.6 mm high x 77.5 mm wide x 58.4 mm deep)
Weight lb. (kg): 1 lb (0.45 kg)
Approvals, Underwriters Laboratories Inc.: Component Recognized
File MH14381
Approvals, CSA: LA66894
Operating Humidity Range (% RH): 90% RH
Accessories:
32004766-001/U – 24 inch Ignition Cable for Q624 and Q652
32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652
32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
32004766-004/U – 60 inch Ignition Cable with straight boots
32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot
32004766-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-001/U – 24 inch Ignition Cable for Q624 and Q652
50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652
50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot –
enter the number of feet in the Quantity box)
50060793-004/U – 60 inch Ignition Cable with straight boots
50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot
50060793-006/U – 36 inch Ignition Cable w/90 degree and straight
boot
50060793-007/U – 36 inch ignition cable w/90 degree boot on one end
only
50060793-008/U – Ignition Cable w/90 degree boot on one end only
50060793-009/U – Ignition Cable w/90 degree boot on one end only
50060793-010/U – Ignition Cable w/90 degree boot on one end only
50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end
used with Q624 and Q652
50060793-012/U – 36 inch Ignition Cable with 90 degree boot and
1/4 in. spad terminal used with Q624 and Q652
Dimensions in inches (millimeters)
M20870B
2-25/32
(71)
2-7/8 (73) 2-9/32 (59)
19 IN. (483 MM)
LEAD WIRES
HIGH VOLTAGE
ELECTRODE
3-17/64 (83)
3-21/32 (95)
4-5/32 (106)
2-15/16
(78)
Material Number Application Voltage Frequency
Q652B1006/U Gas Ignition Transformer 120 Vac 60 Hz
Q652B1014/U Solid State Ignitor Spark Generator-Gas Applications; 220V 60 Hz 220 Vac 60 Hz
816 70-6910
Ignition Transformers
Ignition Transformer Accessories or Parts
Material Number Description Used With
134666/510/U High voltage terminal insulator for Q652 and Q624 Q652; Q624
32004766-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624
32004766-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624
32004766-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624
32004766-004/U 60 inch Ignition Cable with straight boots Q652; Q624
32004766-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624
32004766-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624
32004766-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624
32004766-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624
32004766-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624
32004766-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624
32004766-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624
32004766-012/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624
4074BTN/U Bag assembly consisting of washer (103218), cap terminal (135793) and ferrule (37356) for Q624 Q624A
50060793-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624
50060793-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624
50060793-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624
50060793-004/U 60 inch Ignition Cable with straight boots Q652; Q624
50060793-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624
50060793-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624
50060793-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624
50060793-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624
50060793-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624
50060793-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624
50060793-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624
50060793-012/U 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624
50060793-013/U 48 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624
70-6910 817
Commercial/Industrial
Combustion Controls
Firing Rate Motors and Linkages
M9484D, E, F; M9494D, F Modutrol® IV Motors
Reversing, proportional motors used to drive burner firing rate
valves, dampers or auxiliary equipment. Replaces M941A, C, D
motors.
• Designed for flame safeguard applications in commercial/industrial
oil or gas burner system.
• Vibration resistant electronic drive circuit.
• Regulated by three-wire proportional controller.
• Stroke is field-adjustable to 90 or 160 degrees.
Frequency: 50 Hz; 60 Hz
Stroke: Adjustable; 90 to 160 degrees, Symmetrical
Power Consumption: 15 W
Input Signal: 135 ohm
Shaft Dimensions: double-ended, 3/8 in. square (double-ended, 9.5
mm square)
Deadweight Load on Shaft: Either End – 200 lb (300 lb combined
power and auxiliary shafts); 90.8 kg (136 kg combined power and
auxiliary shafts)
Approximate, Dimensions: 6.45 in high x 5.5 in wide x 7.3 in deep
(164 mm high x 140 mm wide x 185 mm deep)
Ambient Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No. E4436,
Guide No. XAPX for USA and Canada
Supply Voltage: 24 Vac
Accessories:
Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly
Valve. Includes 10 3/4 inch Linkage Rod.
Material
Number
Torque
Rating
(lb-in.)
Torque
Rating
(Nm)
Additional
Torque Ratings
(lb-in.)
Additional
Torque Ratings
(Nm)
Internal
Auxiliary
Switch
Auxiliary
Switch
Setting
Auxiliary Switch
Ratings
Switch Ratings Timing Factory
Stroke
Setting
M9484D1010/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
160 degrees
M9484E1009/U 75 lb-in. 8.5 Nm Breakaway –
150 lb-in.
Breakaway –
17.0 Nm
1 11 degrees 120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 15 seconds,
160 degree stroke
– 30 seconds
90 degrees
M9484E1017/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
1 1 degree 120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484E1033/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
1 7 degrees 120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484F1007/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 7 and
80 degrees
120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484F1023/U 75 lb-in. 8.5 Nm Breakaway –
150 lb-in.
Breakaway –
17.0 Nm
2 At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 15 seconds,
160 degree stroke
– 30 seconds
90 degrees
818 70-6910
Firing Rate Motors and Linkages
Material
Number
Torque
Rating
(lb-in.)
Torque
Rating
(Nm)
Additional
Torque Ratings
(lb-in.)
Additional
Torque Ratings
(Nm)
Internal
Auxiliary
Switch
Auxiliary
Switch
Setting
Auxiliary Switch
Ratings
Switch Ratings Timing Factory
Stroke
Setting
M9484F1031/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 7 and
80 degrees
120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
90 degrees
M9484F1049/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 35 and
120 degrees
120 Vac – 7.2 AFL,
43.2 ALR, 40 VA
pilot duty opposite
contact; At 240
Vac – 3.6 AFL,
21.6 ALR, 40 VA
pilot duty opposite
contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 60 seconds
160 degrees
M9484F1057/U 150 lb-in. 17 Nm Breakaway –
300 lb-in.
Breakaway –
34.0 Nm
2 At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 30 seconds,
160 degree stroke
– 53 seconds
M9494D1000/U 300 lb-in. 34 Nm Breakaway –
600 lb-in.
Breakaway –
68.0 Nm
At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 60 seconds,
160 degree stroke
– 120 seconds
90 degrees
M9494F1003/U 300 lb-in. 34 Nm Breakaway –
600 lb-in.
Breakaway –
68.0 Nm
2 At 120 Vac –
7.2 AFL, 43.2 ALR,
40 VA pilot duty
opposite contact;
At 240 Vac –
3.6 AFL, 21.6 ALR,
40 VA pilot duty
opposite contact
90 degree stroke
– 60 seconds,
160 degree stroke
– 107 seconds
90 degrees
Q100 Butterfly Valve Linkages
Connects V51E valve to M9484 and M9494 Modutrol IV Motors with
adapter plate.
• Fits all sizes of V51E Valves. Mounts easily.
Material Number Linkage Type Used with Actuator Includes Used With
Q100B1006/U Butterfly Gas Valve Modutrol Motor 10 3/4 in. Linkage Rod all sizes V51E Gas Valve
70-6910 819
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V48A; V88A Diaphragm Gas Valves
Dimensions in inches (millimeters)
1
2
1
2
BLEED TAPPING: 1/8-27 NPT.
PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT
FOR 2 THROUGH 3 IN. SIZES.
M8487A
E
C
A
B D
F
APPROXIMATE DIMENSIONS
VALVE
SIZE
(IN.)
A B C D E F
IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4-11/16
5-1/16
5-9/16
5-9/16
6-15/16
6-15/16
6-15/16
119.1
128.6
141.3
141.3
176.2
176.2
176.2
3/4
1
1-1/4
1-1/4
2-1/4
2-1/4
2-1/4
19.1
25.4
31.8
31.8
57.2
57.2
57.2
4-5/8
5
5-7/8
5-7/8
9-1/2
9-1/2
9-1/2
117.5
127.0
149.2
149.2
241.3
241.3
241.3
3-1/2
3-11/16
5-5/16
5-5/16
8-3/8
8-3/8
8-3/8
88.9
93.7
134.9
134.9
212.7
212.7
212.7
1-5/8
2-1/16
2-3/8
2-3/8
3-9/16
3-9/16
3-9/16
41.3
52.4
60.3
60.3
90.5
90.5
90.5
3-13/16
4-5/16
5-5/16
5-5/16
5-5/16
9-5/16
9-5/16
96.8
109.5
134.9
134.9
236.5
236.5
236.5
1-13/16
(46)
3-11/16
(94)
Solenoid-operated diaphragm valves provide slow opening and
fast closing suitable for controlling natural, LP or manufactured
gases. They are normally used on atmospheric boilers,
commercial water heaters, and rooftop heaters.
• V48 for line voltage service; V88 for 24 Vac service.
• Close firmly with diaphragm that is both weight and spring loaded.
• Two second maximum closing time.
• Valve closes on power failure; recommended for final shutoff service.
• Set opening time with various sized bleed orifices or adjustable
bleed valve.
• Use with LP, natural or manufactured gases.
• Made with cast aluminum in straight-through valve pattern.
• Valve position indicator available for 1-1/4 in. V48A2227.
Type of Fuel: Natural; LP; Manufactured
Bleed Tapping: 1/8-27 NPT
Body Pattern: Straight-through
Valve Opening Time: 5 sec max
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Power Consumption: 9 W; 15 VA max
Electrical Connections: 6 in. Leadwires
Operating Temperature Range: 32°F to 125°F (0°C to 52°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ
Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5)
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Pilot Tapping Voltage Approximate, Dimensions Pressure
Rating
(psi)
Pressure
Rating
(kPa)
Current Ratings Comments Includes
V48A2151/U 3/4 in. DN20 1/8-27 NPT 120 Vac 5 7/16 in. high x 3 13/16 in. wide
x 4 5/8 in. deep (138 mm high x
97 mm wide x 118 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2169/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2177/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2185/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2227/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Includes position
indicator
Ground
terminal
V48A2243/U 2 in. DN50 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2250/U 2 1/2 in. DN65 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
820 70-6910
Diaphragm Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Pilot Tapping Voltage Approximate, Dimensions Pressure
Rating
(psi)
Pressure
Rating
(kPa)
Current Ratings Comments Includes
V48A2268/U 3 in. DN80 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2276/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2334/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V48A2342/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.13 max amps at
rated Vac/Hz
Ground
terminal
V88A1618/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1626/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1634/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1659/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide
x 4 5/8 in. deep (138 mm high x
97 mm wide x 118 mm deep)
1/2 psi 3.4 kPa 0.62 max amps at
rated Vac/Hz
V88A1667/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide
x 4 5/8 in. deep (138 mm high x
97 mm wide x 118 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1675/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x
5 in. deep (154 mm high x 127 mm
wide x 109 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1683/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1691/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide
x 5 7/8 in. deep (173 mm high x
135 mm wide x 149 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1709/U 2 in. DN50 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
V88A1717/U 2 1/2 in. DN65 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide
x 9 1/2 in. deep (233 mm high x
237 mm wide x 241 mm deep)
1 psi 6.9 kPa 0.62 max amps at
rated Vac/Hz
70-6910 821
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V48J; V88J High Temperature Diaphragm Gas Valves
Dimensions in inches (millimeters)
1
2
1
2
BLEED TAPPING: 1/8-27 NPT.
PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT
FOR 2 THROUGH 3 IN. SIZES.
M8487A
E
C
A
B D
F
APPROXIMATE DIMENSIONS
VALVE
SIZE
(IN.)
A B C D E F
IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4-11/16
5-1/16
5-9/16
5-9/16
6-15/16
6-15/16
6-15/16
119.1
128.6
141.3
141.3
176.2
176.2
176.2
3/4
1
1-1/4
1-1/4
2-1/4
2-1/4
2-1/4
19.1
25.4
31.8
31.8
57.2
57.2
57.2
4-5/8
5
5-7/8
5-7/8
9-1/2
9-1/2
9-1/2
117.5
127.0
149.2
149.2
241.3
241.3
241.3
3-1/2
3-11/16
5-5/16
5-5/16
8-3/8
8-3/8
8-3/8
88.9
93.7
134.9
134.9
212.7
212.7
212.7
1-5/8
2-1/16
2-3/8
2-3/8
3-9/16
3-9/16
3-9/16
41.3
52.4
60.3
60.3
90.5
90.5
90.5
3-13/16
4-5/16
5-5/16
5-5/16
5-5/16
9-5/16
9-5/16
96.8
109.5
134.9
134.9
236.5
236.5
236.5
1-13/16
(46)
3-11/16
(94)
Solenoid-operated diaphragm valves provide slow opening and
fast closing suitable for controlling natural, LP or manufactured
gases. They are normally used on atmospheric boilers,
commercial water heaters, and rooftop heaters.
• Rated for 150°F (66°C) maximum temperature applications.
• V48 for line voltage service; V88 for 24 Vac service.
• Close firmly with diaphragm that is both weight and spring loaded.
• Two second maximum closing time.
• Valve closes on power failure; recommended for final shutoff service.
• Set opening time with various sized bleed orifices or adjustable
bleed valve.
• Use with LP, natural or manufactured gases.
• Made with cast aluminum in straight-through valve pattern.
Type of Fuel: Natural; LP; Manufactured
Bleed Tapping: 1/8-27 NPT
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through
Valve Opening Time: 5 sec max
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Electrical Connections: 6 in. Leadwires
Operating Temperature Range: 32°F to 150°F (0°C to 66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ
Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5)
Pressure Ratings (psi): 1 psi
Pressure Ratings (kPa): 6.9 kPa
Current Ratings: 0.62 max amps at rated Vac/Hz
Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption
V88J1006/U 1 in. DN25 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm
high x 127 mm wide x 109 mm deep)
9 W; 15 VA max
V88J1022/U 1 1/4 in. DN32 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep
(173 mm high x 135 mm wide x 149 mm deep)
9 W; 15 VA max
822 70-6910
Diaphragm Gas Valves
V4943/V8943A On/Off Diaphragm Gas Valves
V4943A/V8943A are on/off diaphragm gas valve used on boilers,
unit heaters, duct furnaces, makeup air and rooftop heaters.
• Designed for replacement for V4843A/V8843A Gas Valves.
• Suitable for use on atmospheric boilers, commercial water heaters,
and rooftop heaters.
• V8943A/V4943A models are solenoid-operated diaphragm valves for
on/off flow control of natural or LP gas.
• Valve body of die-cast aluminum with a straight-through pattern.
• V4943 are used with line voltage, on/off controllers; V8943A are
used with 24 Vac thermostats or controllers.
• Valve closes on power failure; recommended for final shutoff service.
Type of Fuel: Natural; LP
Bleed Tapping: Internal Bleed
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through, non-offset
Opening Characteristics: Rapid Opening On-Off
Valve Opening Time: 6 sec max
Valve Closing Time: 3 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Electrical Connections: 1/4 in. (6 mm) spade terminals (quick
connects). 30 in. (762 mm) leadwires and cover for electrical conduit
connection provided.
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ (60 Hz only)
Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3371-03,
83 (Z21.21, Z21.78)
Pressure Ratings (psi): 1/2 psi
Pressure Ratings (kPa): 3.4 kPa
Comments: (2) 30" leadwires
Current Ratings: 0.055 max amps at rated Vac/Hz
Dimensions in inches (millimeters)
6-9/16 (167)
FOR 1, 1-1/4
OR
7-3/8 (187)
FOR 1-1/2, 2
SIDE VIEW
6 (152)
6
(152)
TOP VIEW
M23232
VENT CONNECTIONS
(V4944/V8944 HAVE TWO)
Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption
V4943A1011/U 1 in. DN25 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
6 VA max
V4943A1029/U 1 1/4 in. DN32 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
6 VA max
V4943A1037/U 1 1/2 in. DN40 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
6 VA max
V4943A1045/U 2 in. DN50 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
6 VA max
V8943A1012/U 1 in. DN25 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
8 VA max
V8943A1020/U 1 1/4 in. DN32 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x
152 mm deep)
8 VA max
V8943A1038/U 1 1/2 in. DN40 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
8 VA max
V8943A1046/U 2 in. DN50 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x
152 mm deep)
8 VA max
70-6910 823
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V4943/V8943B, C, N Single Stage Pressure Regulating Valves
V4943B, N/8943B, C, N are Single-stage Pressure Regulating
Valves. These valves are used on boilers, unit heaters, duct
furnaces, makeup air and rooftop heaters.
• Designed for replacement for V4843/V8843 Gas Valves.
• Suitable for use on atmospheric boilers, commercial water heaters,
and rooftop heaters.
• V4943/V8943B, C, N models are solenoid-operated diaphragm
valves that combine the functions of safety shutoff and pressure
regulation in a single unit.
• V4943/V8943B, N are for use with natural gas.
• V4943/V8943C are for use with LP gas.
• Valve body of die-cast aluminum with a straight-through pattern.
• V4943 are used with line voltage, on/off controllers; V8943 are used
with 24 Vac thermostats or controllers.
• Valve closes on power failure; recommended for final shutoff service.
Bleed Tapping: 5/16-24 UNF
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through, non-offset
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Frequency: 60 Hz
Electrical Connections: 1/4 in. (6 mm) spade terminals (quick
connects). 30 in. (762 mm) leadwires and cover for electrical conduit
connection provided.
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ (60 Hz only)
Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01,
81 (Z21.21, Z21.78)
Pressure Ratings (psi): 1/2 psi
Pressure Ratings (kPa): 3.4 kPa
Comments: (2) 30" leadwires
Dimensions in inches (millimeter)
6-9/16 (167)
FOR 1, 1-1/4
OR
7-3/8 (187)
FOR 1-1/2, 2
SIDE VIEW
6 (152)
6
(152)
TOP VIEW
M23232
VENT CONNECTIONS
(V4944/V8944 HAVE TWO)
Material
Number
Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Voltage Approximate, Dimensions Valve
Opening
Time
Current
Ratings
Pressure Regulator
Setpoint (in. wc)
Power
Consumption
V4943B1019/U Natural 1 in. DN25 Slow Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max;
6.6 VA
V4943B1027/U Natural 1 1/4 in. DN32 Slow Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943B1035/U Natural 1 1/2 in. DN40 Slow Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943B1043/U Natural 2 in. DN50 Slow Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943N1012/U Natural 1 in. DN25 Rapid Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943N1020/U Natural 1 1/4 in. DN32 Rapid Opening
1-stage
120 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
824 70-6910
Diaphragm Gas Valves
Material
Number
Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Voltage Approximate, Dimensions Valve
Opening
Time
Current
Ratings
Pressure Regulator
Setpoint (in. wc)
Power
Consumption
V4943N1038/U Natural 1 1/2 in. DN40 Rapid Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V4943N1046/U Natural 2 in. DN50 Rapid Opening
1-stage
120 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.055 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
6.6 VA max
V8943B1010/U Natural 1 in. DN25 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943B1028/U Natural 1 1/4 in. DN32 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943B1036/U Natural 1 1/2 in. DN40 Slow Opening
1-stage
24 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943B1044/U Natural 2 in. DN50 Slow Opening
1-stage
24 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943C1018/U LP 1 in. DN25 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High
Fire – 8.8 in. wc to
11.5 in. wc; Factory
Setting, High Fire –
10.0 in. wc
9 VA max
V8943C1026/U LP 1 1/4 in. DN32 Slow Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
3 to 25
sec
0.363 max
amps at rated
Vac/Hz
Adj. Range, High
Fire – 8.8 in. wc to
11.5 in. wc; Factory
Setting, High Fire –
10.0 in. wc
9 VA max
V8943N1013/U Natural 1 in. DN25 Rapid Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943N1021/U Natural 1 1/4 in. DN32 Rapid Opening
1-stage
24 Vac 6 9/16 in. high x 6 in. wide
x 6 in. deep (167 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
V8943N1039/U Natural 1 1/2 in. DN40 Rapid Opening
1-stage
24 Vac 7 3/8 in. high x 6 in. wide
x 6 in. deep (187 mm high
x 152 mm wide x 152 mm
deep)
6 sec max 0.363 max
amps at rated
Vac/Hz
Adj. Range, High Fire
– 3 in. wc to 4.5 in.
wc; Factory Setting,
High Fire – 3.5 in. wc
9 VA max
70-6910 825
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
V4944/V8944B, C, L, N Two Stage Pressure Regulating Gas Valves
V4944B, L, N/8944B, C, L, N are Two-stage Pressure Regulating
Gas Valves. These valves are used on boilers, unit heaters, duct
furnaces, makeup air and rooftop heaters.
• Designed for replacement for V4844/V8844 Gas Valves.
• Suitable for use on atmospheric boilers, commercial water heaters,
and rooftop heaters.
• V4944/V8944B, C, L, N models are solenoid-operated diaphragm
valves that combine the functions of safety shutoff and pressure
regulation in a single unit.
• V4944/V8944B, N are for use with natural gas.
• V4944/V8944C, L are for use with LP gas.
• Valve body of die-cast aluminum with a straight-through pattern.
• V4944 are used with line voltage, dual-stage controllers; V8944 are
used with 24 Vac dual-stage thermostats or controllers.
• Valve closes on power failure; recommended for final shutoff service.
Bleed Tapping: Two 5/16-24 UNF
Pilot Tapping: 1/8-27 NPT
Body Pattern: Straight-through, non-offset
Valve Closing Time: 2 sec max
Mounting: Upright (horizontal)
Materials: Body – Aluminum
Voltage: V4944-120 Vac; V8944-24 Vac
Frequency: 60 Hz
Power Consumption: V4944-9 VA max; V8944-12.4 VA max
Electrical Connections: 1/4 in. (6 mm) spade terminals (quick
connects), leadwires and cover for electrical conduit connection
provided.
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide
No. YIOZ (60 Hz only)
Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01,
81 (Z21.21, Z21.78)
Pressure Ratings (psi): 1/2 psi
Pressure Ratings (kPa): 3.4 kPa
Current Ratings: V4944-0.077 max amps at rated Vac/Hz;
V8944-0.516 max amps at rated Vac/Hz
Dimensions in inches (millimeter)
6-9/16 (167)
FOR 1, 1-1/4
OR
7-3/8 (187)
FOR 1-1/2, 2
SIDE VIEW
6 (152)
6
(152)
TOP VIEW
M23232
VENT CONNECTIONS
(V4944/V8944 HAVE TWO)
Material Number Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Valve
Opening Time
Pressure Regulator Setpoint (in. wc) Comments
V4944B1018/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944B1026/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944B1059/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.7 in. wc; Factory
Setting, High Fire – 3.0 in. wc
(3) 30" leadwires
V4944B1075/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.6 in. wc; Factory
Setting, High Fire – 3.5 in. wc
V4944B1091/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.6 in. wc; Factory
Setting, High Fire – 3.5 in. wc
V4944L1024/U LP 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
826 70-6910
Diaphragm Gas Valves
Material Number Type of
Fuel
Pipe Size
(inch)
Pipe Size
(DN)
Opening
Characteristics
Valve
Opening Time
Pressure Regulator Setpoint (in. wc) Comments
V4944N1011/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1029/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1037/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1045/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V4944N1060/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.0 in. wc; Factory
Setting, High Fire – 3.0 in. wc
(3) 85" leadwires
V8944B1019/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944B1027/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944B1035/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944B1043/U Natural 2 in. DN50 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944C1017/U LP 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
V8944C1025/U LP 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
V8944C1033/U LP 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc;
Adj. Range, High Fire – 8.8 in. wc to 11.5 in.
wc; Factory Setting, Low Fire – 1.4 in. wc;
Factory Setting, High Fire – 10.0 in. wc
(3) 30" leadwires
V8944N1012/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1020/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1038/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1046/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 0.8 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1053/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.2 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
V8944N1061/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc;
Adj. Range, High Fire – 3 in. wc to 4.5 in. wc;
Factory Setting, Low Fire – 1.2 in. wc; Factory
Setting, High Fire – 3.5 in. wc
(3) 30" leadwires
70-6910 827
Commercial/Industrial
Combustion Controls
Diaphragm Gas Valves
Diaphragm Gas Valve Replacement Parts or Accessories
Material Number Description Used With
116930/U 24 Vac, 60 Hz Replacement Coil for V88A Solenoid Operated Valve V88A
116931/U 120 V/60 Hz Replacement Coil for V48A Solenoid Operated Valve V48; V48A
116932/U 220-240 V/50-60 Hz Replacement Coil for V48A Solenoid Operated Valve V48A
118888/U 24V 60 Hz Replacement Coil for V88J V88J
122160/U Orifice - .018" for V48, V88 V48, V88
124674/U Orifice - .011" for V48, V88 V48, V88
126590/U Adjustable Bleed Valve Assembly for V48, V88, V4004. V8004. 1/8 in. NPT to
1/4 in. compression fitting
V48, V88
204480/U Regulator vent pipe fitting to be used with V4843/V8843B, C, L, N and V4844/
V8844B, C, L, N and V4943/V8943, V4944/V8944
V4843B; V4843C; V4843L; V4843N; V8843B; V8843C; V8843L;
V8843N; V4844B; V4844C; V4844L; V4844N; V8844B; V8844C;
V8844L; V8844N; V4943; V8943; V4944; V8944
828 70-6910
Butterfly Gas Valves
V51 Butterfly Gas/Air Valve
Provides modulating control of natural, manufactured, LP gases
or air.
• Use in commercial and industrial installations where large amounts
of gas must be closely controlled.
• NOT for use as safety shutoff valve.
• Adaptable to most modulating jobs.
• Modutrol motor, such as the M9484 or M9494, may be mounted
directly on valve or close to it.
• Valve mechanism has strain release.
• Adjustable stroke over low fire-high fire range.
• Straight-through valve pattern.
• Rugged cast aluminum body provides durability and maintenancefree
operation.
Type of Fuel: Air; natural; manufactured; LP
Body Pattern: Straight-through
Mounting: Motor shaft horizontal
Materials: Body – Aluminum
Operating Temperature Range: 32°F to 140°F (0°C to 60°C)
Approvals, Underwriters Laboratories Inc.: File No. MH5968 Vol. 1
Sec. 1, Guide no. MHKZ
Pressure Ratings (psi): 5 psi
Pressure Ratings (kPa): 34.5 kPa
Used With: Mod Motor with Q100 Linkage
Accessories:
32003396-001/U – V51E mounting kit for 1-1/2 and 2 in. valve actuators
includes brackets and hardware
32003396-002/U – V51E mounting kit for 2-1/2, 3 and 4 in. valve
actuators includes brackets and hardware
Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly
Valve. Includes 10 3/4 inch Linkage Rod.
Dimensions in inches (millimeter)
VALVE
SIZE (in.)
1 1/2
2
2 1/2
3
4
2 21/32
3 5/32
3 27/32
4 1/32
5 21/64
67.5
80.2
97.6
102.4
135.3
A
A
1
in. mm
1 9/16
1 13/16
2 5/16
2 25/64
3 5/32
39.7
46.0
58.7
60.7
80.2
B
B
in. mm
4 1/4
4 1/4
4 13/16
5
5 3/8
108.0
108.0
122.2
127.0
136.5
C
C
in. mm
3 1/32
3 17/32
4 23/32
4 23/32
5 17/64
77.0
89.7
119.9
119.9
133.8
D
D
in. mm
M9532A
1 2 1
1 MAXIMUM DIMENSIONS.
2 NOMINAL DIMENSIONS.
V51E DIMENSIONS
Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Pressure Tapping Approximate, Dimensions
V51E1000/U 1 1/2 in. DN40 4200 cfh 118.9 m3/hr Inlet and outlet pressure
taps – Two downstream
1/4 in. NPT taps
2 11/16 in. high x 3 1/16 in. wide x 5 13/16 in.
deep (68 mm high x 77 mm wide x 148 mm deep)
V51E1018/U 2 in. DN50 9210 cfh 260.7 m3/hr 3 3/16 in. high x 3 9/16 in. wide x 6 1/16 in. deep
(80 mm high x 90 mm wide x 154 mm deep)
V51E1034/U 2 1/2 in. DN65 8390 cfh 199.8 m3/hr 3 7/8 in. high x 4 3/4 in. wide x 7 1/8 in. deep
(98 mm high x 120 mm wide x 181 mm deep)
V51E1059/U 3 in. DN80 14640 cfh 414.5 m3/hr 4 1/16 in. high x 4 3/4 in. wide x 7 3/8 in. deep
(102 mm high x 120 mm wide x 188 mm deep)
V51E1075/U 4 in. DN100 33000 cfh 934.2 m3/hr 5 3/8 in. high x 5 1/4 in. wide x 8 9/16 in. deep
(135 mm high x 134 mm wide x 217 mm deep)
70-6910 829
Commercial/Industrial
Combustion Controls
Butterfly Gas Valves
V5197 Integrated Valve Train Butterfly Gas Valve
Dimensions in inches (millimeters)
10-5/16
(277)
4-27/32 (123)
6-7/16 (165)
2-1/2 (64)
7-1/8
(181)
3-25/32
(96)
M17528
The V5197A valve provides flow control of air, natural gas, liquid
petroleum, & manufactured gases which require a high turn down
ratio. The adjustment screw controls the maximum flow of gas, but
keeps the linear modulating characteristics & stroke.
• Used with air, natural, manufactured or liquefied petroleum (LP)
gases.
• For modulating applications that do not require final shutoff service
of firing rate valve.
• Two valve body types (small and large) applicable to seven pipe
sizes: Small body type for 3/4 in. (19 mm), 1 in. (25 mm), 1-1/4 in.
(32 mm), 1-1/2 in. (38 mm) and 2 in. (51 mm) pipes, NPT or ISO 7
threads. Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm) and 3
in. (76 mm) pipes, NPT or ISO 7 threads.
• Two downstream 1/4 in. NPT threaded pressure taps available.
• Accepts C6097 Pressure Switch mounted directly to flange
(downstream pressure tap only).
• Unpainted cast aluminum body.
• Suitable for electric or pneumatic operators with the appropriate
linkage.
• May be used with manufacturers own linkage and drive motor.
• Flow adjustment screw on bottom of valve controls maximum flow.
• Visual position indicator.
Type of Fuel: Air; natural; manufactured; LP
Pressure Tapping: Inlet and outlet pressure taps – Two downstream
1/4 in. NPT taps
Mounting: Directly bolted to Integrated Valve Train (IVT) components
or IVT adapters
Materials: Body – Die-cast aluminum
Operating Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, Underwriters Laboratories Inc.: Component Listed
Approvals, CSA: Design Certified
Approvals, Swiss RE: Acceptable
Pressure Ratings (psi): 15 psi max
Pressure Ratings (kPa): 1 Bar
Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions
V5197A1003 3/4 in.; 1 in.; 1 1/4 in.;
1 1/2 in.; 2 in.
DN20; DN25; DN32;
DN40; DN50
2450 cfh for 3/4 in.;
3080 cfh for 1 in.;
4430 cfh for 1 1/4 in.;
5010 cfh for 1 1/2 in.;
5480 cfh for 2 in.
51 mm is 155/
38 mm is 142/
32 mm is 125/
25 mm is 87/
19 mm is 69
10 5/16 in. high x 6 7/16 in. wide x 7 11/32 in. deep
(277 mm high x 165 mm wide x 187 mm deep)
V5197A1011 2 in.; 2 1/2 in.; 3 in. DN65; DN80; DN50 12,600 cfh for 2 in.;
14,800 cfh for 2 1/2
in.; 16,900 cfh for 3 in.
76 mm is 478/
64 mm is 419/
51 mm is 356
12 11/16 in. high x 9 1/4 in. wide x 8 13/16 in. deep
(322 mm high x 235 mm wide x 224 mm deep)
Firing Rate Gas Valve Parts
Material Number Description Used With
49084/0021/U Adjusting arm for V51E. V51E
49085B/U Strain Release Assembly V51E
830 70-6910
Gas Valve Actuators
Selection Chart: V5055 and V5097 Industrial Gas Valves with V4055,
V4062 or V9055 Fluid Power Actuators
The chart below describes every model of V5055 or V5097 Valve in
the left column, and every model of Fluid Power Actuator across the
top. While it’s possible to combine any valve with any actuator, we’ve
marked the recommended valve/actuator combinations which cover
most applications with a •.
Each valve described in the left column is available:
• In these sizes: 3/4 to 3 in. (NPT or parallel BSP). V5055A, B, C are
also available in 4 in. size (flange connection only).
• With upstream and/or downstream tap.
Options available on some Fluid Power Actuators include:
• Damper arm shaft, with or without spring return.
• NEMA 4 enclosure.
• Fast or slow open time (13 or 26 seconds).
• Auxiliary switch.
• Valve seal overtravel interlock switch.
For complete specifications and ordering information on V5055 and
V5097 Valves and V4055, V4062 and V9055 Fluid Power Actuators,
refer to Index for specific page numbers.
Fluid Power Actuators/ Industrial Gas Valves Standard pressurea High Pressurea
V5055A, Fb, V5097A V5055B, V5097B V5055C, V5097C V5055D, V5097D V5055E, V5097E
Type Model Pressure Ratinga On-Off Characterized Guidec VSOId On-Off VSOId
V4055
On-Off
A, Ge Standard • • •
B High • f • f •
Dd Fd e Standard • •
Ed High • f •
V4062
Hi-Lo-Off
A Standard • •
B High • f • f •
Dd Standard •
V9055
Modulating
A Standard •
Dd Standard •
a Refer to the table below for actual pressure ratings of the various
combinations of valves and actuators.
b V5055F models meet EN161 leakage requirements.
c Characterized guide provides a more linear relationship between stem
travel and gas flow. Check Honeywell form 70-8311 to verify that flow
curve characteristics match application requirements.
d Valve Seal Overtravel Interlock. Valve has two shutoff seals, actuator has
a proof-of-closure switch.
e V4055F, G models include switch for manual control.
f These combinations have higher pressure ratings; see the table below.
The following combinations of V5055 and V5097 Valves, and V4055, V4062 and V9055 Fluid Power Actuators are approved by these agencies.
Underwriters Laboratories, Inc: Listed: MH1639
V4055A/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055B/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055E/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V4055F/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.).
V4055G/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.).
V4062A, D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.).
V9055A, D/V5055A, B, C, E (3/4-4 in.) or V5097A-E (3/4-3 in.).
Factory Mutual Approved: Report No. 20698, 20835, 21172 and
24061:
Valve Actuator Approvals:
V4055A/V5055A and V5097A.
V4055D/V5055C and V5097C.
V4055A/V5055B and V5097B.
V4055B/V5055D and V5097D.
V4055E/V5055E and V5097E.
V4055F/V5055Ca and V5097C.
V4055G/V5055A, Ba and V5097A, B.
V9055A/V5055B, C and V5097B, C.
a Manual reset safety shut-off valves.
Pressure Ratings of Valve-Actuator Combinations
Model Pipe Size Standard Pressure Actuators
V4055A, D, F, G, V4062A, D, V9055A, D
High Pressure Actuators
V4O55B, E, V4062B
M.O.P.D. a Max. Rated Pressure b M.O.P.D. a Max. Rated Pressure b
Standard Pressure
Valves V5055A, B, C,
F, V5097A, B, C
3/4" to 1-1/2" c 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar
2" to 3" d 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar
4" flanged e 3 PSI 207 mbar 15 PSI 1.0 Bar 5 PSI 340 mbar 15 PSI 1.0 Bar
High Pressure Valves
V5055D, E, V5097D, E
3/4" to 1-1/2" c 5 PSI 340 mbar 75 PSI 5.0 Bar 25 PSI 1720 mbar 75 PSI 5.0 Bar
2" to 3" d 5 PSI 340 mbar 45 PSI 3.0 Bar 15 PSI 1030 mbar 45 PSI 3.0 Bar
a Max Operating Pressure Differential (UL) or Max Operating Pressure
(CSA); maximum allowable pressure drop from inlet to outlet for proper
operation.
b Max Rated Pressure (UL) or Max Close-off Pressure (CSA); maximum
pressure that the valve can be exposed to without leakage or damage to
the valve.
c Applies for small-body V5097 valves 3/4” up to 2” pipe size.
d Applies for large-body V5097 valves 2” up to 3” pipe size.
e V5055A, B, C only.
70-6910 831
Commercial/Industrial
Combustion Controls
Gas Valve Actuators
V4055A, B, D, E On-Off Fluid Power Gas Valve Actuator
Use in combination with V5055 or V5097 Gas Valves to control gas
supply to commercial and industrial burners.
• Use where smooth light off is important.
• One-second maximum closing time.
• Continuously displays the valve position with a red indicator when
open and a yellow indicator when closed.
• Mount in any position directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Operating Temperature Ratings: 60 Hz Models: -40°F to +150°F
(-40°C to +66°C). 50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to
+70°C).
Contact Ratings: V4055D, E ONLY-Proof of Closure (Factory Mutual)
Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp
Used With: V5055; V5097 Gas Valves
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with
V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No.
MH1639 Guide No. YIOZ
Approvals, Factory Mutual: V4055A-When used with the V5055A,
B or V5097A, B: Approved, Report Nos. 20698, 20835, 21172, and
24061; V4055B, D, E-When used with the V5055D or V5097D:
Approved, Report Nos. 20698, 20835, 21172, and 24061
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Dimensions in inches (millimeters)
B
A
1
1
(32.5)
KNOCKOUT
FOR 1/2 INCH
CONDUIT (4)
5 (127.0)
1-9/32
27/32
(21.4)
3-23/32
(94.5)
6-3/4 (171.5)
ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL.
M10981A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4

283
283
283
283
298
298
298

2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8

70
70
70
70
86
86
86

DIM A
V5055 V5097
IN. MM
DIM B
IN. MM
DIM A
IN. MM
DIM B
IN. MM
VALVE VALVE
Material
Number
Electrical
Ratings
Frequency Timing Internal
Auxiliary Switch
Maximum
Safe Operating
Pressure (psi)
Maximum
Safe Operating
Pressure (kPa)
Auxiliary Switch
Ratings
Comments Includes
V4055A1007/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa
V4055A1031/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa
V4055A1064/U 120 Vac 50 Hz; 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1080/U 240 Vac 50 Hz; 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1098/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1114/U 240 Vac 50 Hz; 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055A1296/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
Yes - adjusted to
90% stroke
5 psi 34 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
V4055A1304/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
with return
spring installed
V4055A1312/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Nema 4
Enclosure
V4055B1021/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Damper Shaft
V4055B1039/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Damper Shaft
832 70-6910
Gas Valve Actuators
Material
Number
Electrical
Ratings
Frequency Timing Internal
Auxiliary Switch
Maximum
Safe Operating
Pressure (psi)
Maximum
Safe Operating
Pressure (kPa)
Auxiliary Switch
Ratings
Comments Includes
V4055B1088/U 220 Vac 50 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa
V4055D1001/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055D1019/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa Damper Shaft
V4055D1027/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
Yes 5 psi 34 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
Nema 4
Enclosure
V4055D1035/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
Yes 5 psi 34 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
V4055D1043/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 5 psi 34 kPa
V4055E1016/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Damper Shaft
V4055E1024/U 120 Vac 60 Hz Opening – 26 sec;
Closing – < 1 sec
Yes 15 or 25 psi 103 or 172 kPa 120 Vac – 9.8 AFL,
58.8 ALR, 1/2 hp;
240 Vac – 4.9 AFL,
29.4 ALR, 1/2 hp
Nema 4
Enclosure
Damper Shaft
V4055E1040/U 120 Vac 60 Hz Opening – 13 sec;
Closing – < 1 sec
No 15 or 25 psi 103 or 172 kPa Nema 4
Enclosure
Damper Shaft
70-6910 833
Commercial/Industrial
Combustion Controls
Gas Valve Actuators
V4055F, G Manual Reset Safety Shut-off Gas Valve Actuators
Provide manual reset, safety shut-off functions as required on FM,
IHEA-IRI and NFPA 86A,B,C industrial furnaces, ovens and kilns.
Use with V5055 or V5097 Gas Valves to control gas supply.
• Close in one second maximum.
• Continuously displays the valve position with a red indicator when
closed.
• Mount directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Frequency: 60 Hz
Temperature Range: -40°F to +150°F (-40°C to +66°C)
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with
V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No.
MH1639 Guide No. YIOZ
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Dimensions in inches (millimeters)
B
A
1
1
(32.5)
KNOCKOUT
FOR 1/2 INCH
CONDUIT (4)
5 (127.0)
1-9/32
27/32
(21.4)
3-23/32
(94.5)
6-3/4 (171.5)
ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL.
M10981A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4

283
283
283
283
298
298
298

2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8

70
70
70
70
86
86
86

DIM A
V5055 V5097
IN. MM
DIM B
IN. MM
DIM A
IN. MM
DIM B
IN. MM
VALVE VALVE
Material
Number
Electrical
Ratings
Internal
Auxiliary
Switch
Timing Maximum
Safe
Operating
Pressure
(psi)
Maximum
Safe
Operating
Pressure
(kPa)
Contact Ratings Description Approvals, Factory
Mutual
Used With
V4055F1006/U 120 Vac No Opening – 13 sec;
Closing – < 1 sec
5 psi 34 kPa Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2
hp; 4.9 AFL, 29.4
ALR, 1/2 hp
Manual reset safety
shutoff valve with
proof of closure
switch.
When used with the
V5055D or V5097D:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
V4055G1004/U 120 Vac No Opening – 13 sec;
Closing – < 1 sec
5 psi 34 kPa Manual ON-OFF
actuator normally used
with V5055/V5907A,
B valve bodies. Low
pressure.
When used with
the V5055A, B
or V5097A, B:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
834 70-6910
Gas Valve Actuators
V4062 Off-Lo-Hi Fluid Power Gas Valve Actuators
Use with V5055 or V5097 Gas Valves to control gas supply for
commercial and industrial burners. Valve opens to low fire
position when power is applied; valve opens all the way on
demand.
• Provide final safety shutoff service when used with V5055 or V5097
gas valve.
• One-second maximum closing time.
• Continuously displays the valve position with a red indicator when
open and a yellow indicator when closed.
• Mount in any position directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Electrical Ratings: 120 Vac
Frequency: 60 Hz
Maximum Safe Operating Pressure (psi): 5 psi
Maximum Safe Operating Pressure (kPa): 34 kPa
Temperature Range: -40°F to +150°F (-40°C to +66°C)
Used With: V5034; V5055; V5097; VE5000
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with
V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No.
MH1639 Guide No. YIOZ
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Dimensions in inches (millimeters)
B
A
1
1
(32.5)
KNOCKOUT
FOR 1/2 INCH
CONDUIT (4)
5 (127.0)
1-9/32
27/32
(21.4)
3-23/32
(94.5)
6-3/4 (171.5)
ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL.
M10981A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4

283
283
283
283
298
298
298

2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8

70
70
70
70
86
86
86

DIM A
V5055 V5097
IN. MM
DIM B
IN. MM
DIM A
IN. MM
DIM B
IN. MM
VALVE VALVE
Material
Number
Internal
Auxiliary Switch
Timing Contact Ratings Auxiliary Switch Range Description Comments Includes
V4062A1008/U No Opening – 26 sec;
Closing – < 1 sec
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
V4062A1123/U Yes Opening – 26 sec;
Closing – < 1 sec
120 Vac – 9.8 AFL, 58.8
ALR, 1/2 hp; 240 Vac –
4.9 AFL, 29.4 ALR, 1/2 hp
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
with return
spring installed
V4062A1131/U No Opening – 13 sec;
Closing – < 1 sec
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
V4062A1156/U No Opening – 26 sec;
Closing – < 1 sec
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
For Series 60
Floating Control
V4062A1198/U Yes - adjusted
to 90 degree
stroke
Opening – 13 sec;
Closing – < 1 sec
120 Vac – 9.8 AFL, 58.8
ALR, 1/2 hp; 240 Vac –
4.9 AFL, 29.4 ALR, 1/2 hp
Low pressure HI-LO-OFF
actuator for use with V5055B
and V5097B valve bodies
Damper Shaft
with return
spring installed
V4062D1002/U No Opening – 26 sec;
Closing – < 1 sec
Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2 hp;
4.9 AFL, 29.4 ALR,
1/2 hp
HI-LO-OFF actuator with
Proof of Closure normally
used on V5055C, E/V5907C,
E valve bodies (Low
Pressure)
Damper Shaft
V4062D1010/U No Opening – 13 sec;
Closing – < 1 sec
Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2 hp;
4.9 AFL, 29.4 ALR,
1/2 hp
HI-LO-OFF actuator with
Proof of Closure normally
used on V5055C, E/V5907C,
E valve bodies (Low
Pressure)
Damper Shaft
70-6910 835
Commercial/Industrial
Combustion Controls
Gas Valve Actuators
V9055 Modulating Fluid Power Gas Valve Actuators
Use with V5055 or V5097 Gas Valves to control gas supply for
commercial and industrial burners. Valve opens to low fire
position when power is applied; valve opens all the way on
demand.
• Include integral shaft to drive combustion air damper in unison with
valve.
• One-second maximum closing time.
• Continuously displays the valve position with a red indicator when
open and a yellow indicator when closed.
• Mount in any position directly to valve bonnet with three setscrews.
• Provide final safety shutoff service when used with V5055 or V5097
Gas Valves.
Frequency: 60 Hz
Temperature Range: -40°F to +125°F (-40°C to +52°C)
Internal Auxiliary Switch: No
Includes: Damper Shaft
Approvals, CSA: When used with V5055 and V5097: Certified General
listed File No. 158158, Class 3371 for USA and Canada
Approvals, Underwriters Laboratories Inc.: When used with V5055A,
B, C, E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.) Listed MH1696
Approvals, Swiss RE: When used with V5055 or V5097: Acceptable
Accessories:
203422C/U – 4-20 ma Adapter for V9055
Material
Number
Electrical
Ratings
Comments Timing Maximum
Safe
Operating
Pressure
(psi)
Maximum
Safe
Operating
Pressure
(kPa)
Contact Ratings Description Approvals, Factory
Mutual
Used With
V9055A1055/U 120 Vac Opening – 26 sec;
Closing – < 1 sec
5 psi 34 kPa Low pressure
Modulating-OFF actuator
for use with V5055B
valve bodies
When used with
the V5055B, C
or V5097B, C:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
V9055A1063/U 120 Vac Nema 4
Enclosure
Opening – 26 sec;
Closing – < 1 sec
5 psi 34 kPa Low pressure
Modulating-OFF actuator
for use with V5055B
valve bodies
When used with
the V5055B, C
or V5097B, C:
Approved, Report
Nos. 20698, 20835,
21172, and 24061
V5034; V5055;
V5097; VE5000
V9055D1000/U 120 Vac Opening – 26 sec;
Closing – < 1 sec
5 psi 34 kPa Proof of Closure
(Factory Mutual)
Switch – 9.8 AFL,
58.8 ALR, 1/2 hp;
4.9 AFL, 29.4 ALR,
1/2 hp
Low pressure
Modulating-OFF actuator
with Proof of Closure
normally used on
V5055C, E/V5907C, E
valve bodies.
V5034; V5055;
V5097; VE5000
836 70-6910
Gas Valve Actuators
Dimensions in inches (millimeters)
B
E
F
C
D
G A
1 3
D
1/4 INCH NPT
DOWNSTREAM TAP
AND PLUG
1/4 INCH NPT
UPSTREAM TAP
AND PLUG (1/4 BSP
ON INTERNATIONAL
MODELS)
2
1
2
3
[32.5]
KNOCKOUT
FOR1/2 INCH
CONDUIT (4)
OCTAGON
3/4 [19.1] BOLT
HOLES (8)
ON 3-3/4 (95)
RADIUS
1
9
32
1
3
16
[30]
9
3
16
[233]
27
32 [21.5]
3 23
32
5
[94.5]
3 [127.0]
19
32 [91]
6 3
4
[171.5]
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
14-1/8
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-13/16
8-13/16
11-7/32
5-3/4
5-3/4
5-3/4
5-3/4
8-3/8
9-1/4
9-1/4
12-1/2
13-1/8
13-1/8
13-1/8
13-1/8
13-1/4
13-3/4
13-3/4
16-3/16
2-13/16
2-13/16
2-13/16
2-13/16
3-1/2
4-1/2
4-1/2

333.4
333.4
333.4
333.4
336.5
349.3
349.3
411.0
DIM A
IN. MM
DIM B
IN. MM
DIM C
IN. MM
DIM D
IN. MM
DIM E
IN. MM
DIM F
IN. MM
DIM G OCTAGON
IN. MM IN. MM
ALLOW 4 INCHES CLEARANCE FOR ACTUATOR REMOVAL.
ADD 1/8 INCH TO DIMENSION FOR MODELS WITH NEMA 4 ENCLOSURE.
ADD 1/4 INCH TO DIMENSION A FOR MODELS WITH NEMA 4 ENCLOSURE.
M7321
282.6
282.6
282.6
282.6
285.8
298.5
298.5
358.8
69.9
69.9
69.9
69.9
73.0
85.7
85.7
147.6
208.0
208.0
208.0
208.0
211.1
223.8
223.8
285.0
146.1
146.1
146.1
146.1
212.7
235.0
235.0
317.5
2-1/4
2-1/4
2-1/4
2-1/4
2-3/4
2-3/4
2-3/4
4-5/8
57.2
57.2
57.2
57.2
69.9
69.9
69.9
117.5
4-13/16
4-13/16
4-13/16
4-13/16
7-19/32
7-19/32
7-19/32

122.2
122.2
122.2
122.2
192.9
192.9
192.9

71.4
71.4
71.4
71.4
88.9
114.3
114.3

Fluid Actuator Accessories and Parts
Material Number Description Used With
133568/U Auxiliary Switch (Adjustable Valve Position) for V4055, V4062 or V9055 V4055; V4062; V9055
133569/U Replacement Pre-ignition Interlock (Proof of Closure) Switch for V4055D, E; V4062D or V9055D V4055; V4062; V9055
203422C/U 4-20 ma Adapter for V9055 V9055
7616BR/U Crank Arm assembly with clip for Damper Arm of V4055, V4062 or V9055 V4055; V4062; V9055
70-6910 837
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
V5055 Industrial Gas Valves
Safety shutoff valves used with V4055, V4062 and V9055 fluid
power actuators to control gas flow to commercial and industrial
burners.
• Use with natural or LP gases.
• Mount directly in gas supply line.
• Include 1/4 in. NPT upstream and downstream taps and plug.
• 4 in. models have only flanged connections.
• V5055 normally closed valves are rated for final shutoff service
safety shutoff.
• V5055A, C, D, E Valves are for On-Off service.
• V5055B Valve has a characterized guide and in combination with the
V4055, V4062, and V9055 Fluid Power Actuators, provides slowopening,
hi-lo-off, and modulating functions respectively.
• V5055C, E, F Valves have a double seal and are used with V4055D,
E Actuators to provide proof-of-closure switch and valve seal overtravel
interlock.
• V5055D, E, F Valves are for high pressure applications.
Operating Temperature Range: -40°F to +150°F; When used with
V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 –
-40°C to +52°C)
Approvals, Underwriters Laboratories Inc.: When used with V4055A,
B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ
Approvals, CSA: When used with V4055, V4062, and V5097: Certified
General listed File No. 158158, Class 3371 for USA and Canada
Approvals, Swiss RE: When used with the V4055A, G and V9055A:
Approved, Report Nos. 20698, 20835, 21172, and 24061
Used With: V9055; V4055; V4062
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055A1004/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1012/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055A1020/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055A1038/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1046/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1053/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1228/U 4 in. DN100 10200 cfh 288.8 m3/hr Flanged With V4055A, D or V4062
– 3 psi (20.7 kPa); With
V4055B or E – 5 psi
(340 mbar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055A1343/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
838 70-6910
Industrial Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055B1002/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1010/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055B1028/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055B1069/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1077/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1085/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055B1150/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062
– 3 psi (20.7 kPa); With
V4055B or E – 5 psi (340
mbar)
When used with
the V4055A, G and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1000/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1018/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1026/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055C1034/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1042/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
70-6910 839
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055C1059/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1109/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062
– 3 psi (20.7 kPa); With
V4055B or E – 5 psi (340
mbar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055C1182/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with
the V4055D, F and
V9055A: Approved,
Report Nos. 20698,
20835, 21172, and
24061
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055D1008/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1016/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1024/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1032/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1040/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1057/U 3 in. DN80 5230 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055D1065/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055B: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055E1005/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055E1013/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055E1021/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi
(1 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055E1039/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
840 70-6910
Industrial Gas Valves
Material
Number
Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Connection
Type
Maximum Operating
Differential Pressure
Approvals, Factory
Mutual
Comments Includes
V5055E1047/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055E1054/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055E1062/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
When used with the
V4055E: Approved,
Report Nos. 20698,
20835, 21172, and
24068
1/4 in. -18 NPT
upstream tap and
plug, 1/4 in. -18 NPT
downstream tap and
plug
V5055F1003/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
Meets Intent of
DIN Seat Leakage
Requirements
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055F1011/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
Meets Intent of
DIN Seat Leakage
Requirements
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
V5055F1037/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi
(1.6 bar)
Meets Intent of
DIN Seat Leakage
Requirements
1/4 in. -18 NPT
downstream tap and
plug, 1/4 in. -18 NPT
upstream tap and plug
Dimensions in inches (millimeters)
B
E
F
C
D
A 1
1/4 INCH NPT
DOWNSTREAM
TAP AND PLUG
1
KNOCKOUT
FOR1/2 INCH
CONDUIT (4)
OCTAGON
5 (127)
27/32 (21)
3-23/32 (95)
6-3/4 (172)
ALLOW 2 IN. (51 mm) CLEARANCE FOR ACTUATOR REMOVAL.
M27268A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
VALVE
SIZE
INCH
11-1/8
11-1/8
11-1/8
11-1/8
11-1/4
11-3/4
11-3/4
283
283
283
283
286
299
299
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
70
70
70
70
73
86
86
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-13/16
8-13/16
208
208
208
208
211
224
224
5-3/4
5-3/4
5-3/4
5-3/4
8-3/8
9-1/4
9-1/4
146
146
146
146
213
235
235
2-1/4
2-1/4
2-1/4
2-1/4
2-3/4
2-3/4
2-3/4
57
57
57
57
70
70
70
4-7/8
4-7/8
4-7/8
4-7/8
7-19/32
7-19/32
7-19/32
124
124
124
124
193
193
193
2-13/16
2-13/16
2-13/16
2-13/16
3-1/2
4-1/2
4-1/2
71
71
71
71
89
114
114
DIM A
IN. MM
DIM B
IN. MM
DIM C
IN. MM
DIM D
IN. MM
DIM E
IN. MM
DIM F
IN. MM
OCTAGON
IN. MM
1-9/32
(33)
1/4 INCH NPT UPSTREAM
TAP AND PLUG
70-6910 841
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
OCTAGON
H
6-3/4 (171)
1-9/32 (33)
A
B
C
D
DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J
E
G
F
J
OCTAGON
5 (127)
VALVE
SIZE
(IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4
283
283
283
283
298
298
298
2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8
70
70
70
70
86
86
86
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-5/16
8-5/16
208
208
208
208
211
211
211
8-1/4
8-1/4
8-1/4
8-1/4
11-3/4
11-3/4
11-3/4
210
210
210
210
298
298
298
IN. MM IN. MM IN. MM
62
62
62
62
91
91
91
5
5
5
5
8
8
8
127
127
127
127
203
203
203
58
58
58
58
113
113
113
23
23
23
23
38
38
38
100
100
100
100
165
165
165
71
71
71
71
114
114
114
3/4
1
1-1/4
1-1/2
2
2-1/2
3
M27581
1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL.
1
2-7/16
2-7/16
2-7/16
2-7/16
3-5/8
3-5/8
3-5/8
2-5/16
2-5/16
2-5/16
2-5/16
4-7/16
4-7/16
4-7/16
7/8
7/8
7/8
7/8
1-1/2
1-1/2
1-1/2
3-15/16
3-15/16
3-15/16
3-15/16
6-1/2
6-1/2
6-1/2
2-13/16
2-13/16
2-13/16
2-13/16
4-1/2
4-1/2
4-1/2
842 70-6910
Industrial Gas Valves
V5097 Integrated Valve Train
Safety shutoff valves used with V4055, V4062 and V9055 fluid
power actuators to control gas flow to commercial and industrial
burners.
• Use with natural or LP gases.
• Mount directly in gas supply line.
• Two Valve body types. Small body type for 3/4 in., 1 in., 1-1/4 in.,
1-1/2 in., 2 in. pipes. Large body types for 2 in., 2-1/2 in. and 3 in.
pipes.
• Seven pipe adapter sizes from 3/4 in. to 3 in. have NPT or BSP
threaded connections.
• Provides three 1/4 in. upstream and two 1/4 in. downstream tap and
plug.
• CE version provides an additional downstream tap and plug.
• Yellow SHUT indicator attached to the valve stem provides an
indication of the valve closed position.
• V5097A, C, D, E Valves are for on-off service.
• V5097B Valve has a characterized guide and in combination with the
V4055, V4062 and V9055 Fluid Power Actuators, provides slowopening,
HI-LO-OFF, and modulating functions, respectively.
• V5097C, E Valves have a double seal and are used with V4055D, E
Actuators to provide proof-of-closure switch and valve seal overtravel
interlock.
• Actuators to provide proof-of-closure switch and valve seal overtravel
interlock.
• V5097D, E Valves are for high pressure applications.
• Two valve body types (small and large) applicable to server pipe
size.
Operating Temperature Range: -40°F to +150°F; When used with
V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 –
-40°C to +52°C)
Approvals, Underwriters Laboratories Inc.: When used with V4055A,
B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ
Approvals, CSA: When used with V4055, V4062, and V5097: Certified
General listed File No. 158158, Class 3371 for USA and Canada
Approvals, Swiss RE: When used with the V4055A, G: Approved,
Report Nos. 20698, 20835, 21172, and 24061
Approvals, CE: CE #E3070 (Gastec)
Comments: Select Proper Pipe Adapter
Includes: Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT
downstream taps
Used With: V9055; V4055; V4062
Material Number Pipe Size
(inch)
Pipe Size
(DN)
Capacity
(cfh)
Capacity (m3/hr) Maximum Operating
Differential Pressure
Integrated Valve
Train Body Size
Approvals, Factory Mutual
V5097A1004/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Small body When used with the V4055A,
G: Approved, Report Nos.
20698, 20835, 21172, and
24061
V5097A1012/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055A,
G: Approved, Report Nos.
20698, 20835, 21172, and
24061
V5097B1002/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Small body When used with the V4055A,
G and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24061
V5097B1010/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055A,
G and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24061
V5097C1000/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Small body When used with the V4055D,
F and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24066
V5097C1018/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055D,
F and V9055A: Approved,
Report Nos. 20698, 20835,
21172, and 24066
V5097D1008/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi (1.6 bar)
Small body When used with the V4055B:
Approved, Report Nos.
20698, 20835, 21172, and
24068
V5097D1016/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055B:
Approved, Report Nos.
20698, 20835, 21172, and
24068
V5097E1005/U 3/4 in. or 1 in.
or 1 1/4 in. or
2 in.
DN20 or DN25
or DN32 or
DN50
665 cfh to
3620 cfh
18.8 to 102.5 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 25 psi (1.6 bar)
Small body When used with the V4055E:
Approved, Report Nos.
20698, 20835, 21172, and
24068
V5097E1013/U 2 in. or 2
1/2 in. or 3 in.
DN50 or DN65
or DN80
3620 cfh to
5230 cfh
102.5 to 148.0 m3/hr With V4055A, D or V4062
– 5 psi (340 mbar); With
V4055B or E – 15 psi (1 bar)
Large body When used with the V4055E:
Approved, Report Nos.
20698, 20835, 21172, and
24068
70-6910 843
Commercial/Industrial
Combustion Controls
Industrial Gas Valves
Dimensions in inches (millimeters)
6-3/4 (171)
1-9/32
(33)
A
B
C
D
DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J
E
G
H
F
J
OCTAGON
OCTAGON
5 (127)
VALVE
SIZE
(IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
11-1/8
11-1/8
11-1/8
11-1/8
11-3/4
11-3/4
11-3/4
283
283
283
283
298
298
298
2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
3-3/8
3-3/8
70
70
70
70
86
86
86
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-5/16
8-5/16
208
208
208
208
211
211
211
8-1/4
8-1/4
8-1/4
8-1/4
11-3/4
11-3/4
11-3/4
210
210
210
210
298
298
298
IN. MM IN. MM IN. MM
62
62
62
62
91
91
91
5
5
5
5
8
8
8
127
127
127
127
203
203
203
58
58
58
58
113
113
113
23
23
23
23
38
38
38
100
100
100
100
165
165
165
71
71
71
71
114
114
114
3/4
1
1-1/4
1-1/2
2
2-1/2
3
M11682B
1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL.
1
2-7/16
2-7/16
2-7/16
2-7/16
3-5/8
3-5/8
3-5/8
2-5/16
2-5/16
2-5/16
2-5/16
4-7/16
4-7/16
4-7/16
7/8
7/8
7/8
7/8
1-1/2
1-1/2
1-1/2
3-15/16
3-15/16
3-15/16
3-15/16
6-1/2
6-1/2
6-1/2
2-13/16
2-13/16
2-13/16
2-13/16
4-1/2
4-1/2
4-1/2
844 70-6910
Industrial Gas Valves
Integrated Valve Train Pipe Adapters
Material Number Pipe Size
(inch)
Pipe Size
(DN)
Connection
Type
Integrated Valve
Train Body Size
Description Used With
32000109-001/U 3/4 in. DN20 NPT Small body 3/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-002/U 1 in. DN25 NPT Small body 1 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32000109-003/U 1 1/4 in. DN32 NPT Small body 1 1/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-004/U 1 1/2 in. DN40 NPT Small body 1 1/2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-005/U 2 in. DN50 NPT Small body 2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32000109-006/U 3/4 in. DN20 BSP Small body 3/4 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32000109-007/U 1 in. DN25 BSP Small body 1 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-001/U 2 in. DN50 NPT Large body 2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-002/U 2 1/2 in. DN65 NPT Large body 2 1/2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32001605-003/U 3 in. DN80 NPT Large body 3 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-004/U 2 in. DN50 BSP Large body 2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
32001605-005/U 2 1/2 in. DN65 BSP Large body 2 1/2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required
for Valve Train Assembly.
V5097; V4297;
V5197
32001605-006/U 3 in. DN80 BSP Large body 3 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for
Valve Train Assembly.
V5097; V4297;
V5197
V5055/5097 Replacement Parts or Accessories
Material Number Description Used With
133392A/U O-Ring Assembly for 2 in., 2 1/2 in., and 3 in. V5055 valves V5055/V5097 valves
133393A/U O-Ring Assembly for 1 in., 1 1/4 in., and 1 1/2 in. V5055 valves V5055/V5097 valves
133398AA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055A valves V5055/V5097 valves
133398BA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055B valves V5055/V5097 valves
133398CA/U Replacement Bonnet Assembly, with 137253A replacement Seal Assembly for small body (3/4, 1, 1 1/2 in.)
V5055/V5097C.
V5055/V5097 valves
133417AA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055A valves V5055/V5097 valves
133417BA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055B valves V5055/V5097 valves
133417CA/U Bonnet Assembly for 2, 2 1/2, or 3 in. V5055C or V5097C valves V5055C/V5097C valves
137253A/U Replacement seal assembly. For 4 inch V5055. V5055
4074EYE/U Bag assembly for V5097 (large body) includes 6 ea bolts, nuts and washers. Large Body V5097
4074EYF/U Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. Small Body V5097
4074EYK/U Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. Small Body V5097
4074EYL/U Bag assembly for V5097 (large body) includes (2) O-rings, (1) grease capsule. Large Body V5097
70-6910 845
Commercial/Industrial
Combustion Controls
Pilot Gas Valves
V4046C; V8046C Pilot Gas Valves
Dimensions in inches (millimeters)
1-3/16
(30)
DIM. A
1-3/8
(35)
1-5/8
(41)
1-3/4 (45)
2-5/8 (67)
1-3/4 (45)
DIM. B
1-1/4 (32)
BASIC
CENTER
45
BASIC
CENTER
8-32 x 1/4 IN.(6)
DEEP (2)
1/2-14
NPSM
36 IN. (915)
LEADS (2)
THREAD
SIZE
MODEL
V4046C,
V8046C
BODY
SIZE
THREAD
SIZE
SMALL
SMALL
LARGE
LARGE
1/8-27 NPT
1/4-18 NPT
1/4-18 NPT
3/8-18 NPT
5/16
3/8
1/2
1/2
8
10
13
13
2-3/4
3
3-1/4
3-1/4
70
76
83
83
DIM. A DIM. B
IN MM IN MM
M16595A
Provide on-off control of natural, LP and manufactured gases to
pilot burners in industrial and commercial applications.
• Magnetically operated, normally closed.
• Provide instantaneous action when energized.
• On power failure, valve closes in one second maximum.
• Use in any position, directly in pipe line or on support bracket.
• Replace the solenoid coil without removing the valve body from the
piping connections.
• Straight-through valve pattern.
• Available in line voltage or low voltage models.
Type of Fuel: Air; natural; manufactured; LP
Body Pattern: Straight-through
Valve Opening Time: 1 sec max
Valve Closing Time: 1 sec max
Mounting: Directly in pipe or on support bracket
Materials: Body – Aluminum
Power Consumption: 8 W
Operating Temperature Range: -40°F to +125°F (-40°C to +52°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No. MH1639,
V3, S3 - Guide No. YIOZ
Approvals, CSA: Certificate No. 158158-2500006058, Guide No.
C3371-03, 83
Approvals, Factory Mutual: Approved: Report No. 17450
Pressure Ratings (psi): 10 psi
Pressure Ratings (kPa): 68.9 kPa
Material Number Pipe Size (inch) Capacity (cfh) Capacity (m3/hr) Voltage Frequency Electrical Connections Approvals,
Swiss RE
V4046C1005/U 1/8 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1021/U 1/4 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1047/U 1/4 in. 55 cfh 1.56 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1054/U 3/8 in. 67 cfh 1.90 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable
V4046C1120/U 3/8 in. 67 cfh 1.90 m3/hr 120 Vac 60 Hz Two 10 ft. leadwires and 1/2 in. conduit bushing Acceptable
V8046C1006/U 1/8 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
V8046C1014/U 1/4 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
V8046C1022/U 1/4 in. 55 cfh 1.56 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
V8046C1030/U 3/8 in. 67 cfh 1.90 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing
846 70-6910
Solenoid Gas Valves
V4295; V8295 Solenoid Gas Valves
V4295A/V8295A normally closed and V4295S/V8295S normally
open (vent) solenoid gas valves, are suitable for furnaces, ovens,
atmospheric burners, commercial water heaters, rooftop make-up
air units, power burners, and commercial/industrial boilers.
• V8295A, S are used with 24 Vac controllers.
• V4295A, S are used with 120 Vac controllers.
• Positive close off of gas flow when de-energized.
• High valve spring force allows up to 0.7 psi back pressure at valve
seat.
• No inlet pressure influence at valve seat.
• Inlet pressure changes do not affect ability to close valve.
• Low operating noise.
• Low rush-in current.
• Upstream and downstream taps allows tapping and testing pressure
points.
Type of Fuel: Air; natural; manufactured; mixed; LP
Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT
Body Pattern: Straight-through, non-offset
Valve Opening Time:less than 1 sec
Valve Closing Time: less than 1 sec
Mounting: Vertical to 90 degrees from vertical
Materials: Body – Die-cast aluminum
Frequency: 50 Hz; 60 Hz
Electrical Connections: Screw terminals
Operating Temperature Range: -40°F to +140°F (-40°C to +60°C)
Approvals, Swiss RE: Acceptable
Approvals, Control Safety Devices: Acceptable
Material
Number
Pipe
Size
(inch)
Pipe
Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Voltage Approximate,
Dimensions
Current
Ratings
Pressure
Ratings
(psi)
Pressure
Ratings
(kPa)
Approvals,
Underwriters
Laboratories
Inc.
Approvals,
CSA
Approvals,
Factory
Mutual
V4295A1015 1/2 in. DN15 250 cfh 7.1 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1023 3/4 in. DN20 645 cfh 18.3 m3/hr 120 Vac 5 1/4 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(133 mm high x 87 mm
wide x 70 mm deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1031 1 in. DN25 790 cfh 22.4 m3/hr 120 Vac 5 1/4 in. high x
3 15/16 in. wide x 3 in.
deep (133 mm high x
100 mm wide x 76 mm
deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1049 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 120 Vac 8 in. high x 5 15/16 in.
wide x 4 3/8 in. deep
(203 mm high x 151 mm
wide x 111 mm deep)
0.34
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1056 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 120 Vac 8 3/8 in. high x
5 15/16 in. wide x
4 3/8 in. deep (213 mm
high x 151 mm wide x
111 mm deep)
0.3 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1064 2 in. DN50 3465 cfh 98.1 m3/hr 120 Vac 8 3/8 in. high x
6 11/16 in. wide x
5 3/8 in. deep (213 mm
high x 170 mm wide x
137 mm deep)
0.525
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1072 2 1/2 in. DN65 5070 cfh 143.5 m3/
hr
120 Vac 12 3/4 in. high x
9 1/2 in wide x 7 7/8 in.
deep (324 mm high x
241 mm wide x 200 mm
deep)
0.575
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1080 3 in. DN80 6100 cfh 172.7 m3/
hr
120 Vac 12 3/4 in. high x
9 1/2 in wide x 7 7/8 in.
deep (324 mm high x
241 mm wide x 200 mm
deep)
0.675
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
70-6910 847
Commercial/Industrial
Combustion Controls
Solenoid Gas Valves
Material
Number
Pipe
Size
(inch)
Pipe
Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Voltage Approximate,
Dimensions
Current
Ratings
Pressure
Ratings
(psi)
Pressure
Ratings
(kPa)
Approvals,
Underwriters
Laboratories
Inc.
Approvals,
CSA
Approvals,
Factory
Mutual
V4295A1098 3/8 in. 210 cfh 5.9 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.16
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1106 1/2 in. DN15 290 cfh 8.2 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.16
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1114 3/4 in. DN20 610 cfh 17.3 m3/hr 120 Vac 3 3/16 in. high x
3 7/16 in. wide x
2 3/4 in. deep (81 mm
high x 87 mm wide x
70 mm deep)
0.2 max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1122 1 in. DN25 825 cfh 23.4 m3/hr 120 Vac 6 5/16 in. high x
3 15/16 in. wide x 3 in.
deep (160 mm high x
100 mm wide x 76 mm
deep)
0.2 max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1130 1 1/4 in. DN32 1950 cfh 55.2 m3/hr 120 Vac 8 9/16 in. high x
5 15/16 in. wide x
4 3/8 in. deep (217 mm
high x 151 mm wide x
111 mm deep)
0.55
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1148/U 1 1/2 in. DN40 2270 cfh 64.3 m3/hr 120 Vac 8 9/16 in. high x
5 15/16 in. wide x
4 3/8 in. deep (217 mm
high x 151 mm wide x
111 mm deep)
0.55
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295A1155 2 in. DN50 3740 cfh 105.9 m3/
hr
120 Vac 9 3/16 in. high x
6 11/16 in. wide x
5 3/8 in. deep (233 mm
high x 170 mm wide x
137 mm deep)
0.54
max
amps
at rated
Vac/Hz
5 psi 34.5 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03,
04, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295S1005 3/4 in. DN20 350 cfh 9.9 m3/hr 120 Vac 5 1/2 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(140 mm high x 87 mm
wide x 70 mm deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295S1013 1 in. DN25 420 cfh 11.9 m3/hr 120 Vac 5 1/2 in. high x
3 15/16 in. wide x 3 in.
deep (140 mm high x
100 mm wide x 76 mm
deep)
0.16
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 83
Approved:
Report No.
J.I.OD6A2.
AF
V4295S1021 1 1/4 in. DN32 1100 cfh 31.1 m3/hr 120 Vac 8 3/4 in. high x
5 15/16 in. wide x
4 3/8 in. deep (222 mm
high x 151 mm wide x
111 mm deep)
0.34
max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Listed: File No.
MH18476, V1,
S1 - Guide No.
YIOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 83
Approved:
Report No.
J.I.OD6A2.
AF
V8295A1016 1/2 in. DN15 250 cfh 7.1 m3/hr 24 Vac 4 7/16 in. high x 2 7/8 in.
wide x 2 3/16 deep
(113 mm high x 73 mm
wide x 56 mm deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1024 3/4 in. DN20 645 cfh 18.3 m3/hr 24 Vac 5 1/4 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(133 mm high x 87 mm
wide x 70 mm deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1032 1 in. DN25 790 cfh 22.4 m3/hr 24 Vac 5 1/4 in. high x
3 15/16 in. wide x 3 in.
deep (133 mm high x
100 mm wide x 76 mm
deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
848 70-6910
Solenoid Gas Valves
Material
Number
Pipe
Size
(inch)
Pipe
Size
(DN)
Capacity
(cfh)
Capacity
(m3/hr)
Voltage Approximate,
Dimensions
Current
Ratings
Pressure
Ratings
(psi)
Pressure
Ratings
(kPa)
Approvals,
Underwriters
Laboratories
Inc.
Approvals,
CSA
Approvals,
Factory
Mutual
V8295A1040 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 24 Vac 8 in. high x 5 15/16 in.
wide x 4 3/8 in. deep
(203 mm high x 151 mm
wide x 111 mm deep)
1.6 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1057 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 24 Vac 8 3/8 in. high x
5 15/16 in. wide x
4 3/8 in. deep (213 mm
high x 151 mm wide x
111 mm deep)
1.7 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295A1065 2 in. DN50 3465 cfh 98.1 m3/hr 24 Vac 8 3/8 in. high x
6 11/16 in. wide x
5 3/8 in. deep (213 mm
high x 170 mm wide x
137 mm deep)
2.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
V8295S1006 3/4 in. DN20 350 cfh 9.9 m3/hr 24 Vac 5 1/2 in. high x 3 7/16 in.
wide x 2 3/4 in. deep
(140 mm high x 87 mm
wide x 70 mm deep)
0.8 max
amps
at rated
Vac/Hz
2 psi 13.8 kPa Component
Recognized;
File No. YLOZ
Certificate
No. 158158-
1154280,
Guide No.
C3371-03, 85
Approved:
3/8 in.,
1/2 in.,
3/4 in. only
70-6910 849
Commercial/Industrial
Combustion Controls
Solenoid Gas Valves
V4297A Solenoid Safety Shut-off Valve for IVT
V4297A are normally closed solenoid gas valve. Suitable for
use on furnaces, ovens, atmospheric burners, commercial
water heaters, rooftop make-up air units, power burners, and
commercial/industrial boilers.
• V4297A are used with 120 Vac controllers.
• Positive close off of gas flow when de-energized.
• High valve spring force allows up to 0.7 psi back pressure at valve
seat.
• No inlet pressure influence at valve seat.
• Inlet pressure changes do not affect ability to close valve.
• Low operating noise.
• Low rush-in current.
• Upstream and downstream taps allows tapping and testing pressure
points.
• For use with the Integrated Valve Train.
• Accepts C6097 Pressure Switch mounted directly to flange
(upstream pressure tap only).
Type of Fuel: Air; natural; manufactured; mixed; LP
Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT
Body Pattern: Straight-through, non-offset
Valve Opening Time: less than 1 sec
Valve Closing Time: less than 1 sec
Flanges: Required, Order Separately
Mounting: Directly bolted to Integrated Valve Train Components
Materials: Body – Die-cast aluminum
Voltage: 110 Vac; 120 Vac
Frequency: 50 Hz; 60 Hz
Electrical Connections: Screw terminals
Operating Temperature Range: -40°F to +130°F (-40°C to +54°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No.
MH18476, V1, S1 - Guide No. YIOZ
Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371-
03, 04, 83
Approvals, Swiss RE: Acceptable
Pressure Ratings (psi): 5 psi
Pressure Ratings (kPa): 34.5 kPa
Replacement Parts:
4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea
bolts, nuts and washers.
4074EYK/U – Bag assembly for V5097 (small body) includes (2)
O-rings, (1) grease capsule.
Dimensions in inches (millimeters)
2 (51)
5 (127)
5-1/2 (140)
5-5/8 (143)
3-3/4 (95)
1-1/2
(38)
2-3/4
(70)
1/2 (13)
5-3/4 (147)
6-1/4
(159)
10-1/4
(260)
M23226
TOP VIEW
Material
Number
Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity
(m3/hr)
Approximate, Dimensions Integrated Valve
Train Body Size
Current Ratings
V4297A1005 3/4 in. to 1 1/4 in. DN20 or DN25 or
DN32
650 cfh; 700 cfh;
780 cfh
19.8 m3/hr 9 in. high x 5 3/4 in. wide x 5 5/8 in.
deep (229 mm high x 147 mm wide x
143 mm deep)
Small body, small
flow
0.2 max amps at
rated Vac/Hz
V4297A1013 3/4 in. to 2 in. DN20 or DN25 or
DN32 or DN40 or
DN50
1190 cfh; 1460 cfh;
2260 cfh; 2735 cfh;
3060 cfh
10 1/4 in. high x 5 3/4 in. wide x 5 5/8 in.
deep (260 mm high x 147 mm wide x
143 mm deep)
Small body, large
flow
0.5 max amps at
rated Vac/Hz
850 70-6910
Solenoid Gas Valves
V4297S Normally Open Vent Valve for IVT
V4297S are normally open (vent) solenoid gas valves. Suitable
for use on furnaces, ovens, atmospheric burners, commercial
water heaters, rooftop make-up air units, power burners, and
commercial/industrial boilers.
• V4297S is used with 120 Vac controllers.
• Low operating noise.
• Low rush-in current.
• Upstream and downstream taps allows tapping and testing pressure
points.
• For use with the Integrated Valve Train.
Type of Fuel: Air; natural; manufactured; mixed; LP
Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT
Body Pattern: Straight-through, non-offset
Valve Opening Time: less than 1 sec
Valve Closing Time: less than 1 sec
Flanges: Required for Stand Alone
Mounting: Directly bolted to Integrated Valve Train Components
Materials: Body – Die-cast aluminum
Voltage: 110 Vac; 120 Vac
Frequency: 50 Hz; 60 Hz
Electrical Connections: Screw terminals
Operating Temperature Range: -40°F to +145°F (-40°C to +63°C)
Approvals, Underwriters Laboratories Inc.: Listed: File No.
MH18476, V1, S1 - Guide No. YIOZ
Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371-
03, 04, 83
Approvals, Swiss RE: Acceptable
Pressure Ratings (psi): 5 psi
Pressure Ratings (kPa): 34.5 kPa
Replacement Parts:
4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea
bolts, nuts and washers.
4074EYK/U – Bag assembly for V5097 (small body) includes (2)
O-rings, (1) grease capsule.
4074EYL/U – Bag assembly for V5097 (large body) includes (2)
O-rings, (1) grease capsule.
Dimensions in inches (millimeters)
2-5/8
3 (69)
(76)
1-1/2
(38)
5/16
(8)
3/4 (18)
3/4 (18)
2
(51)
5 (127) 8 (203)
1-1/2
3/16 (5) (32)
M23252
2
(51)
12-3/8
(314)
3-1/8
(79)
1/2 (13) 4-1/2 (114)
5/8
(16)
1 (25)
1/2
(13)
1-1/4 IN.
NPT
1/2 (13)
(3 HOLES)
3/8 (10)
(3 HOLES)
2-5/8
(69)
9-1/2
(241)
3-1/8
(79)
3/8
(10)
1/2
(13)
1/2
(13)
7/8
(22)
4-1/8
(105)
3-1/8 (79) 5 (127)
3/8
(10)
1/2
(13)
1-1/4
(32)
2 (51)
1-1/2
(32)
3/16 (5)
1-15/16
(49)
2-3/8
(60)
M23251
2 (51)
1 IN.
NPT
Material Number Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions Integrated Valve Train
Body Size
Current Ratings
V4297S1003 DN25 714 cfh 20.2 m3/hr 9 1/2 in. high x 3 1/8 in. wide x 5 in.
deep (241 mm high x 79 mm wide x
127 mm deep)
Small body 0.2 max amps at rated
Vac/Hz
V4297S1011 DN32 1115 cfh 31.6 m3/hr 12 3/8 in. high x 5 in. wide x 8 in.
deep (314 mm high x 127 mm wide x
203 mm deep)
Large body 0.34 max amps at
rated Vac/Hz
70-6910 851
Commercial/Industrial
Combustion Controls
Servo Regulated Gas Valves
V4730C; V4734C; V8730C Gas/Air Servo Regulated Gas Valves
Body Pattern: Straight flange
Valve Opening Time: Dead time maximum: 1 second; First valve –
< 1 second; Second valve – reaches 50% of the adjustable outlet
pressure within 5 seconds
Materials: Body: Aluminum alloy, die-cast
Frequency: 50 Hz; 60 Hz
Ambient Temperature Range: 5°F to 140°F (-15°C to +60°C)
Approvals, Underwriters Laboratories Inc.: File No. MH18476
Approvals, CSA: File: Certificate No: 158158-1227192
Approvals, Others: Gas Appliance Directive: 90.396/EEC, PIN:
0063AT1198, Low Voltage Directive: 73/23/EEC, Electro Magnetic
Compatibility Directive: 89/336/EEC
Maximum Safe Operating Pressure (psi): 0.5 psi (CSA approved),
1.45 psi for 120V; 1 psi for 24V (UL approved)
Maximum Operating Pressure (mbar): 200 mbar (UL approved)
100 mbar for 120V; 69 mbar for 24V (UL approved), 35 mbar (CSA
approved)
Comments: The minimum load for which the system can be used is
14-17% of the reference load, which equals a minimum pressure
differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas
control.
Coil Insulation Solenoid Valves: Class H insulation system
Current Ratings: V1 Current Rating – 0.16A; V2 Current Rating –
0.16A; V1 + V2 Current Rating – 0.32A
Material Number Pipe Size
(inch)
Capacity (kW) Capacity (kBtuh) Voltage Electrical
Connections
Pipe Connection Includes Max. Capacity
with Strainer (cfh)
V4730C1006-0000 1/2 in. Natural Gas 0.64
sp.gr –
22-150 KW
Natural Gas 0.64
sp.gr – 73-
512 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-001 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 221
cfh
V4730C1014-0000 3/4 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-002 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V4730C1022-0000 1 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-003 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V4730C1030-0000 1 1/4 in. Natural Gas
0.64 sp.gr –
55-382 KW
when used with
VMU335,
71-500KW
Natural Gas 0.64
sp.gr – 185-
1300 kBtuh
when used with
VMU335,245-
1710 kBtuh
120 Vac
(+10%, -15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-004 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1300
cfh
852 70-6910
Servo Regulated Gas Valves
Material Number Pipe Size
(inch)
Capacity (kW) Capacity (kBtuh) Voltage Electrical
Connections
Pipe Connection Includes Max. Capacity
with Strainer (cfh)
V4734C1002-0000 1 1/4 in. Natural Gas
0.64 sp.gr –
97-680 KW
when used with
VMU680
Natural Gas 0.64
sp.gr – 326-
2287 kBtuh
when used with
VMU680
120 Vac
(+10%, -15%)
Mesh screen filter and
32006652-004 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
V8730C1007-0000 1/2 in. Natural Gas 0.64
sp.gr –
22-150 KW
Natural Gas 0.64
sp.gr – 73-
512 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-001 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 221
cfh
V8730C1015-0000 3/4 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-002 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V8730C1023-0000 1 in. Natural Gas 0.64
sp.gr –
43-300 KW
Natural Gas 0.64
sp.gr – 146-
1024 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-003 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1024
cfh
V8730C1031-0000 1 1/4 in. Natural Gas
0.64 sp.gr –
55-382 KW
when used with
VMU335,
71-500 KW
Natural Gas 0.64
sp.gr – 185-
1300 kBtuh
when used with
VMU335,
245-1710 kBtuh
24 Vac (+10%,
-15%)
Standard DIN
plug connector
with 36 in.
(914 mm)
leadwires,
included.
1/8 in. (3mm) NPT
pressure taps at inlet
and outlet flanges.
Six flange pressure
taps connections
are provided at the
main body to mount
either a pressure
switch (low or high)
or a Valve Proving
System (VPS).
Mesh screen filter and
32006652-004 Flange
kit. (Kit includes 1
pipe adapter, 1 O-ring,
4 mounting screws,
1 DIN connector and
wiring harness kit.)
Nat. Gas (Delta P=
1 in. w.c.) – 1300
cfh
70-6910 853
Commercial/Industrial
Combustion Controls
Servo Regulated Gas Valves
Dimensions in inches (millimeters)
M22414
6-1/8 (156)
1-27/32
(48)
4-7/32
(107)
5-1/4 (133)
7-5/16
(240)
2 (51)
2-1/32
(52)
1-11/16 3-7/8 (98)
(43)
PRESSURE
SWITCH
OPTIONAL
VALVE
POSITION
INDICATOR
LAMPS
M22415
6-1/8 (156)
1-27/32
(48)
4-7/32
(107)
5-1/4 (133)
6-1/2
(166)
2 (51)
2-1/32
(52)
1-11/16 3-7/8 (98)
(43)
OPTIONAL
PRESSURE
SWITCH
VALVE
POSITION
INDICATOR
LAMPS
M16865
6-9/16 (166)
1-27/32
(48)
4-7/32
(107)
5-1/4 (133)
7-5/16
(190)
2 (51)
2-1/32
(52)
1-11/16 3-7/8 (98)
(43)
OPTIONAL
PRESSURE
SWITCH
VALVE
POSITION
INDICATOR
LAMPS
M16864
6-9/16 (166)
1-7/8
(48)
4-5/16
(109)
5-11/32 (136)
8-15/32
(215)
2-1/4 (57)
3
(76)
1-3/4 4-1/32 (102)
(44)
OPTIONAL
PRESSURE
SWITCH
V4730C; V4734C; V8730C Accessories and Parts
Material Number Description
50002653-001/U Manual Shut-Off Valve Kit (1 in. NPT or smaller valves)
854 70-6910
Venturi Mixing Unit
Venturi Mixing Unit
Dimensions in inches (millimeters)
M22417D
8-19/32 (218)
7-7/8 (200) LG
5-1/2 (140) SM
9-9/32 DIA.
(236 DIA.)
LG
6-1/4 DIA.
(159 DIA.)
SM
1
2
1
2
1 LG (LARGE) IS VENTURI MIXING UNIT VMU500.
2 SM (SMALL) ARE VENTURI MIXING UNITS VMU150/300/335.
The venturi mixing unit (VMU), combined with the V4730C/
V8730C gas valves and specific direct current (dc) fan, has been
developed for modulating premix appliances like gas burners and
gas boilers.
• All adjustment and test points are accessible from one side.
• Has a wide modulation band (14 to 100% of the boiler load).
• Flexible mounting positions of gas control to venturi manifold and
venturi manifold to fan.
• Two stainless steel sensing tubes are provided for use with or
without manual safety shutoff valve.
Materials: Housing: Aluminum, Venturi: Statically dissipative statcon
PF, Seals: Rubber (NBR).
Ambient Temperature Range: 32°F to 212°F (0°C to 100°C)
Approvals, Underwriters Laboratories Inc.: File No. MH18476
Approvals, CSA: File: Certificate No: 158158-1227192
Pipe Connection: Four M5 screws and a rubber O-ring are provided
with the venturi to assemble it to the V4730C/V8730C gas valve. The
stainless steel tube provided with the venturi has to be connected
between the venturi inlet (connection provided) and the gas valve
regulator. Longer sensing tube for use with manual safety shutoff
valve (KTTBA002). Shorter sensing tube for use without manual
safety shutoff valve (KTTBA001).
Current Ratings: V1 Current Rating – 0.16A; V2 Current Rating –
0.16A; V1 + V2 Current Rating – 0.32A
Material Number Body Pattern Maximum Safe Operating
Pressure (psi)
Maximum Operating
Pressure (mbar)
Comments Reference Load
VMU150A1011 Straight flange 2.9 psi (UL approved),
1/2 psi (CSA approved)
200 mbar (UL approved),
35 mbar (CSA approved)
Pressure Drop: Approximately 3.2 in. wc (800 Pa)
across the venturi at reference load. The minimum
load for which the system can be used is 14-17%
of the reference load, which equals a minimum
pressure differential of 0.2 in. wc (50 Pa) of the
1:1 venturi/servo regulator gas control.
150 kW (512,000 Btuh)
VMU185A1084 1/2 psi (CSA approved;
2.9 psi (UL approved)
35 mbar (CSA approved),
200 mbar (UL approved)
Pressure Drop: Approximately 3.2 in. wc (800 Pa)
across the venturi at reference load. The minimum
load for which the system can be used is 14-17%
of the reference load, which equals a minimum
pressure differential of 0.2 in. wc (50 Pa) of the
1:1 venturi/servo regulator gas control.
185 kW (632,000 Btuh)
VMU300A1046 Straight flange 2.9 psi (UL approved),
1/2 psi (CSA approved)
200 mbar (UL approved),
35 mbar (CSA approved)
Pressure Drop: Approximately 3.2 in. wc (800 Pa)
across the venturi at reference load. The minimum
load for which the system can be used is 14-17%
of the reference load, which equals a minimum
pressure differential of 0.2 in. wc (50 Pa) of the
1:1 venturi/servo regulator gas control.
300 kW (1,024,000 Btuh)
VMU335A1018 Straight flange 2.9 psi (UL approved),
1/2 psi (CSA approved)
200 mbar (UL approved),
35 mbar (CSA approved)
Pressure Drop: Approximately 3.2 in. wc (800 Pa)
across the venturi at reference load. The minimum
load for which the system can be used is 14-17%
of the reference load, which equals a minimum
pressure differential of 0.2 in. wc (50 Pa) of the
1:1 venturi/servo regulator gas control.
335 kW (1,143,000 Btuh)
70-6910 855
Commercial/Industrial
Combustion Controls
Pressure Switches
C437D, E 2000 Series Gas Pressure Switches
Dimensions in inches (millimeters)
1-5/16
(33.3)
1
(25.4)
6-1/2
(165.1)
7-3/4
(196.9)
2 (50.8)
45 45
7-3/8 (187.3)
1/8–27 NPT 1/2–14 NPT TAPPED FOR
1/2 IN. CONDUIT
1
2
137755 MOUNTING BRACKET (2), IN 4074BWK BAG ASSEMBLY – OPTIONAL.
VENT TAPPING. REMOVE DUST-SEAL LABEL BEFORE MOUNTING. M27582
6-1/4 (159)
5/16 (8) (4)
5/8
(15.9)
(4)
7-11/16
DIA.
(195.3)
1/8
(3.2)
3-7/16 (87.3)
1
2
C437D, E Series 2000 Gas Pressure Switches are pressureactuated
devices used in industrial gas systems for safety
shutoff. Series 2000 models have snap acting MicroSwitch™ snap
switches to open a circuit on pressure rise or drop.
• C437 models have direct- and reverse-acting SPST (non-mercury)
switching.
• Models intended for lockout applications must be manually reset
before resuming operation.
• Models with pressure range of 1 to 26 in. wc (0.25 to 6.5 kPa)
compensate for momentary surges in gas pressure with a restrictive
orifice in inlet pressure channel.
• Impede tampering and provide dust-resistant operation with
enclosed setting.
• Increase strength of control diaphragm with Buna N fiber-reinforced
material.
• Two Buna-N fiber-reinforced seal-off diaphragms for added reliability.
• Clear glass cover allows observation of interior mechanism to aid in
setting and checkout.
Application: Industrial gas system applications for safety shutoff,
pressure control, or differential-pressure control.
Switch Operation: Manual Reset
Sensor Element: BUNA N Diaphragm
Materials: Case: Die-cast aluminum
Approximate, Dimensions: 7 3/4 in. high x 6 1/4 in. wide x 3 7/16 in.
deep (197 mm high x 159 mm wide x 87 mm deep)
Operating Temperature Range: 32°F to 125°F (0°C to 52°C)
Temperature Ratings: 125°F - Maximum Ambient (52°C - Maximum
Ambient)
Electrical Connections: Screw terminals
Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A
resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive
Pipe Connection: Main or High Pressure – 1/2 in. NPT internal thread;
Vent or Low pressure – 1/8 in. NPT internal thread
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP2168,
Guide No. MFHX
Approvals, CSA: Certified: File No. LR1620, Guide No. 380-W-1.16
Approvals, Factory Mutual: Approved: Report No. 22018, 24127,
J.I.IF4A3.AF
Approvals, Swiss RE: Acceptable
Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure
Range (psi)
Differential Pressure
Range (kPa)
Differential Type Switching Action
C437D2003/U 1 to 26 in. wc; 5.0 psi -
Maximum Sustained
0.5 to 7.0 kPa; 34.5 kPa
- Maximum Sustained
1 3/4 in. wc 0.44 kPa Subtractive SPST, break on rise,
non-mercury
C437D2011/U 1/2 to 5 psi; 15.0 psi -
Maximum Sustained
3.0 to 35 kPa; 103.4 kPa
- Maximum Sustained
1/2 psi 3.45 kPa Subtractive SPST, break on rise,
non-mercury
C437D2029/U 1 to 10 psi; 30.0 psi -
Maximum Sustained
5.0 to 70.0 kPa;
206.8 kPa - Maximum
Sustained
1 psi 6.89 kPa Subtractive SPST, break on rise,
non-mercury
C437E2002/U 1 to 26 in. wc; 5.0 psi -
Maximum Sustained
0.5 to 7.0 kPa; 34.5 kPa
- Maximum Sustained
1 3/4 in. wc 0.44 kPa Additive SPST, Break on Fall,
non-mercury
C437E2010/U 1/2 to 5 psi; 15.0 psi -
Maximum Sustained
3.0 to 35 kPa; 103.4 kPa
- Maximum Sustained
1/2 psi 3.45 kPa Additive SPST, Break on Fall,
non-mercury
C437E2028/U 1 to 10 psi; 30.0 psi -
Maximum Sustained
5.0 to 70.0 kPa;
206.8 kPa - Maximum
Sustained
1 psi 6.89 kPa Additive SPST, Break on Fall,
non-mercury
C437E2036/U 0.5 to 5.5 in. wc; 3.0 psi
- Maximum Sustained
0.1 to 1.4 kPa; 20.7 kPa
- Maximum Sustained
0.25 in. wc 0.06 kPa Additive SPST, Break on Fall,
non-mercury
856 70-6910
Pressure Switches
C6097 Pressure Switch
Dimensions in inches (millimeters)
27/32
(22)
HOLE
HOUSING
GAS CONNECTION
1/4 NPT WITH DUST SEAL
2-1/4
(57)
3-3/16
(81)
1-17/32
(90)
2-21/32 (68) 2-21/32 (68)
31/32
(25)
25/32
(21)
1-3/32 (28) 15/32 (12)
13/32
(11)
2-23/32 (69) 2-23/32 (69)
1-3/4 (45)
2-13/32
(61)
ATMOSPHERIC
PRESSURE
REFERENCE PORT
OR DIFFERENTIAL
CONNECTION
1/8 NPT
INDICATOR
M29773
1 2 3
P
NO
NC
COM
TERMINAL DIAGRAM
Pressure Switches are safety devices used in positive-pressure
or differential-pressure systems to sense gas or air pressure
systems.
• For use with natural gas, liquid propane (LP) gas, or air.
• Diaphragm-actuated safety-limit switch.
• Switch can be wired to turn on alarm.
• C6097A models break control circuit at setpoint on pressure fall.
• C6097B models break control circuit at setpoint on pressure rise.
• Lockout with manual reset and recycle options.
• Lockout models have external manual reset button.
• Removable transparent cover protects scaleplate and adjusting knob.
• Pipe tappings allow selection of positive pressure (air only) or
venting connections (NPT mount only).
• 1/4 in. NPT or flange mount models for direct mounting to Honeywell
Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in. wc or 1.5 to 7 psi.
• Surge orifice.
• Integral vent limiter on all models.
Application: Safety devices used in positive-pressure or differentialpressure
systems to sense gas or air pressure changes
Operating Temperature Range: -40°F to +140°F (-40°C to +60°C)
Electrical Connections: Screw terminals
Electrical Ratings: Ignition Transformer: 540 VA, Pilot Valve: 50 VA.
Main Valve: 400 VA with 2-1/2 times inrush
Contact Ratings: 120 Vac Switch Contact – 3.0 AFL, 18.0 ALR, 5.0 A
resistive; 240 Vac Switch Contact – 3.0 AFL, 18.0 ALR, 5.0 A resistive
Approvals, Underwriters Laboratories Inc.: Component Listed, MP
2168-8-1
Approvals, CSA: File # 95329 Certificate 2632-01
Approvals, Factory Mutual: JI 2D4A1.AF
Approvals, Swiss RE: Acceptable
Approvals, Others: CSD-1 AFB: Acceptable
Material
Number
Operating
Range (psi)
Operating
Range (kPa)
Differential
Pressure Range
(psi)
Differential
Pressure Range
(kPa)
Differential
Type
Switch
Operation
Switching
Action
Approximate,
Dimensions
Pipe
Connection
Mounting
C6097A1004/U 0.4 to 5 in. wc 0.10 to 1.25 kPa 0.16 in. wc
Nominal;
0.24 in. wc
Maximum
0.04 kPa
Nominal;
0.06 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097A1012/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc
@ min. setpoint;
max. 4.2 in. wc
@ max. setpoint
max. 0.60 kPa
@ min. setpoint;
max. 1.05 kPa
@ max. setpoint
Additive Manual
Reset
Break on
pressure
fall
3 17/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(90 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097A1020/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc
@ min. setpoint;
max. 4.2 in. wc
@ max. setpoint
max. 0.60 kPa
@ min. setpoint;
max. 1.05 kPa
@ max. setpoint
Additive Manual
Reset
Break on
pressure
fall
2 19/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(66 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097A1038/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc
@ min. setpoint;
max. 12 in. wc
@ max. setpoint
max. 2.5 kPa @
min. setpoint;
max. 3.0 kPa @
max. setpoint
Additive Manual
Reset
Break on
pressure
fall
3 17/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(90 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
70-6910 857
Commercial/Industrial
Combustion Controls
Pressure Switches
Material
Number
Operating
Range (psi)
Operating
Range (kPa)
Differential
Pressure Range
(psi)
Differential
Pressure Range
(kPa)
Differential
Type
Switch
Operation
Switching
Action
Approximate,
Dimensions
Pipe
Connection
Mounting
C6097A1046/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc
@ min. setpoint;
max. 12 in. wc
@ max. setpoint
max. 2.5 kPa @
min. setpoint;
max. 3.0 kPa @
max. setpoint:
Additive Manual
Reset
Break on
pressure
fall
2 19/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(66 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097A1053/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc
Nominal;
0.48 in. wc
Maximum
0.06 kPa
Nominal;
0.12 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097A1061/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc
Nominal;
0.48 in. wc
Maximum
0.06 kPa
Nominal;
0.12 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
2 1/4 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(57 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097A1079/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc
Nominal; 2.4 in.
wc Maximum
0.27 kPa
Nominal;
0.60 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097A1087/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc
Nominal; 2.4 in.
wc Maximum
0.27 kPa
Nominal;
0.60 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
2 1/4 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(57 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097A1095/U 0.4 to 5 in. wc 0.10 to 1.25 kPa max. 0.6 in. wc
@ min. setpoint;
max. 0.25 in. wc
@ max. setpoint
max. 0.15 kPa
@ min. setpoint;
max. 0.25 kPa
@ max. setpoint
Additive Manual
Reset
Break on
pressure
fall
3 17/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(90 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097A1103/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 psi @
min. setpoint;
max. 1.4 psi @
max. setpoint
max. 7.6 kPa @
min. setpoint;
max. 9.6 kPa @
max. setpoint
Additive Manual
Reset
Break on
pressure
fall
2 19/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(66 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097A1111/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 psi @
min. setpoint;
max. 1.4 psi @
max. setpoint
max. 7.6 kPa @
min. setpoint;
max. 9.6 kPa @
max. setpoint
Additive Manual
Reset
Break on
pressure
fall
3 17/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(90 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097A1129/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal;
0.3 psi
Maximum
0.69 kPa
Nominal;
2.07 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
2 1/4 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(57 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097A1137/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal;
0.3 psi
Maximum
0.69 kPa
Nominal;
2.07 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097A1210/U 0.4 to 5 in. wc 0.10 to 1.25 kPa 0.16 in. wc
Nominal;
0.24 in. wc
Maximum
0.04 kPa
Nominal;
0.06 kPa
Maximum
Additive Auto
recycle
Break on
pressure
fall
2 1/4 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(57 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097A1228/U 0.4 to 5 in. wc 0.10 to 1.25 kPa max. 0.6 in. wc
@ min. setpoint;
max. 0.25 in. wc
@ max. setpoint
max. 0.15 kPa
@ min. setpoint;
max. 0.25 kPa
@ max. setpoint
Additive Manual
Reset
Break on
pressure
fall
3 17/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(90 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
Flange
Mount
858 70-6910
Pressure Switches
Material
Number
Operating
Range (psi)
Operating
Range (kPa)
Differential
Pressure Range
(psi)
Differential
Pressure Range
(kPa)
Differential
Type
Switch
Operation
Switching
Action
Approximate,
Dimensions
Pipe
Connection
Mounting
C6097B1002/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc
@ min. setpoint;
max. 12 in. wc
@ max. setpoint
max. 2.5 kPa @
min. setpoint;
max. 3.0 kPa @
max. setpoint
Subtractive Manual
Reset
Break on
pressure
rise
3 17/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(90 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097B1010/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc
@ min. setpoint;
max. 12 in. wc
@ max. setpoint
max. 2.5 kPa @
min. setpoint;
max. 3.0 kPa @
max. setpoint
Subtractive Manual
Reset
Break on
pressure
rise
2 19/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(66 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097B1028/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc
@ min. setpoint;
max. 4.2 in. wc
@ max. setpoint
max. 0.60 kPa
@ min. setpoint;
max. 1.05 kPa
@ max. setpoint
Subtractive Manual
Reset
Break on
pressure
rise
3 17/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(90 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097B1036/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc
@ min. setpoint;
max. 4.2 in. wc
@ max. setpoint
max. 0.60 kPa
@ min. setpoint;
max. 1.05 kPa
@ max. setpoint
Subtractive Manual
Reset
Break on
pressure
rise
2 19/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(66 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097B1044/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 in. wc
@ min. setpoint;
max. 1.4 in. wc
@ max. setpoint
max. 7.6 kPa @
min. setpoint;
max. 9.6 kPa @
max. setpoint
Subtractive Manual
Reset
Break on
pressure
rise
2 19/32 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(66 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097B1051/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 in. wc
@ min. setpoint;
max. 1.4 in. wc
@ max. setpoint
max. 7.6 kPa @
min. setpoint;
max. 9.6 kPa @
max. setpoint
Subtractive Manual
Reset
Break on
pressure
rise
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097B1069/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc
Nominal;
0.48 in. wc
Maximum
0.06 kPa
Nominal;
0.12 kPa
Maximum
Subtractive Auto
recycle
Break on
pressure
rise
2 1/4 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(57 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097B1077/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc
Nominal; 2.4 in.
wc Maximum
0.27 kPa
Nominal;
0.60 kPa
Maximum
Subtractive Auto
recycle
Break on
pressure
rise
2 1/4 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(57 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097B1085/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc
Nominal; 2.4 in.
wc Maximum
0.27 kPa
Nominal;
0.60 kPa
Maximum
Subtractive Auto
recycle
Break on
pressure
rise
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097B1093/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal;
0.3 psi
Maximum
0.69 kPa
Nominal;
2.07 kPa
Maximum
Subtractive Auto
recycle
Break on
pressure
rise
2 1/4 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(57 mm high x
69 mm wide x
69 mm deep)
Flange
Mount
C6097B1101/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal;
0.3 psi
Maximum
0.69 kPa
Nominal;
2.07 kPa
Maximum
Subtractive Auto
recycle
Break on
pressure
rise
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
C6097B1119/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc
Nominal;
0.48 in. wc
Maximum
0.06 kPa
Nominal;
0.12 kPa
Maximum
Subtractive Auto
recycle
Break on
pressure
rise
3 3/16 in. high x
2 23/32 in. wide x
2 23/32 in. deep
(81 mm high x
69 mm wide x
69 mm deep)
Vent
or Low
pressure –
1/8 in. NPT
internal
thread
1/4 in. NPT
internal
thread
70-6910 859
Commercial/Industrial
Combustion Controls
Pressure and Limit Controllers
L404F Pressuretrol® Controllers
Provide operating control with automatic limit protection for
pressure systems up to 300 psi (2068 kPa).
• Use with steam, air, noncombustible gases, or fluids non-corrosive
to pressure sensing element.
• Models have snap-acting switching to open or close a circuit on
pressure rise.
• Have adjustable differentials.
• Adjustments are made by screws on top of case.
• Mount using 1/4 inch -18 NPT internal pipe threads or surface mount
through base of case.
• Ground screw terminal.
Application: Provide control of steam, air, non-combustible gases or
non-corrosive fluids
Differential Type: Subtractive
Mounting: 1/4 inch-18 NPT internal thread connection on diaphragm
assembly, 1/4 -19 BSPT internal thread on models with BSPT ground
screw; or surface mount through back of case
Switch Operation: Auto recycle
Sensor Element: Stainless steel diaphragm standard; Brass Bellows
on models with 20 to 300 psi
Operating Temperature Range: -35°F to +150°F (-37°C to +66°C)
Electrical Connections: Screw terminals
Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A
resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive
Pipe Connection - Main or High Pressure: 1/4 inch-18 NPT internal
thread standard; 1/4 -19 BSPT internal thread on models with BSPT
ground screw
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP466,
Guide No. MBPR
Approvals, CSA: Certified: File No. LR1620, Guide No. 400-E-O; or
Certified: File No. LR95329 for Miss-wiring Compliant models
Approvals, Swiss RE: Acceptable
Material
Number
Operating
Range (psi)
Operating
Range (kPa)
Maximum
Sustained
Pressure (psi)
Maximum
Sustained
Pressure (kPa)
Differential
Pressure
Range (psi)
Differential
Pressure
Range (kPa)
Switching Action Includes Comments
L404F1060/U 2 to 15 psi 14 to 103 kPa 25 psi 172 kPa 2 to 6 psi 14 to 41 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
L404F1078/U 5 to 50 psi 35 to 345 kPa 85 psi 586 kPa 6 to 14 psi 41 to 97 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
L404F1094/U 20 to 300 psi 138 to 2068 kPa 350 psi 2413 kPa 20 to 50 psi 138 to 345 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
L404F1102/U 10 to 150 psi 69 to 1034 kPa 225 psi 1151 kPa 10 to 22 psi 60 to 152 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
L404F1219/U 2 to 15 psi 14 to 103 kPa 25 psi 172 kPa 2 to 6 psi 14 to 41 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
BSPT ground
screw and
European
Enclosure
L404F1227/U 10 to 150 psi 69 to 1034 kPa 225 psi 1151 kPa 10 to 22 psi 60 to 152 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
BSPT ground
screw and
European
Enclosure
L404F1235/U 20 to 300 psi 138 to 2068 kPa 350 psi 2413 kPa 20 to 50 psi 138 to 345 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
BSPT ground
screw and
European
Enclosure
L404F1243/U 5 to 50 psi 35 to 345 kPa 85 psi 586 kPa 6 to 14 psi 41 to 97 kPa SPDT snap action,
make R-W, break R-B
on pressure rise
BSPT ground
screw and
European
Enclosure
L404F1367/U 1 to 8 psi 7 to 55 kPa 25 psi 172 kPa 0.75 to 2 psi 5 to 14 kPa Snap switch breaks
R-B (closes R-W)
on pressure rise.
Make-on devices omit
terminal B.
Range Stop
installed at
8 PSI
L404F1375/U 5 to 50 psi 35 to 350 kPa 85 psi 586 kPa 6 to 14 psi 40 to 100 kPa Snap switch makes
R-W on pressure rise
Miss-wiring
Compliant (less
B terminal)
L404F1383/U 10 to 150 psi 70 to 1035 kPa 225 psi 1151 kPa 10 to 22 psi 70 to 150 kPa Snap switch makes
R-W on pressure rise
Miss-wiring
Compliant (less
B terminal)
L404F1391/U 20 to 300 psi 140 to 2070 kPa 350 psi 2413 kPa 20 to 50 psi 140 to 345 kPa Snap switch makes
R-W on pressure rise
Miss-wiring
Compliant (less
B terminal)
L404F1409/U 2 to 15 psi 14 to 103 kPa 25 psi 172 kPa 2 to 6 psi 15 to 40 kPa Snap switch makes
R-W on pressure rise
Miss-wiring
Compliant (less
B terminal)
860 70-6910
Pressure and Limit Controllers
Dimensions in inches (millimeters)
3-3/4
(95)
1-1/16 (27)
13/16 (21)
1-3/16
(30)
HOLE FOR
1/2 INCH
CONDUIT
DIFFERENIAL
ADJUSTMENT
SCREW
1-1/2 (38)
2-1/8 (54)
M19635B
1-13/16
(46)
4-1/2 (115)
4-11/32 (111)
1-61/64 (50) 1-15/16 (49)
3/16 X 11/32
(5 X 9)
KNOCKOUT
MAIN SCALE
ADJUSTMENT
SCREW
1/4 –18 NPT
CLEAR
PLASTIC
COVER
3-7/8
(99)
2-3/4 (70)
3-1/4 (83)
DIMENSION
"A"
(SEE TAB)
1
1
1 15 TO 100 kPa (2 TO 15 PSI) SCALE MODELS ONLY.
PSI
RANGE
2 TO 15
5 TO 50
10 TO 150
20 TO 300
DIMENSION
"A"
123
126
126
146
70-6910 861
Commercial/Industrial
Combustion Controls
Pressure and Limit Controllers
L404T, V Oil Pressuretrol® Limit Controllers
Oil pressure sensing devices for use on oil burner systems using
any type of fuel oil, including heavy pretreated oils.
• Clear plastic cover allows observation of the pressure settings.
• Models have snap-acting switching to open or close a circuit on
pressure rise.
• L404T High pressure limit, break a circuit on oil pressure rise above
setpoint.
• L404V Low Pressure limit, makes a circuit on oil pressure rise above
setpoint.
• Adjustments are made by screws on top of case.
• Mount using 1/4 inch -18 NPT internal pipe threads or surface mount
through base of case.
• Ground screw terminal.
Application: Oil pressure limit switch for fuel oil, including heavy oil
applications
Differential Type: Subtractive
Mounting: 1/4 in. NPT internal thread or surface mount through back
of case
Switch Operation: Auto recycle
Sensor Element: Stainless Steel diaphragm
Approximate, Dimensions: 4 31/32 in. high x 4 1/2 in. wide x 2 3/4 in.
deep (126 mm high x 114 mm wide x 70 mm deep)
Operating Temperature Range: -35°F to +150°F (-37°C to +66°C)
Electrical Connections: Screw terminals
Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A
resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive;
Pipe Connection: Main or High Pressure – 1/4 in. NPT internal thread
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP2168,
Guide No. MFHX
Approvals, CSA: Certified: File No. LR95329
Dimensions in inches (millimeters)
3-3/4
(95)
1-1/16 (27)
13/16 (21)
1-3/16
(30)
HOLE FOR
1/2 INCH
CONDUIT
DIFFERENIAL
ADJUSTMENT
SCREW
1-1/2 (38)
2-1/8 (54)
M19635B
1-13/16
(46)
4-1/2 (115)
4-11/32 (111)
1-61/64 (50) 1-15/16 (49)
3/16 X 11/32
(5 X 9)
KNOCKOUT
MAIN SCALE
ADJUSTMENT
SCREW
1/4 –18 NPT
CLEAR
PLASTIC
COVER
3-7/8
(99)
2-3/4 (70)
3-1/4 (83)
DIMENSION
"A"
(SEE TAB)
1
1
1 15 TO 100 kPa (2 TO 15 PSI) SCALE MODELS ONLY.
PSI
RANGE
2 TO 15
5 TO 50
10 TO 150
20 TO 300
DIMENSION
"A"
123
126
126
146
Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure
Range (psi)
Differential Pressure
Range (kPa)
Switching Action Includes
L404T1055/U 5 to 50 psi; 85 psi -
Maximum Sustained
35 to 350 kPa; 586 kPa -
Maximum Sustained
6 to 14 psi 40 to 100 kPa SPST snap-acting
break on pressure rise
L404T1063/U 10 to 150 psi; 225 psi -
Maximum Sustained
70 to 1035 kPa; 1151 kPa
- Maximum Sustained
10 to 22 psi 70 to 150 kPa SPST snap-acting
break on pressure rise
L404V1087/U 10 to 150 psi; 225 psi -
Maximum Sustained
70 to 1035 kPa; 1151 kPa
- Maximum Sustained
10 to 22 psi 70 to 150 kPa Snap switch makes
R-W on pressure rise
Miss-wiring Compliant
(less B terminal)
L404V1095/U 5 to 50 psi; 85 psi -
Maximum Sustained
35 to 350 kPa; 586 kPa -
Maximum Sustained
6 to 14 psi 40 to 100 kPa Snap switch makes
R-W on pressure rise
Miss-wiring Compliant
(less B terminal)
862 70-6910
Pressure and Limit Controllers
L4079 Pressuretrol® Limit Controllers
Dimensions in inches (millimeters)
3-7/8
(98)
1/4
(6)
(2-15 PSI ONLY)
KNOCKOUT
FOR 1/2 INCH
CONDUIT (2)
6
(1/4)
4-15/16
(125)
KNOCKOUT
(2) FOR NO.
10 SCREW
1/4 - 18 NPT
1-1/16
(27)
M22435
2-1/8
(54)
1-13/16
(46)
1-13/16
(46)
13/16
(21)
13/16
(21)
3-1/2 (89)
1-1/2 (38)
3/16 (5)
1-13/16
(46)
4-1/2 (114) (COVER)
4-3/8 (111) (CASE)
1-15/16
(49)
1-15/16
(49)
High pressure limit switches.
• Stainless steel diaphragm for use with steam, air, noncombustible
gases and fluids non-corrosive to stainless steel.
• L4079W is for Oil Applications.
• Micro Switch™ snap-acting switches open automatically on pressure
rise; must be manually reset.
• Mount using 1/4 in. NPT female fitting on diaphragm assembly or
surface mount through back of case.
Mounting: 1/4 in. NPT internal thread or surface mount through back
of case
Sensor Element: Stainless Steel diaphragm
Approximate, Dimensions: 5 in. high x 4 1/2 in. wide x 3 1/2 in. deep.
(127 mm high x 114 mm wide x 89 mm deep.)
Temperature Ratings: 150°F - Maximum Ambient (66°C - Maximum
Ambient)
Electrical Connections: Screw terminals
Contact Ratings: 120 Vac Switch Contact – 9.8 AFL, 58.8 ALR; 240
Vac Switch Contact – 4.9 AFL, 29.4 ALR
Pipe Connection: Main or High Pressure – 1/4 in. NPT internal thread
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP466,
Guide No. MBPR
Approvals, Swiss RE: Acceptable
Material Number Application Operating Range (psi) Operating Range (kPa) Switch Operation Switching Action
L4079A1035/U Provide limit control of steam,
air, non-combustible gases or
non-corrosive fluids
2 to 15 psi; 25 psi -
Maximum Sustained
14 to 103 kPa; 172 kPa -
Maximum Sustained
Manual Reset SPST (two) break
simultaneously on pressure rise
L4079A1050/U Provide limit control of steam,
air, non-combustible gases or
non-corrosive fluids
10 to 150 psi; 225 psi -
Maximum Sustained
69 to 1034 kPa; 1151 kPa -
Maximum Sustained
Manual Reset SPST (two) break
simultaneously on pressure rise
L4079B1033/U Provide limit control of steam,
air, non-combustible gases or
non-corrosive fluids
2 to 15 psi; 25 psi -
Maximum Sustained
14 to 103 kPa; 172 kPa -
Maximum Sustained
Manual Reset SPST break on pressure rise
L4079B1041/U Provide limit control of steam,
air, non-combustible gases or
non-corrosive fluids
10 to 150 psi; 225 psi -
Maximum Sustained
70 to 1035 kPa; 1151 kPa -
Maximum Sustained
Manual Reset SPST break on pressure rise
L4079B1058/U Provide limit control of steam,
air, non-combustible gases or
non-corrosive fluids
5 to 50 psi; 85 psi -
Maximum Sustained
35 to 350 kPa; 586 kPa -
Maximum Sustained
Manual Reset SPST break on pressure rise
L4079B1066/U Provide limit control of steam,
air, non-combustible gases or
non-corrosive fluids
20 to 300 psi; 350 psi -
Maximum Sustained
140 to 2070 kPa; 2413 kPa -
Maximum Sustained
Manual Reset SPST break on pressure rise
L4079W1000/U High oil pressure limit switch for
heavy oil applications.
10 to 150 psi; 225 psi -
Maximum Sustained
35 to 350 kPa; 1151 kPa -
Maximum Sustained
Manual Reset SPST break on pressure rise -
Oil Applications
70-6910 863
Commercial/Industrial
Combustion Controls
Pressure and Limit Controllers
L408J Vaporstat® Controllers
Provide operating control and automatic high limit protection
for vapor heating systems with pressures up to 4 psi (8 kPa). All
models have Microswitch snap switches to open or close a circuit
on a pressure rise.
• Stainless steel diaphragm for use with liquids, air, noncombustible
gases, ammonia, oxygen, distilled water and similar media.
• Provide SPDT switching.
• Clear plastic cover allows observation of the pressure settings.
• Mount using hexagonal fitting with 1/4 in. NPT internal threads for
direct mounting to the 14026 (steel) or 50024585-001 (brass) Steam
Trap (siphon loop).
• Ground Screw terminal.
Application: Provide operating control and automatic limit protection
for pressure systems with pressures up to 4 psi (8 kPa)
Differential Type: Subtractive
Mounting: 1/4 in. NPT internal thread or surface mount through back
of case
Sensor Element: Stainless Steel diaphragm
Approximate, Dimensions: 5 1/8 in. high x 4 1/2 in. wide x 4 1/2 in.
deep. (130 mm high x 114 mm wide x 114 mm deep.)
Operating Temperature Range: -35°F to +150°F (-37°C to +66°C)
Electrical Connections: Screw terminals
Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A
resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive
Pipe Connection: Main or High Pressure – 1/4 in. NPT internal thread
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP466,
Guide No. MBPR
Approvals, CSA: Certified: File No. LR1620, Guide No. 400-E-O
Approvals, Swiss RE: Acceptable
Dimensions in inches (millimeters)
1-5/32
(29)
2-1/8 (54) 1/4 – 18 NPT
2-1/4 (57)
1-13/16
(46)
1-15/16
(49)
1-61/64
(50)
4-11/32 (110)
CASE
4-1/2 (114)
COVER
3-7/8
(98)
2-3/4 (70)
1-1/16 (27)
13/16
(21)
5-1/8
(130)
3-23/32
(95)
1-1/16
(27)
7/8
(22) DIA.
1-3/16 (30)
2-1/4 (57)
4-1/2 (114)
M19770
3/16 (9) x 21/64 (8) KNOCKOUT (2)
Material
Number
Operating Range
(psi)
Operating Range
(kPa)
Differential Pressure
Range (psi)
Differential Pressure
Range (kPa)
Switch Operation Switching Action Comments
L408J1009/U 0 to 16 oz/in2 0 to 6.9 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPDT make R-W,
break R-B on
pressure rise
L408J1017/U 0 to 4 psi 0 to 28 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPDT make R-W,
break R-B on
pressure rise
L408J1025/U 0 to 16 oz/in2 0 to 6.9 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPST make on
pressure rise Only
Miss-wiring
Compliant
L408J1033/U 0 to 4 psi 0 to 28 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPST make on
pressure rise Only
Miss-wiring
Compliant
864 70-6910
Pressure and Limit Controllers
L91 Proportional Pressuretrol® Controllers
W R B W R B W R B
PRESSURE RISE PRESSURE RISE
L91A,B L91D M16597
Modulating pressure operating control for regulation of liquid or
air and other non-corrosive gases.
• Use with steam, air, noncombustible gases, or other fluids noncorrosive
to the brass or phos-bronze (300 psi models) bellows.
• Do NOT use with combustible mediums or any medium chemically
harmful to phos-bronze bellows (10-300 psi models) or brass bellows
(all other pressure range models).
Application: Modulating pressure control for regulation of liquid, air, or
other non-corrosive gases.
Switch Operation: Modulating
Operating Temperature Range: 32°F to 150°F (0°C to 66°C)
Electrical Connections: Screw terminals
Pipe Connection: Main or High Pressure – 1/4 in. NPT external thread
Material
Number
Operating Range
(psi)
Operating Range
(kPa)
Differential
Pressure
Range (psi)
Differential
Pressure
Range (kPa)
Mounting Sensor
Element
Approximate, Dimensions Modulation
Output
L91A1037/U 0 to 15 psi;
25 psi - Maximum
Sustained
0 to 103 kPa;
172 kPa -
Maximum
Sustained
0.5 psi 3.4 kPa optional surface
mount through
back of case
Brass bellows 6 7/8 in. high x 4 1/2 in. wide x
2 7/8 in. deep (175 mm high x
114 mm wide x 73 mm deep)
Single
potentiometer,
140 ohms
L91A1052/U 5 to 150 psi;
225 psi -
Maximum
Sustained
34 to 1034 kPa;
1151 kPa -
Maximum
Sustained
5 psi 34 kPa optional surface
mount through
back of case
Brass bellows 5 3/4 in. high x 4 1/2 in. wide x
2 3/4 in. deep (146 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
140 ohms
L91A1078/U 10 to 300 psi;
325 psi -
Maximum
Sustained
69 to 2068 kPa;
2241 kPa -
Maximum
Sustained
12 psi 83 kPa optional surface
mount through
back of case
Phos-bronze
bellows
6 1/16 in. high x 4 1/2 in. wide
x 2 3/4 in. deep (154 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
140 ohms
L91A1136/U 10 to 300 psi;
325 psi -
Maximum
Sustained
69 to 2068 kPa;
2241 kPa -
Maximum
Sustained
12 psi 83 kPa optional surface
mount through
back of case
Phos-bronze
bellows
6 1/16 in. high x 4 1/2 in. wide
x 2 3/4 in. deep (154 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
140 ohms
L91B1035/U 0 to 15 psi;
25 psi - Maximum
Sustained
0 to 103 kPa;
172 kPa -
Maximum
Sustained
1.5 to 12 psi 10 to 83 kPa optional surface
mount through
back of case
Brass bellows 6 7/8 in. high x 4 1/2 in. wide x
2 7/8 in. deep (175 mm high x
114 mm wide x 73 mm deep)
Single
potentiometer,
140 ohms
L91B1050/U 5 to 150 psi;
225 psi -
Maximum
Sustained
34 to 1034 kPa;
1151 kPa -
Maximum
Sustained
5 to 23 psi 35 to 160 kPa optional surface
mount through
back of case
Brass bellows 5 3/4 in. high x 4 1/2 in. wide x
2 3/4 in. deep (146 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
140 ohms
L91B1068/U 10 to 300 psi;
325 psi -
Maximum
Sustained
69 to 2068 kPa;
2241 kPa -
Maximum
Sustained
28 to 110 psi 193 to 758 kPa optional surface
mount through
back of case
Phos-bronze
bellows
6 1/16 in. high x 4 1/2 in. wide
x 2 3/4 in. deep (154 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
140 ohms
L91B1100/U 5 to 150 psi;
225 psi -
Maximum
Sustained
0 - 1 MPa;
1151 kPa -
Maximum
Sustained
5 to 23 psi 35 to 160 kPa 1/4 in BSP-TR
thread Mounting
Brass bellows 5 3/4 in. high x 4 1/2 in. wide x
2 3/4 in. deep (146 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
135 ohms
L91B1118/U 10 to 300 psi;
325 psi -
Maximum
Sustained
0 - 2 MPa;
2241 kPa -
Maximum
Sustained
28 to 110 psi 193 to 758 kPa 1/4 in BSP-TR
thread Mounting
Phos-bronze
bellows
6 1/16 in. high x 4 1/2 in. wide
x 2 3/4 in. deep (154 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
140 ohms
L91B1241/U 10 to 300 psi;
325 psi -
Maximum
Sustained
69 to 2068 kPa;
2241 kPa -
Maximum
Sustained
12 to 48 psi 85 to 330 kPa optional surface
mount through
back of case
Phos-bronze
bellows
6 1/16 in. high x 4 1/2 in. wide
x 2 3/4 in. deep (154 mm high x
114 mm wide x 70 mm deep)
Single
potentiometer,
140 ohms
L91D1015/U 0 to 15 psi;
25 psi - Maximum
Sustained
0 to 103 kPa;
172 kPa -
Maximum
Sustained
1.5 to 12 psi 10 to 83 kPa optional surface
mount through
back of case
Brass bellows 6 7/8 in. high x 4 1/2 in. wide x
2 7/8 in. deep (175 mm high x
114 mm wide x 73 mm deep)
Dual
potentiometer,
140 ohms
L91D1031/U 5 to 150 psi;
225 psi -
Maximum
Sustained
34 to 1034 kPa;
1151 kPa -
Maximum
Sustained
11 to 52 psi 76 to 359 kPa optional surface
mount through
back of case
Brass bellows 5 3/4 in. high x 4 1/2 in. wide x
2 3/4 in. deep (146 mm high x
114 mm wide x 70 mm deep)
Dual
potentiometer,
140 ohms
70-6910 865
Commercial/Industrial
Combustion Controls
Pressure and Limit Controllers
Dimensions in inches (millimeters)
M29781
L91A,B,D
ALL OTHER
MODELS
10 TO 300 PSI
0 TO 15 PSI
0 TO 16 OZ/IN 2
1/4-18 NPT
DIM A (SEE TABULATION TABLE) DIM B (SEE
TABULATION
TABLE)
DIM C (SEE
TABULATION
TABLE)
1
2
2
3 4
1
2
3
4
4-1/2 (114.3) (COVER)
(110.3) (CASE)
3-57/64 (98.8)
3-13/32 (86.5)
(29.4)
(27.8)
(46.0)
(53.5)
(69.9)
(30.2)
1-1/16
1-3/16
(27.0)
(98.4)
(22.2)
4-11/32
(52.8)
(94.5)
(2)
EXTERNAL THREADS ON 0 TO 15 PSI MODELS; INTERNAL THREADS ON ALL OTHER MODELS.
SOME MODELS ARE ALSO AVAILABLE WITH 1/4-19 BSP-TR INTERNAL THREADS; SEE TABLE 1.
PROPORTIONING RANGE ADJUSTING SCREW ON L91B,D MODELS ONLY.
33312B KNURLED ADJUSTMENT SCREW KNOB, 7/8 IN. [22.2 MM] DIAMETER,. KNOB IS INCLUDED WITH 10 TO 300 PSI [0.07 TO .07 MPa] MODELS;
OPTIONAL ACCESSORY FOR OTHER MODELS.
FOR 10 TO 300 PSI [0.07 TO 2.07 MPa] MODELS. DIM C INCLUDES THE KNURLED ADJUSTMENT KNOB.
TABULATION OF DIMENSIONS A, B, AND C
OPERATING RANGE DIM A DIM B DIM C
CUSTOMARY UNITS METRIC UNITS IN. MM IN. MM IN. MM
0 TO 15 PSI
5 TO 150 PSI
10 TO 300 PSI
0 TO 103 kPa
0.03 TO 1.03 MPa
0.07 to 2.07 MPa
2-7/16
1-5/8
1-1/4
61.9
41.3
31.8
1-7/32
13/16
5/8
31.0
20.6
15.9
6-7/8
5-3/4
6-1/16
174.6
146.1
154.0
1-5/32
1-3/32
1-13/16
2-1/8
3-7/8
2-3/4
7/8
2-5/64
3-23/32
13/16
(20.1)
1-1/16
(27.0)
4 4
866 70-6910
Pressure and Limit Controllers
P7810 Pressure Control
Line voltage pressure controller that provides automatic operating
control, automatic limit protection, manual reset limit protection,
and 4-20 mA modulating firing rate control for pressure systems
up to 300 psi.
• May be used with steam, air, non-combustible gases or fluids that
will not corrode the pressure sensing element.
• Models available in 15, 150, 300 psi maximum setpoints.
• LED indicators show limit function/lockout.
• Reset function easily accessible under cover.
• Clear cover allows setpoint and differentials to be read (but not
adjusted) without opening the cover.
Application: On-off, Modulate and Limit Control
Sensor Element: Stainless Steel, solid state sensor
Materials: Case: Plastic
Approximate, Dimensions: 5 1/4 in. high x 4 21/32 in. wide x 3 3/8 in.
deep (133 mm high x 119 mm wide x 86 mm deep)
Voltage: 120 Vac
Frequency: 50 Hz; 60 Hz
Power Consumption: 3.6 W, 4.7 VA @ 50Hz; 3.3 W, 4.0 VA @ 60 Hz
Operating Temperature Range: 32°F to 140°F (0°C to +60°C)
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Electrical Connections: Screw terminals
Contact Ratings: 120 Vac Switch Contact – 9.8 AFL, 58.8 ALR,
10.0 A resistive
Pipe Connection: Main or High Pressure – 1/2 in. NPT internal thread
Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268,
Guide No. MCCZ
Approvals, CSA: Certified: File No. LR95329-6
Approvals, Factory Mutual: Approved: Report No. J.I.2D3A6AF
Modulation Output: 4 mA to 20 mA
Dimensions in inches (millimeters)
RESET
PRESSURETROL¨
1/4 (6)
2x1-5/8
(41)
1-5/8
(41) 2-5/8 (67)
3-7/32 2x5-1/4 (133)
(82)
2-17/32
(64)
3-3/8 (86)
5-1/4
(133)
2x
3-3/16
(81)
2-1/8
(55)
4-23/32
(120)
2x27/32 (22)
DIAMETER
5-29/32 (150)
4-21/32
(119)
2-5/8
(67)
4
(102)
4-3/4
(120)
3/8
(10) 7/8
(22)
1
1
1
DIMENSIONS WITH DOOR IN OPEN POSITION.
M23225
2
2
PIPE THREAD IS 1/4 INCH NATIONAL PIPE THREAD FOR P7810A,B; 1/2 INCH NATIONAL PIPE THREAD FOR P7810C,D.
3
3
3 WIRING COMPARTMENT ACCESS COVER.
Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure
Range (psi)
Differential Pressure
Range (kPa)
Switching Action
P7810C1000/U 0 to 15 psi; 22.5 psi - Maximum
Sustained
0 to 103 kPa; 155 kPa - Maximum
Sustained
2 to 10 psi 14 to 69 kPa Break on pressure rise
P7810C1018/U 0 to 150 psi; 225 psi - Maximum
Sustained
0 to 1034 kPa; 1151 kPa - Maximum
Sustained
5 to 20 psi 35 to 135 kPa Break on pressure rise
P7810C1026/U 0 to 300 psi; 450 psi - Maximum
Sustained
0 to 2068 kPa; 3103 kPa - Maximum
Sustained
15 to 50 psi 103 to 340 kPa Break on pressure rise
70-6910 867
Commercial/Industrial
Combustion Controls
Pressure and Limit Controllers
Pressure Controls and Limits Accessories
Material Number Description Used With
106729/U C437, C637 Glass Lens, 6" diameter C437, C637
129178E/U Cover Assembly L404, L604
137632/U C437, C637 Paper Lens Gasket C437, C637
139870/U C437, C637 Lens Gasket for Rainproof Models C437, C637
139870A/U Glass lens with rubber gasket for NEMA 3 C437 and C637. C437, C637
14026/U Steam Trap “Black Iron Siphon Loop” for L404, L408, L91 or P7810A, B L404, L91, L604
209731A/U 1/2 in. NPT Brass Siphon Loop for P7810C, D P7810C, P7810D
23176CB/U L91 Potentiometer - 135 ohm L91
23176CF/U L91 Potentiometer - 135 ohm L91
32003039-001/U C6097 Lamp Kit, Position Indication C6097
32003040-001/U C6097 Cover, Recycle Model C6097
32003041-001/U C6097 Cover, Manual Reset Model C6097
4074BWJ/U Pressure Control/Limits, Limit Stop Assembly - to limit setpoint. Includes 129564 Range Stop, 107194 Range Stop
Screw and 23466 Wrench.
L404, L604, L91, L4079
50024585-001/U Steam Trap “1/4 in. NPT Brass Siphon Loop” for L404, L408, or L91 L404, L91, L604
868 70-6910
Modernization and Replacement
RM7895 On-Off Primary Control with Prepurge
Microprocessor-based integrated primary burner control for
automatically fired gas, oil, or combination fuel single burner
applications. Provides level of safety, functional capability and
features beyond conventional controls.
• Functions include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and
troubleshooting
• Subbase, amplifier, and prepurge timer are required for operation
• Options include PC interface using ModBus™, keyboard display
module, Data ControlBus™ Module, remote display module and firstout
expanded annunciator
• Five LEDs provide sequence information
• Interchangeable plug-in flame amplifiers
• Optional local or remote annunciation of operation and fault
information
• Nonvolatile memory retains history files and sequencing status after
power loss
• Optional remote reset capability
• Optional report generation using Modbus™
• Selectable relight or lockout on loss of flame
• Airflow switch check
Honeywell RA890, R4795, R7795 All 120 V models.
Fireye M-Series
IMPORTANT: For on-off, gas-fired systems, some authorities having
jurisdiction prohibit the wiring of any limit or operating contacts in
series with the main fuel valve(s).
DIRECTIONS:
1. Disconnect all power to programmer.
2. Remove old programmer from subbase (trade-in to Honeywell
Authorized Flame Safeguard Distributor).
3. Mark all wires on subbase; i.e., wires connected to terminal “1”
should be marked “1.” Disconnect wires as they are marked.
4. Remove old subbase.
5. Mount Q7800A Subbase.
6. Connect wires to subbase per attached cross reference. Pay close
attention to footnotes. For example: to convert a Fireye UVM-2 to a
RM7895, the wire marked “A” would connect to terminal #9 on the
Q7800. The wire marked “8” would connect to Q7800 terminal #8.
7. A superscript letter, such as “a” designates a footnote. Study these
footnotes carefully.
8. Plug in the RM7895. Make sure you select the proper ST7800A
Purge Timer and Detector for the application.
9. There are 2 wires on the amplifier section of the RM7895, which are
used to select the desired trial for ignition timing and mode (lock-out
or recycle). Refer to the RM7895 instruction sheet (form 66-1090)
for assistance with proper selection.
10. If a low voltage controller is used on the RA890 or UVM-1, remove
it and replace it with a line voltage controller. The line voltage
controller should be connected in series with the limits.
11. If a low voltage airflow switch is used on the RM7895, it must be
replaced with a line voltage airflow switch.
12. The following models are recommended for replacements:
Honeywell Device to be Replaced Replace With Amplifier
RA890E, F RM7895A R7847A
RA890G RM7895A R7849A
R4795A, D/W-R7290 AMP RM7895A
R4795A, D/W-R7289 AMP RM7895B R7847A
R7795A RM7895A R7849
R7795B RM7895A R7847
R7795C RM7895C R7849
R7796D RM7895C R7847
R4140P RM7895C R7847A or R7849A
R4140Y RM7895A
Fireye Device to be Replaced Replace With Amplifier
TFM1, 2, 3H RM7895A R7847A
UVM1, 2, 3, 3H R7849A
UVM5 RM7895C R7849A
CONVERSION CHART FOR RM7895 120 VOLT ONLY
Q7800 TERMINAL L1 L2 3 4 6 7 8 9 10 21 F G
Programmer to be Converted
RA890 (All) 1a 2 c b, d 6 b 3d 5 4 — F G
R4795 (All) a 2 c 8, 7 1 6b 3 5 4 — F G
R7795A, B L1 L2 9 8 16 3 5 6 18 — F G
R7795C, D L1 L2 9 8 16 3 5 6 18 7 F G
R4140P L1 L2 A M 3 P 5 7 — 6 S1 S2
R4140Y L1 L2 9 8 4 3 6 7 5 — Fe G
Fireye: UVM/TFM (All models)/MII 1 1 A 8 7 6 3 5 4 — S2f S1
UVM-1 (Prior to 1968) a 2 A b, d 1 b 3 5 4 — Sf S
UVM-2 (Prior to 1968), All others a 2 A 8 1 6 3 5 4 — Sf S
a Connect power to terminal L1.
b If no airflow switch is used, jumper Q7800 terminal 6 to 7.
c Replace low voltage alarm (if used) with line voltage alarm. Connect alarm directly to Q7800 terminal 3.
d On power burners, identify burner motor wire on terminal 3 and connect it to Q7800 terminal 4.
e Select amplifier to match detector being used.
f On UVM models, the detector must be changed to a Honeywell C7027 or C7035.
70-6910 869
Commercial/Industrial
Combustion Controls
Electromechanical Burner Controls
RA890F Protectorelay™ Primary Control
Primary control provides solid state, electronic flame safeguard
protection for industrial and commercial single or dual fuel
burners for rectification type flame detection.
• Uses rectification principle of electronic flame detection.
• Replaces RA890E in most applications and mounts on same
Q270A1024 Subbase.
• Recycles if flame signal lost while in Run. Failure to establish pilot
results in a lockout.
• Safe-start check prevents start-up if flame-simulating failure occurs
in flame detector circuit.
• Includes built-in protection against ignition crossover in flame rod
systems.
• Includes SPDT alarm contacts.
• Solid state circuitry.
• Mounts and removes easily through use of captive mounting screws.
• Mounting base is made of strong thermoplastic.
Application: Primary control for rectification application (Flame Rod for
example)
Frequency: 50 Hz; 60 Hz
Temperature Range: 60 Hz models -20°F to +115°F, 50 Hz models
-20°F to +105°F (50 Hz Models -29°C to +41°C, 60 Hz Models -29°C
to +46°C)
Approximate, Dimensions: 5 in. high x 5 in. wide x 4 3/4 in. deep
(including subbase) (127 mm high x 127 mm wide x 121 mm deep
(including subbase))
Approvals, Underwriters Laboratories Inc.: UL Listed: 120V models
only; File No. MP268, Guide No. MCCZ
Approvals, CSA: CSA Certified: 120V models only; File No. LR1620
Approvals, Factory Mutual: Approved: Report No. 17678, 19417,
19784
Material Number Voltage Flame Failure
Response Time (sec)
Alarm Relay
Switching
Safety Switch Timing Description
RA890F1270/U 120 Vac 0.8 sec SPDT 15 seconds Rectification, with alarm contacts
RA890F1288/U 120 Vac 3.0 sec SPDT 15 seconds Rectification, with alarm contacts
RA890F1296/U 208 Vac 3.0 sec SPDT 15 seconds Rectification, with alarm contacts
RA890F1304/U 220 Vac 0.8 sec SPDT 15 seconds Rectification, with alarm contacts
RA890F1338/U 120 Vac 0.8 sec SPDT 30 seconds Rectification, with alarm contacts
RA890F1346/U 120 Vac 3.0 sec SPDT 30 seconds Rectification, with alarm contacts
RA890F1387/U 240 Vac 3.0 sec SPDT 15 seconds Rectification, with alarm contacts
RA890F1478/U 120 Vac 0.8 sec SPDT 15 seconds Rectification, with alarm contacts, fast safe start check.
RA890G Protectorelay™ Primary Control
Primary control provides solid state, electronic flame safeguard
protection for industrial and commercial single or dual fuel
burners applications using Ultraviolet flame detectors.
• Design for interrupted ignition with intermittent pilot on gas burners,
and interrupted or intermittent ignition on oil burners.
• Use with a C7027, C7035 or C7044 Minipeeper Ultraviolet Flame
Detector for flame sensing.
• Recycles if flame signal lost while in Run. Failure to establish pilot
results in a lockout.
• Safe-start check prevents start-up if flame-simulating failure occurs
in flame detector circuit.
• Includes SPDT alarm contacts.
• Solid state circuitry, eliminates warm-up and increases resistance to
vibration.
• Mounts and removes easily through use of captive mounting screws.
• Mounting base is made of strong thermoplastic.
Application: Either a line or low voltage controller can be used
Frequency: 50 Hz; 60 Hz
Temperature Range: 60 Hz models -20°F to +115°F, 50 Hz models
-20°F to +105°F (50 Hz Models -29°C to +41°C, 60 Hz Models -29°C
to +46°C)
Approximate, Dimensions: 5 in. high x 5 in. wide x 4 3/4 in. deep
(including subbase) (127 mm high x 127 mm wide x 121 mm deep
(including subbase))
Approvals, Underwriters Laboratories Inc.: UL Listed: 120V models
only; File No. MP268, Guide No. MCCZ
Approvals, CSA: CSA Certified: 120V models only; File No. LR9S329
Approvals, Factory Mutual: Approved: Report No. 22013
Material Number Voltage Flame Failure
Response Time (sec)
Alarm Relay
Switching
Safety Switch Timing Description
RA890G1229/U 120 Vac 0.8 sec SPDT 15 seconds Ultraviolet, with alarm contacts
RA890G1245/U 220 Vac 0.8 sec SPDT 15 seconds Ultraviolet, with alarm contacts
RA890G1260/U 120 Vac 3.0 sec SPDT 15 seconds Ultraviolet, with alarm contacts
RA890G1286/U 240 Vac 3.0 sec SPDT 15 seconds Ultraviolet, with alarm contacts
Q270 Wiring Mount Base
Application: Wiring Mounting Base for RA890, R4795
Material Number Description Used With
Q270A1024/U Wiring Mounting Base for RA890, R4795 RA890, R4795
870 70-6910
Testers and Demonstrators
A7800 Tester
Provides quick operational check of the 7800 SERIES System
components.
• Allows testing different 7800 SERIES devices using configuration
plugs and functional switches to simulate interlocks and control
functions.
• Indicator lamps represent outputs as activated.
Application: Tester
Voltage: 120 Vac
Frequency: 50 Hz; 60 Hz
Temperature Range: -30°F to +150°F (-34.5°C to +65°C)
Material Number Required Components Includes Used With
A7800A1010/U Configuration Plugs, Included Configuration Plugs 7800 SERIES Relay Modules with Valve Proving System or New Optical Detector Amplifiers
A7800 and DSP2672 Replacement Parts
Material Number Application Used With Comments
203579A/U Tester; DSP2672 RM7800/40/45 (non VPS side) Configuration Plug RM7800; RM7840 Configures A7800 and DSP2672
203579B/U Tester; DSP2672 RM7838A Configuration Plug Configures A7800 and DSP2672
203579C/U Tester; DSP2672 RM7838B, C Configuration Plug Configures A7800 and DSP2672
203579D/U Tester; DSP2672 RM7885A Configuration Plug Configures A7800 and DSP2672
203579E/U Tester; DSP2672 RM7890 (non VPS models) Configuration Plug Configures A7800 and DSP2672
203579F/U Tester; DSP2672 RM7895, 96, 97, 98 (non VPS side) Configuration Plug Configures A7800 and DSP2672
203579G/U Tester; DSP2672 RM7823 Configuration Plug Configures A7800 and DSP2672
203579H Tester; DSP2672 RM7865 Configuration Plug Configures A7800 and DSP2672
203579J/U Tester; DSP2672 RM7838B, C (VPS) Configuration Plug A7800A1010 Tester Configures A7800 and DSP2672
203579K/U Tester; DSP2672 RM7890 (VPS) Configuration Plug A7800A1010 Tester
203579L/U Tester; DSP2672 RM7800/40G,L (VPS side) Configuration Plug A7800A1010 Tester
203579M/U Tester; DSP2672 RM7898 (VPS Side) Configuration Plug A7800A1010 Tester
70-6910 871
Commercial/Industrial
Combustion Controls
Testers and Demonstrators
Demonstrators or Trainers
DSP3452
DSP3981
DSP3956
DSP3564U
The DSP3452 is designed for training and demonstration of
Honeywell Burner and Boiler Controls with auxiliary devices
that are typically used with commercial and industrial burners. It
demonstrates the wiring and operation of primary safety controls.
• The trainer can be used with Honeywell primary controls or
programming controls (not included with the trainer).
• The nine trouble switches simulate a range of faults from a burned
out pilot valve to a faulty flame detector to an inoperative firing rate
motor.
• The trainer measures 20 1/2 in. x 32 in. x 12 1/2 in. It weighs
approximately 30 lbs.
Color: Black
Material
Number
Application Voltage Frequency Approximate,
Dimensions
Required
Components
Includes Used With Comments
DSP3452/U Primaries,
Programmers or 7800
Series Trainer
120 Vac 50 Hz; 60 Hz 20 1/2 in. x 32 in.
x 12 1/2 in.
Devices for
wiring and
training
jumper wires, propane gas
hose with regulator, detector
mounting adapters
Primaries,
Programmers
and 7800 SERIES
Relay Modules
Complete Flame
Safeguard Training
Package
DSP3564/U ControlLink FAR
Trainer/Demonstrator
120 Vac 50 Hz; 60 Hz Relay Module, R7999 Control
and 3 ML Motors; Relay Module,
R7999 Control and 4 ML Motors
ControLinks Fuel
Air Ratio controls
DSP3956/U ControLink FAR
Configuration Toolkit
ZM Software; USB-485
Converter with cable and
Connector for Controlinks
ControLinks Fuel
Air Ratio controls
DSP3981/U For Controlinks
Configuration and
Monitoring
120 Vac 50 Hz; 60 Hz ControLinks Fuel
Air Ratio controls
With S7999D
Touchscreen for
FAR Monitoring or
Programming
SOLA Demonstrators
The DSP3943 is used as a SOLA commissioning or monitoring
tool when a System or Local Operator Interface is not required
for operation. The DSP contains the S7999B1026 touchscreen
display which uses a wizardlike process to assist you through the
commissioning process.
The DSP3980 contains an S7999D1006 Touchscreen Display to
commission or monitor the SOLA system when a System or Local
Operator Interface is not required for operation. The DSP3980
includes the power supply for operation and cable with connector
for the SOLA system. A USB storage drive is provided to save
display screen snapshots or trending information.
Voltage: 120 Vac
Color: Black
Material Number Application Frequency Includes Used With Comments
DSP3943/U Demonstrator, SOLA 60 Hz S7910A1001 SOLA HC; S7999 Touchscreen Display;
S7910 Keyboard display, system switches and ports
DSP3980/U Demonstrator 50 Hz; 60 Hz SOLA Controls Touchscreen for R7910/R7911
SOLA Monitoring or Programming
872 70-6910
Testers and Demonstrators
Flame Simulator
Flame simulators simplify the troubleshooting of flame safeguard
controls by providing a quick method to check the flame detection
function.
Material Number Application Color Comments Used With
123514A/U Flame Simulator, Rectification Flame Amplifiers Brown Applications with test jack in G circuit R4075B; R4181A; R4138A, B; R7253A;
R8169B; R7257A; R7247A; R7847A
203659/U Simulates C7027, C7035, C7044 Flame Simulators for
7800 SERIES
Purple Simulates Minipeeper Flame Detectors 7800 SERIES Relay modules
FSP1535 Tester
Provides quick operational check of Honeywell RA890 or R4795
nonprogramming primary controls.
• Includes indicator lights that visually represent functions of ignition,
pilot and main valve as unit simulates system operation.
• Eliminates need to operate entire system.
• Tests units with rated voltage from 100 to 240, 50/60 Hz by
connecting line cord to the rated voltage.
Voltage: 120 Vacor 240 Vac
Frequency: 50 Hz; 60 Hz
Material Number Application Used With
FSP1535/U Tester RA890; R4795
FSP5004 Tester
A Tester that provides quick operational check of most Honeywell
BC7000, R4140, R7140 and R4150 programmers and R7795
primary controls (order 198355A adapter separately).
• Includes indicator lights that visually represent control functions of
programmer as unit simulates system operation.
• Works with 120 Vac, 60 Hz controls.
• Use to test some Gordon-Piatt programmers.
• Cannot be used to test some R4140 and R4150 models due to
design or wiring differences. Reference the list at right to see if
you have one of the controls that CANNOT be tested. If you do,
check these out using the instructions provided in their respective
instruction manuals.
• R4150/R4140/BC7000/R7795/R7140 Tester (120V only). Provides a
quick operational check.
Voltage: 120 Vac
Frequency: 50 Hz; 60 Hz
Material Number Application Comments Used With
FSP5004/U Tester DO NOT USE WITH: BC7000L1018, BC7000L1034, BC7000L1063; R4140D1004, R4140E1001,
R4140M1079, or non-120 Vac R4140 models
BC7000; R4140; R7795;
R7140
70-6910 873
Industrial Flame
Monitoring
Signal Processors
P531; P532 3-channel, Signal Processors
The P532/P531 supports three separate viewing heads, two
S55XBE and one S70X. Independent 2 x SPDT Flame On relay
contacts are provided for each viewing head (6 total). 0-20 or
4-20mA scalable analog output also provided for each viewing
head. SIL 3 capable.
• 3 channels.
• Two SPDT flame relay outputs, one SPDT self-check relay output
and one N.O. alarm relay output per channel.
• FM and CSA approved.
• Monitor the UV and IR flame component simultaneously or
separately when using the S550B/BE.
• Monitor 3 viewing heads simultaneously.
• Independent configuration for each viewing head.
• 2 sets of configuration data per viewing head.
• Viewing head temperature indication.
• Automatic set-up functionality.
• Automatic viewing head detection.
• Modbus and RS422 protocol compatible.
• NEMA 1 Enclosure Rated.
Output: 4-20mA
Communications: ModBus and RS422 Compatible
Mounting: Cabinet mounting tabs
Connection Type: Removable terminals
Dimensions: 4.3 in. wide x 5.8 in. deep x 5.5 in. high (109 mm wide x
147 mm deep x 117 mm high)
Approvals, CSA: Approved (Temperature Range -40 to 158°F; -40 to
70°C)
Approvals, Factory Mutual: Approved (Temperature Range -40 to
158°F; -40 to 70°C)
Used With: S550BE, S552BE, S556BE, S70X, S80X viewing heads
Material Number Description Application Keypad Status
Monitoring
Electrical
Ratings
Frequency Required Components
P531AC AC Signal Processor Signal Processor with 3
channels without keypad
Use KP532U
keypad
LEDs 85-264 Vac +
24 Vdc backup
50 Hz; 60 Hz Appropriate Flame
Detector
P531DC DC Signal Processor Signal Processor with 3
channels without keypad
Use KP532U
keypad
LEDs 22-26 Vdc+
24 Vdc backup
Appropriate Flame
Detector
P532AC AC Signal Processor Signal Processor with 3
channels and keypad
Integrated tri-color display 85-264 Vac +
24 Vdc backup
50 Hz; 60 Hz Appropriate Flame
Detector
P532DC DC Signal Processor Signal Processor with 3
channels and keypad
Integrated tri-color display 22-26 Vdc+
24 Vdc backup
Appropriate Flame
Detector
P532UI Program module/keypad
used with the P531
Program module/keypad
used with the P531
600U Flame Rod Signal Processor
Model 600 Ultra Flame Rod is a reliable Flame Detecting system
based on the proven principle of measuring rectified current flow
through a flame rod when a flame touches it. The Model 600 Flame
Detector measures the rectified current and closes the flame relay
if the current exceeds the value for the flame-on set-point.
Output: 175 Vac for flame rod
Mounting: DIN rail, 35mm
Connection Type: Removable terminals
Dimensions: 2-63/64 in. wide x 3-1/4 in. deep x 5-31/64 in. high
(76 mm wide x 83 mm deep x 139 mm high)
Used With: Flame Rod
Material Number Description Application Keypad Status Monitoring Electrical Ratings Frequency
600U Flame rod signal processor with DPDT
flame relay contacts, DPST ignition
transformer relay or ignition coil drive
Flame rod signal
processor
Integrated LEDs 85 to 132Vac or 170 to
264Vac
50 Hz; 60 Hz
874 70-6910
Signal Processors
P522 Signal Processor with 2 Channels and Keypad
The P522 supports two switched (not simultaneously) S55XBE
viewing heads. 2 x SPDT Flame On relay contacts and 0-20 or
4-20mA scalable analog output is also provided. SIL 3 capable.
• 2 channels.
• Integrated keypad.
• Two SPDT flame relay outputs and one SPDT self-check relay
output.
• FM and CSA approved.
• Flame failure response and time delay on set-up.
• Connect 2 viewing heads, monitoring 1 at a time.
• Independent configuration for each viewing head.
• 2 sets of configuration data per viewing head.
• Viewing head temperature indication.
• Modbus and RS422 protocol compatible.
• NEMA 1 Enclosure Rating.
Application: Signal Processor with 2 channels and keypad
Keypad: Integrated
Status Monitoring: LEDs
Output: 4-20mA
Communications: ModBus and RS422 Compatible
Mounting: Cabinet mounting tabs
Connection Type: Removable terminals
Dimensions: 4.3 in. wide x 6.4 in. deep x 6.7 in. high (109 mm wide x
162 mm deep x 170 mm high)
Approvals, CSA: Approved
Approvals, Factory Mutual: Approved (Temperature Range -32 to
+122°F; 0 to +50°C)
Material Number Description Electrical Ratings Frequency Used With Required Components
P522AC AC Signal Processor 85-264 Vac + 24 Vdc
backup
50 Hz; 60 Hz S550B/BE, S552B/BE, S556B/
BE viewing heads
Appropriate Flame Detector
P522DC DC Signal Processor 22-26 Vdc+ 24 Vdc
backup
S550B/BE, S552B/BE, S556B/
BE viewing heads
Appropriate Flame Detector
WATCHDOGIII Flare Stack Signal Processor
The P222 is used with S256 viewing head for remote monitoring of
flare flame. 2 x SPDT Flame On relay contacts for T1 timer and 1 x
SPDT for T2 timer. 0-20 or 4-20mA scalable analog output is also
provided. Two timers are included for flame delay off settings one
0 to 60 seconds (T1) and one 0 to 3600 seconds (T2).
Application: Flare Stack signal processor with 1 channel and keypad
Keypad: Integrated
Status Monitoring: LEDs
Output: 0/4-20mA
Communications: ModBus and RS422 Compatible
Mounting: Cabinet mounting tabs
Connection Type: Removable terminals
Dimensions: 4.3 in. wide x 6.4 in. deep x 6.7 in. high (109 mm wide x
162 mm deep x 170 mm high)
Approvals, QPS: Approved
Material Number Description Electrical Ratings Frequency Used With Required Components
P222 Watchdog Signal Processor 85-264 Vac + 24 VDC
backup
50 Hz; 60 Hz S256 WATCHDOGIII flare stack
viewing head
Appropriate Flame Detector
WATCHDOGIII Kit consisting of P222 processor,
S256B Viewing Head, 10-ft. C328
cable, quick disconnect plug.
85-264 Vac 50 Hz; 60 Hz
70-6910 875
Industrial Flame
Monitoring
Signal Processors
S256B Flare Stack Viewing Head
S256B is a UV flare stack viewing head/flame detector, that detects
the presence or absence of flame at the flare stack tip. Used for
continuous UV flare stack monitoring to ensure no unburned toxic
or waste gas releases into the atmosphere.
• Not adversely affected by Gamma Rays or X-Rays.
• Solar blind.
• Ground mounted, up to 1000 feet away from flare stack tip.
• UV gain selection of 0-99.
• Digital display.
• Quick disconnect plug.
• Easy to install with no plant shutdown.
• NEMA 4X / IP67 enclosure rating.
• Ambient temperature: -40°F to +140°F (-40°C to +70°C).
• 22-26 VDC supplied by signal processor.
• Used with P222 signal processor.
Application: Flame Detector for use with P222 processor
NEMA Rating: 4X
Electrical Connections: Quick disconnect plug
Mounting: 2" Pipe mount
Electrical Ratings: 22 to 26Vdc from signal processor
Dimensions: 3.7 in. wide x 20.3 in. deep x 13.7 in. high (94 mm wide x
516 mm deep x 348 mm deep)
Ambient Temperature Range: -40 to 140°F (-40 to 60°C)
Approvals, QPS: QPS to CSA 22.2
Environmental, Electrical, or Ingress Protection Rating: IP67
Comments: One color monitoring
Used With: P222 Processor
Material Number UV Gain Adjustment IR Gain Adjustment Digital Displays Description
S256B 0-99 Yes (1) UV viewing head for use with P222
700 Signal Processor with 1 Channel
The 700 supports one UV or IR viewing head model S70X or S80X.
2 x SPDT Flame On relay contacts and 0-20 or 4-20mA scalable
analog output is also provided. SIL 3 capable.
• 1 channel.
• Two SPDT flame relay outputs and one SPDT self-check relay
output.
• FM and CSA approved.
• Status LEDs.
• DIN rail mounting.
• Modbus and RS422 protocol compatible.
• NEMA 1 Enclosure Rating.
Application: Signal processor with 1 channel and keypad
Status Monitoring: LEDs
Output: 4-20mA
Communications: ModBus and RS422 Compatible
Mounting: DIN rail
Connection Type: Removable terminals
Dimensions: 2.9 in. wide x 3.3 in. deep x 5.5 in. high (74 mm wide x
84 mm deep x 140 mm high)
Approvals, CSA: Approved
Approvals, Factory Mutual: Approved (Temperature Range 32 to
140°F; 0 to 60°C)
Material Number Description Keypad Electrical Ratings Frequency Used With Required Components
700ACSP AC Signal Processor Integrated 85-264 Vac 50 Hz; 60 Hz All models of S702, S706, S802,
S806 viewing heads
Appropriate Flame
Detector
700DCSP DC Signal Processor Integrated 22-26 Vdc All models of S702, S706, S802,
S806 viewing heads
Appropriate Flame
Detector
876 70-6910
All-in-One Viewing Head and Processor
All-in-One Viewing Head and Processor
U2-101x and U2-101x PF are integrated viewing head and
processor (All in One) with integral touch screen for operator
interface. One Normally Open Flame relay contact and one
Normally Open Fault relay contact is provided for interlock. 0-20
or 4-20 mA scalable analog output is also provided. Power input
is 24 VDC @120 mA. Temperature sensor is included that provides
display in degree F and C. System is self checking (no mechanical
shutter) fit for use in SIL3 application. Approvals include (IP66),
Class I Div 1 (IEC Ex d-ATEX Zone 1) for PF version and Class I,
Div 2 (IEC Ex nA) for quick disconnect type models. For remote
monitoring and configuration, FLAMETOOL –HMI (support 32
loops) or FLAMETOOL-PC (Supports 248 loops) is available.
Available models are UVtron only (clean gases), IR only (oil and
coal), UVtron plus IR (for all fuels- all applications including SRU,
Kiln etc.). (UVSS is currently disabled).
Application: Combination DC signal processor and dual UV/IR
Viewing head
Keypad: Integrated
Electrical Ratings: 22-26 Vdc
Output: 4-20mA
Communications: ModBus and RS422 Compatible
Dimensions: 4.3 in. wide x 5.8 in. deep x 5.5 in. high (109 mm wide x
147 mm deep x 117 mm high)
Approvals, CSA: Approved (Temperature Range -40 to 158°F; -40 to
70°C)
Approvals, Factory Mutual: Approved (Temperature Range -40 to
158°F; -40 to 70°C)
Approvals, Others: SIL3 (Temperature Range -40 to 158°F; -40 to
70°C)
Material Number Description Status Monitoring Mounting Connection Type Used With Required Components
Combination DC signal processor and dual UV/IR Viewing head
U2-1010 Combination DC signal
processor and dual UV/IR
Viewing head.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
12 pin connector Cable and connector, PT
adapter and purge air
coupler sold separately.
U2-1010-PF Combination DC signal
processor and dual UV/IR
Viewing head with 10-ft
pigtail.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
pigtail, 10-ft (3m) PT adapter and purge air
coupler sold separately.
U2-1010-PF-050 Combination DC signal
processor and dual UV/IR
Viewing head with 50-ft
(15m) pigtail.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
pigtail, 50-ft (15m) PT adapter and purge air
coupler sold separately.
U2-1010-PF-100 Combination DC signal
processor and dual UV/IR
Viewing head with 100-ft
(30m) pigtail.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
pigtail, 100-ft (30m) PT adapter and purge air
coupler sold separately.
U2-1018-PF Combination DC signal
processor and dual UV/
IR Viewing head with
10-ft pigtail. Pipe fitting
connection.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
pigtail, 10-ft (3m) PT adapter and purge air
coupler sold separately.
Combination DC signal processor and IR Viewing head
U2-1012 Combination DC signal
processor and IR Viewing
head.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
12 pin connector Cable and connector, PT
adapter and purge air
coupler sold separately.
U2-1012-PF Combination DC signal
processor and IR Viewing
head with 10-ft pigtail.
Pipe fitting connection.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
pigtail, 10-ft (3m) PT adapter and purge air
coupler sold separately.
Combination DC signal processor and UV Viewing head
U2-1016 Combination DC signal
processor and UV
Viewing head.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
12 pin connector Cable and connector, PT
adapter and purge air
coupler sold separately.
U2-1016-PF Combination DC signal
processor and UV
Viewing head with
10-ft pigtail. Pipe fitting
connection.
LED for each sensor, flame
relay, and self check.
1" NPT process
connection
pigtail, 10-ft (3m) PT adapter and purge air
coupler sold separately.
70-6910 877
Industrial Flame
Monitoring
IFM Accessories
ISO UNIT
Material Number Application Description Used With
ISO-OR Replacement O-ring Replacement O‑ring for ISO‑UNIT and ISO‑UNITSS ISO-UNIT and ISO-UNITSS
ISO-QW Replacement quartz window Replacement quartz window for ISO‑Unit and
ISO‑UnitSS
ISO-UNIT and ISO-UNITSS
ISO-RR Replacement retainer ring Replacement retainer ring for ISO‑UNIT ISO-UNIT
ISO-RRSS Replacement retainer ring Replacement retainer ring for ISO‑UNITSS ISO-UNITSS
ISO-UNIT Sealing union with quartz
window
1 in. NPTF sealing union with quartz window and
1/2 in. NPTF purge port.
ISO-UNITHPGT Sealing Union - Stainless Steel
1" NPTF w/1/2" purge port
Sealing Union ‑ Stainless Steel 1" NPTF w/1/2" purge
port
ISO-UNITSS Sealing union with quartz
window
1 in. NPTF stainless steel sealing union with quartz
window and 1/2 in. NPTF purge port.
Flame Tool
Material Number Application Description Used With Comments
FLAMETOOLS-HMI/U For all series 700, 500 and U2 Remote programming and logging using touchscreen
system. Uses Honeywell S7999 display
All 700, 500 and U2 family Supports multiple loops
FLAMETOOLS-PC For all series 700, 500 and U2 Remote programming and logging using user PC.
Supports Windows 7 and 8, includes RS232 converter
cable and manual
All 700, 500 and U2 family Supports multiple loops
878 70-6910
IFM Accessories
Industrial Flame Monitoring Accessories
Material Number Application Description Used With
700-1 Swivel Mount Swivel Mount, 1" NPT to 1/2" NPT S700 and S800 Viewing
heads
700-2 Swivel Mount Swivel mount for S700 and S800 series viewing heads.
Flanged connection to 1/2 in. NPTM connection.
S700 and S800 series
viewing heads
700-3 Swivel Mount Swivel mount for S700 and S800 series viewing heads.
1/2 in. NPTF to 1/2 in. NPTM connection.
S700 and S800 series
viewing heads
700ACC Model S700 viewing head
cooling jacket
Model S700 viewing head cooling jacket. Use with
vortex coolers.
Vortex coolers
700CRLT Liquid tight cable restraint Liquid tight cable restraint for S700 and S800 series
viewing heads. For S800 viewing head, purchase S800
adapter ring, part 800-ACC-RING, separately.
S700 and S800 series
viewing heads. For S800
viewing head, purchase
S800 adapter ring, part
800-ACC-RING, separately.
700DA Delrin adapter replacement Delrin adapter replacement for S700 series viewing
heads. 1/2 in. NPTF process and 1/4 in. NPTF purge
connections.
S700 series viewing heads
700DA-1 Delrin adapter replacement Delrin adapter replacement for S700 series viewing
heads. 1 in. NPTF process and 1/4 in. NPTF purge
connections.
S700 series viewing heads
700LTA Liquid tight viewing head cable
adapter
Liquid tight viewing head cable adapter for S700/S800
series viewing heads.
S700 and S800 series
viewing heads
700RAA Model S700/S800 viewing
head right angle adapter
Model S700/S800 viewing head right angle adapter.
1/2 in. NPTF to 1/2 in. NPTM connection.
700UA Ultem heat insulating adapter Ultem heat insulating adapter for S700 series viewing
heads. 1/2 in. NPTF process and 1/4 in. NPTF purge
connections.
S700 series viewing heads
800ACC Model S800 viewing head
cooling jacket
Model S800 viewing head cooling jacket. Use with
vortex coolers.
Vortex coolers
800ACC-RING Adapter ring Adapter ring to fit 800 viewing head to 700ACC cooling
jacket and 700CRLT cable restraint.
800 viewing head to
700ACC cooling jacket and
700CRLT cable restraint
800DA Delrin adapter replacement Delrin adapter replacement for S800 series viewing
heads. 1/2 in. NPTF process and 1/4 in. NPTF purge
connections.
S800 series viewing heads
800UA Ultem heat insulating adapter Ultem heat insulating adapter for S800 series viewing
heads. 1/2 in. NPTF process and 1/4 in. NPTF purge
connections.
S800 series viewing heads
ACC55XBE Air cooling canister for Model
S55XBE viewing heads
Air cooling canister for Model S55XBE viewing heads.
1/4 inch air inlet port. Use with vortex coolers.
Model S55XBE viewing
heads; Vortex coolers
ACC5XX Air cooling canister for Model
5XX viewing heads
Air cooling canister for Model 5XX viewing heads.
1/4 inch air inlet port. Use with vortex coolers.
Model 5XX viewing heads;
Vortex coolers
ASY55XBE Model S55xBE viewing head
installation.
Cable Assembly, 50 foot C330S with overmolded
S55xBE connector. Includes 50 foot 4 conductor cable
with foil/braid shield and coupling nut tied to shield.
Use with Model S55xBE Viewing Heads
Model S55xBE Viewing
Heads
ASY55XBE-50 Model S55xBE viewing head
installation.
Cable Assembly, 50 foot C330S with overmolded
S55xBE connector. Includes 50 foot 4 conductor cable
with foil/braid shield and coupling nut tied to shield.
Use with Model S55xBE Viewing Heads
Model S55xBE Viewing
Heads
ASY55XBE-100 Model S55xBE viewing head
installation
Cable Assembly, 100 foot C330S with overmolded
S55xBE connector. Includes 200 foot 4 conductor
cable with foil/braid shield and coupling nut tied to
shield. Use with Model S55xBE Viewing Heads
Model S55xBE Viewing
Heads
70-6910 879
Industrial Flame
Monitoring
IFM Accessories
Material Number Application Description Used With
ASY55XBE-200 Model S55xBE viewing head
installation.
Cable Assembly, 200 foot C330S with overmolded
S55xBE connector. Includes 200 foot 4 conductor
cable with foil/braid shield and coupling nut tied to
shield. Use with Model S55xBE Viewing Heads
Model S55xBE Viewing
Heads
ASY55XBE-300 Model S55xBE viewing head
installation
Cable Assembly, 300 foot C330S with overmolded
S55xBE connector. Includes 300 foot 4 conductor
cable with foil/braid shield and coupling nut tied to
shield. Use with Model S55xBE Viewing Heads
Model S55xBE Viewing
Heads
ASY785 Model S70x/S80x viewing
head installation.
Cable Assembly, 50 foot C330S with pre-wired S70x/
S80x connector. Includes 50 foot 4 conductor, 22g
cable with drain, foil/braid shield and connector
housing tied to shield. Use with Model S70x/S80x
Viewing Heads
Model S70x/S80x Viewing
Heads
ASY785-200 Model S70x/S80x viewing
head installation.
Cable Assembly, 200 foot C330S with pre-wired
S70x/S80x connector. Includes 50 foot 4 conductor,
22g cable with drain, foil/braid shield and connector
housing tied to shield. Used with Model S70x/S80x
Viewing Heads
Model S70x/S80x Viewing
Heads
ASY786 Model S70x/S80x viewing
head installation.
Field Wireable Shielded Connector for S70x/S80x
Viewing Heads. Used with Model S70x/S80x Viewing
Heads
Model S70x/S80x Viewing
Heads
ASY964 15-ft cable with quick
disconnect
15-ft cable (12 conductor) with quick disconnect for all
U2 non-pipe fitting models.
U2-1010, U2-1012,
U2-1016, U2-1018 models
only.
C12S 12 conductor cable with
braided shield
12 conductor cable with braided shield for use with
all U2 combination DC signal processor and viewing
heads. Sold per foot.
U2-1010, U2-1012,
U2-1016, U2-1018,
U2-1010-pf, U2-1012-pf,
U2-1016-pf, U2-1018-pf
models only. Used with
-pf models for cable
extension.
C330S 4 Conductor Cable with
braided shield for S70x, S80x
and S55xBE Viewing heads
4 Conductor Cable with braided shield for all Iris
viewing heads
S55xBE, S70x/S80x
viewing heads, P522, and
P53x signal processors.
M3204 Vortex air cooler, model 3204. Vortex air cooler, model 3204 -4SCFM (113SLPM) for
maximum refrigeration 275 BTU/HR (69 Kcal/hr)
All cooling jackets
M3208 Vortex air cooler, model 3208. Vortex air cooler, model 3208 -8SCFM (227 SLPM) for
maximum refrigeration 550 BTU/HR (139 Kcal/hr)
All cooling jackets
M3210 Vortex air cooler, model 3210. Vortex air cooler, model 3210 -10 SCFM (283SLPM)
for maximum refrigeration 650 BTU/HR (164 Kcal/hr)
All cooling jackets
M4025 Vortex air cooler, model 4025. Vortex air cooler, for cabinet model 4025 - maximum
refrigeration 1700 BTU/HR (428 Kcal/hr)
For processor cabinet
cooling
M-701-1 Swivel Mount Swivel mount, 2 in. pipe slip-on to 1 in. NPT
connection.
All viewing heads- S70x
with DA-1
M-701-2 Swivel Mount Swivel Mount, 2" NPT to 1" NPT All viewing heads- S70X
with DA-1
M-701-2-FLG Flanged swivel mount Flanged swivel mount, 2 in. flanged to 1 in. NPTF. All viewing heads- S70X
with DA-1
M-701-2-SS Swivel Mount Swivel mount, 2 in. NPT female to 1 in. NPT female,
Stainless steel construction.
All viewing heads- S70X
with DA-1
M-701-3 Flanged swivel mount Flanged swivel mount, 3-bolt, 4.5 in. flanged to 1 in.
NPTF.
All viewing heads- S70X
with DA-1
M-701-3P Swivel Mount Swivel mount, 3 in. NPTF to 1 in. NPTF connection. All viewing heads- S70X
with DA-1
M-701-4 Swivel Mount Swivel mount, 2-bolt to 1 in. NPTF connection. All viewing heads- S70X
with DA-1
M-702-6 Orifice and retaining ring set. Orifice and retaining ring set. Used for all viewing
heads.
Used for all viewing heads.
PT-GA1 High temperature gasket for
1 in. locking coupler.
High temperature gasket for 1 in. locking coupler. 1 in. locking coupler
PT-QL1 Quartz lens for 1 in. locking
coupler.
Quartz lens for 1 in. locking coupler. 1 in. locking coupler
R-518-08 Viewing Head S256 Quick
Disconnect Plug
Viewing Head S256 Quick Disconnect Plug WDIII S256 viewing head
880 70-6910
IFM Accessories
Material Number Application Description Used With
R-518-11 Model S55xBE viewing head
installation.
S55xBE Field Wireable Cable with 6-8mm cable
bushing for use with C330S cable. Includes Field
wireable with proper bushing size to provide IP seal
with C330S cable. No shield at connector, less robust
version. Used with Model S55xBE Viewing Heads
Model S55xBE viewing
head, and C330S cable.
R-518-12 Heat Block-1" NPT All viewing heads with 1" NPTF connection All viewing heads with 1"
NPTF connection
R-518-13 Heat insulating nipple for
S70X/S80X series viewing
heads.
1/2 in. NPT Ultem heat insulating nipple for S70X/S80X
series viewing heads.
S70X/S80X series viewing
heads
R-518-CL12-HTG Locking coupler 1 in. NPT locking coupler with high temperature
gasket. Must be used with R-518-PT12 or R-518-
PT12L
All viewing head that has
1" NPTF
R-518-CL12-PG Locking quick disconnect/cam
and groove coupler adapter
1 in. NPT aluminum locking quick disconnect/cam and
groove coupler adapter with 1/2 in. NPT purge. Must
be used with R-518-PT12 and R-518-PT12L
All viewing head that has
1" NPTF
R-518-CL13-HTG Locking coupler 1/2 in. NPT locking coupler with high temperature
gasket. Must be used with R-518-PT13 or R-518-
PT13L
All viewing heads that
have 1/2" NPTF connection
R-518-PT12 Insulating locking coupler
adapter
1 in. NPT Ultem insulating locking coupler adapter.
Used with U2 processor/viewing head.
1 in. NPT Ultem insulating
locking coupler adapter
use with R-518-CL12-HTG
and R-518-CL12PG
R-518-PT12L Locking coupler adapter with
quartz lens.
1 in. NPT Ultem locking coupler adapter with quartz
lens.
1 in. NPT Ultem insulating
locking coupler adapter
with quartz lens for use
with R-518-CL12-HTG and
R-518-CL12PG
R-518-PT13 Locking coupler adapter only. 1/2 in. NPT Ultem insulating locking coupler adapter
use with R-518-CL13-HTG and R-518-CL13HTG
R-518-PT13L Locking coupler adapter with
quartz lens.
1/2 in. NPT Ultem locking coupler adapter with quartz
lens.
UVSOURCE Testing any UV based system Ultraviolet light source battery operated Test for any UV tube based
system
70-6910 881
Industrial Flame
Monitoring
IFM Accessories
Fiberoptic System
Material Number Application Description Used With
FASA-GLASS Glass fiber optics assembly for
IR flame detection
Glass fiber optics complete assembly for IR flame
detection with guide pipes and flex connection.
Standard assembly length 5‑feet. Standard 5‑ft fiber
optic cable. Use FASA‑GLASS‑FT to add additional fiber
optic cable length and inner/outer assemblies
FASA-GLASS-FT Glass fiber optics assembly for
IR flame detection
Glass fiber optics complete assembly per foot adder
for FASA‑GLASS, for IR flame detection. Includes
fiber optic cable and inner/outer assemblies in 1‑ft
segments.
FASA-GLASS
FASA-INT-GLASS Glass fiber optics assembly for
IR flame detection
Glass fiber optics inner tube assembly for IR flame
detection with flex connector. No guide pipes. Standard
assembly length 5‑ft. Use FASA‑INT‑GLS‑FT to add
additional fiber optic cable length and inner assembly
in 1‑ft length
FASA-INT-GLS-FT Glass fiber optics assembly for
IR flame detection
Glass fiber optics inner assembly per foot adder for
FASA‑INT‑GLASS, for IR flame detection. Includes fiber
optic cable and inner assembly in 1‑ft increment.
FASA-INT-GLASS
FASA-INT-QTZ-FT Quartz fiber optics assembly
for UV/IR flame detection
Quartz fiber optics inner tube assembly per foot adder
for FASA‑INT‑QUARTZ, for UV/IR flame detection.
Includes fiber optic cable and inner assembly in 1‑ft
segments.
FASA-INT-QUARTZ
FASA-INT-QUARTZ Quartz fiber optics assembly
for UV/IR flame detection
Quartz fiber optics inner tube assembly for UV/IR flame
detection with flex connector. No guide pipes. Standard
assembly length 5‑ft. Use FASA‑INT‑QTZ‑FT to add for
longer than 5'
FASA-QUARTZ Quartz fiber optics assembly
for UV/IR flame detection
Quartz fiber optics complete assembly for UV/IR
flame detection with guide pipes and flex connection.
Standard assembly length 5. Use FASA‑QUARTZ‑FT for
longer than 5’ by 1’ increment
FASA-QUARTZ-FT Quartz fiber optics assembly
for UV/IR flame detection
Quartz fiber optics complete assembly per foot adder
for FASA‑QUARTZ, for UV/IR flame detection. Includes
fiber optic cable and inner/outer assemblies in 1‑ft
increment
FASA-QUARTZ
FLEX-HOSE Hose for fiber optics assembly. 1/2 in. NPT x 36 in. long flex hose for fiber optics
assembly.
FOC-GLASS 5-ft Glass Fiber optic cable for
IR viewing heads.
5‑ft Glass Fiber optic cable, for IR viewing heads. Use
FOC‑GLASS‑FT adder for each additional foot in length
required.
IR viewing heads
FOC-GLASS-FT Glass fiber optic cable per foot
adder for FOC-GLASS, for IR
flame detection.
Glass fiber optic cable per foot adder for FOC‑GLASS,
for IR flame detection.
FOC-GLASS, for IR flame
detection
FOC-QUARTZ 5-ft Fiber optic cable, quartz
bundle for UV/IR viewing
heads with high temperature
epoxy
5‑ft Fiber optic cable, quartz bundle for UV/IR
viewing heads with high temperature epoxy. Use
FOC‑QUARTZ‑FT adder for each additional foot in
length required.
FOC-QUARTZ-FT
FOC-QUARTZ-FT Quartz fiber optic cable for UV/
IR flame detection
Quartz fiber optic cable per foot adder for
FOC‑QUARTZ, for UV/IR flame detection.
FOC-QUARTZ
FOLC-9C Fiber optic lens cartridge and
coupler
Fiber optic lens cartridge and coupler ‑ 9 degree
viewing angle
FASA and FASA-INT
FOLC-HS Replacement fiber optic lens
cartridge mounting hood/lens
housing
Replacement fiber optic lens cartridge mounting hood/
lens housing with 1/2 inch NPT connection.
882 70-6910
IFM Accessories
Material Number Application Description Used With
FOLC-SC Fiber optic lens cartridge and
coupler
Fiber optic lens cartridge and coupler ‑ straight
connection.
S550FOAD Fiber optics adapter viewing
head side
Fiber optics adapter for S55XB/S55XBE viewing head
and U2 models.
S55XB/S55XBE viewing
heads, U2
S550FOADY-FT Fiber optics adapter Fiber optics adapter with air purge connection for all
viewing heads with 1" NPT connection
S55XB/S55XBE viewing
heads, U2
S550FOADY-FT-AL Fiber optics adapter Fiber optics adapter with air purge connection for all
viewing heads with 1" NPT connection
S55XB/S55XBE viewing
heads, U2
S592-OR Spare Parts for FOLC-SC and
FOLC-9C
Metal O‑Ring Spare Parts for FOLC‑SC and FOLC‑9C FOLC-SC and FOLC-9C
S592-PC Spare Parts for FOLC-SC and
FOLC-9C
Fiber assembly quartz lens (plano/convex) for FOLC‑SC
and FOLC‑9C
FOLC-SC and FOLC-9C
S592-PP Spare Parts for FOLC-SC and
FOLC-9C
Plano/Plano window For FOLC‑SC and FOLC‑9C FOLC-SC and FOLC-9C
S592-RR Spare Parts for FOLC-SC and
FOLC-9C
Retainer clip for FOLC‑SC and FOLC‑9C FOLC-SC and FOLC-9C
S700FOAD Fiber optics adapter Fiber optics adapter for S70X viewing heads. Any 1/2" viewing head/
FASA
S800FOAD Fiber optics adapter Fiber optics adapter for S80X viewing heads. S80X viewing heads
70-6910 883
Industrial Flame
Monitoring
IFM Accessories
GHE Igniter System
The GHE High Energy Ignitor is a non fouling high energy device,
designed to directly ignite all liquid and gaseous fuels. The GE
High Tension Ignitor is designed to provide reliable ignition and
or warm up when and where required. It can be applied to boiler
applications from industrial to utility lime and cement kiln heaters,
etc.
Material Number Application Description Used With Comments
GHE1-3 Gas high energy pilot igniter
assembly used with gaseous
fuels
Gas high energy pilot igniter assembly
used with liquid and gaseous fuels,
1-3 MBH capacity, 1-7/8 inch OD with
36 inch SS flex hose, 36 inch SS air
hose, burner mounting tube, high
energy probe, igniter tip 12 in. long x
1/2 in OD.
Gaseous fuels 1-3 MMBTU/HR capacity, 1-7/8 inch OD with
36 inch SS flex hose, 36 inch SS air hose, burner
mounting tube, high energy probe, igniter tip 12 in.
long x 1/2 in OD. Standard assembly length 2-feet.
Use IGADD for each 1-ft assembly length addition.
Order Powerpack-12-CS, IGN-CPC-10 HT cable,
IGN-CPC-ADD for longer than 10' cable and Power
pack cabinet. Integral optical flame scanner option
is available.
GHE2-5 Gas high energy pilot igniter
assembly used with gaseous
fuels
Gas high energy pilot igniter assembly
used with liquid and gaseous fuels,
1-3 MBH capacity, 1-7/8 inch OD with
36 inch SS flex hose, 36 inch SS air
hose, burner mounting tube, high
energy probe, igniter tip 12 in. long x
1/2 in OD.
Gaseous fuels 2-5 MMBTU/HR capacity, 2-7/8 inch OD with
36 inch SS flex hose, 36 inch SS air hose, burner
mounting tube, high energy probe, igniter tip 12 in.
long x 1/2 in OD. Standard assembly length 2-feet.
Use IGADD for each 1-ft assembly length addition.
Order Powerpack-12-CS, IGN-CPC-10 HT cable,
IGN-CPC-ADD for longer than 10' cable and Power
pack cabinet. Integral optical flame scanner and
quick disconnect options are available.
GT-LITE Ignitor Spark tip / probe Ignitor Spark tip / probe, 12 inch long
x 1/2 inch OD.
12 inch long x 1/2 inch OD.
HEPADD High energy probe High energy probe per foot adder for
lengths over 2-feet. Use to add length
to IPASS, gas high energy replacement
pilot igniter probe assembly, in 1-foot
increments.
IPASS Use to add length to IPASS, gas high energy
replacement igniter probe assembly, in 1-foot
increments.
HV-HT Replacement internal GHE
ignitor cable with contact
Replacement internal GHE ignitor
cable with contact, 2-feet length
standard. Internal cable from igniter tip
to junction box. Use HV-HT-FT cable
adder for each additional foot in length
required.
GHE ignitor cable Internal cable from igniter tip to junction box. Use
HV-HT-FT cable adder for each additional foot in
length required.
HV-HT-FT Replacement internal GHE
ignitor cable
Replacement internal GHE ignitor cable
per foot adder for lengths over 2-feet.
Use to add length to HV-HT in 1-foot
increments.
GHE ignitor cable Use to add length to HV-HT in 1-foot increments.
IGADD Ignitor assembly per foot
adder
Ignitor assembly per foot adder for
igniter length over 2-ft. Use to add
length to GHE1-3 or GHE2-5, gas high
energy pilot igniter assembly in 1-foot
increments.
Add length to GHE1-3
or GHE2-5, gas high
energy pilot igniter
assembly in 1-foot
increments
Foot adder for igniter length over 2-ft
IGN-CPC-10 Ignitor cable 10 ft with canon
plug
Ignitor cable 10 ft with canon plug
for POWERPACK-12-CS. From power
pack to igniter. To add length, use
IGN-CPC-ADD.
POWERPACK-12-CS From power pack to igniter. To add length, use
IGN-CPC-ADD.
IGN-CPC-ADD Cannon plug cable Cannon plug cable adder for length
over 10-ft. Per foot adder for IGNCPC-
10.
IGN-CPC-10. For length over 10-ft
IGN-CPC-LB Replacement ignitor probe
junction box with canon plug
receptacle
Replacement ignitor probe junction
box with canon plug receptacle for
GHE ignitors.
GHE ignitors
IPASS GHE pilot igniter probe
assembly without burner
mounting tube, flange, gas
insert or air/gas flex hoses.
GHE pilot igniter probe assembly
includes igniter tip, junction box.
Standard assembly is 2'. Use HEPADD
for longer length. Order 12- Jule
PowerPack,-12-CS and IGN-CPC-10/
IGN-CPC-ADD
Gaseous fuels Includes high energy probe, igniter tip 12 in. long
x 1/2 in OD and junction box with receptacle.
Standard assembly length 2-feet. Use HEPADD for
each 1-ft assembly length addition. Order 12-Joule
POWERPACK-12-CS and associated cabling with
canon plug
NEMA-12-ADD NEMA 12 enclosure for igniter
powerpack.
NEMA 12 enclosure for igniter
powerpack.
Igniter powerpack
884 70-6910
IFM Accessories
Material Number Application Description Used With Comments
NEMA-4-ADD NEMA 4 enclosure for igniter
powerpack.
NEMA 4 enclosure for igniter
powerpack.
Igniter powerpack
NEMA-4X-ADD NEMA 4X enclosure for igniter
powerpack.
NEMA 4X enclosure for igniter
powerpack.
Igniter powerpack
POWERPACK-12-CS Ignitor 12 Joule Power pack
for GHE and IPASS
Ignitor 12 Joule Power Pack GHE and IPASS 120V/220V/50-60Hz, output energy 2,500Vdc, 12
Joule pulses @ 6 sparks/second.
QDADD Quick disconnect/cam and
groove coupler
Add quick disconnect/cam and groove
coupler on GHE2-5 in place of the
standard flange connection to the
burner mounting tube.
GHE2-5
70-6910 885
Industrial Flame
Monitoring
Viewing Heads
700 and 800 System
Available in single sensor only, UVTron or IR. Options include
quick disconnect with two LEDs or factory installed cable.
Application: Flame Detector for Oil Fired burners
Mounting: 1/2" NPTF or 1" NPTF with 1/4" NPT Purge connection
Electrical Ratings: 22 to 26Vdc from signal processor
Sight Pipe (NPT): 1/2 in.
Purge Air Pipe (NPT): 1/4 in.
Ambient Temperature Range: -40 to 149°F (-40 to 65°C)
Approvals, CSA: Approved CSA, FM IEC, SIL3 (Temp rating -40 to
149°F/-40 to 65°C)
Approvals, Factory Mutual: Approved
Environmental, Electrical, or Ingress Protection Rating: IP64
Required Components: Order ASY785 (50foot) or ASY785-200 (200ft)
for molded, shielded cable assemblies. ASY785 or ASY785-200 are
recommended for new installations.
Material
Number
Type Electrical Connections Shutter UV Gain
Adjustment
IR Gain
Adjustment
Dimensions Comments Used With
S702 IR Compact
viewing head
with 15-foot
cable
Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep
x 2.0 in. high (51 mm wide
x 246 mm deep x 51 mm
high)
Removable connector
cover for diagnostic LED
viewing during installation.
Use with 700 AC SP
or 700DC SP
S702PF IR Compact
viewing head
with 10-foot
cable
Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep
x 2.0 in. high (51 mm wide
x 246 mm deep x 51 mm
high)
S706 UV Compact
viewing head
with 15-foot
cable
Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep
x 2.0 in. high (51 mm wide
x 246 mm deep x 51 mm
high)
Removable connector
cover for diagnostic LED
viewing during installation.
Use with 700 AC SP
or 700DC SP
S706PF UV Compact
viewing head
with 15-foot
cable
Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep
x 2.0 in. high (51 mm wide
x 246 mm deep x 51 mm
high)
Use with 700 AC SP
or 700DC SP
S802 IR Compact
viewing head
with 15-foot
cable
Quick disconnect plug Electronic 1-9 1.8 in. wide x 9.2 in. deep
x 1.8 in. high (46 mm wide
x 234 mm deep x 46 mm
high)
Removable connector
cover for diagnostic LED
viewing during installation.
Use with 700 AC SP
or 700DC SP
S806 UV Compact
viewing head
with 15-foot
cable
Quick disconnect plug Electronic 1-9 1.8 in. wide x 9.2 in. deep
x 1.8 in. high (46 mm wide
x 234 mm deep x 46 mm
high)
Removable connector
cover for diagnostic LED
viewing during installation.
Use with 700 AC SP
or 700DC SP
886 70-6910
Viewing Heads
S55xBE Viewing head
The S550BE is provided with UVTron and IR sensors. System
is self checking, no mechanical shutters, not adversely affected
by X or Gamma rays generated by pipe check welding. Suitable
for all fuel flames, single or multiple fuels. Optional pipe fitting
(PF) versions provided with factory installed cable. Suitable for
hazardous location duty. SIL 3 capable.
• Not adversely affected by Gamma Rays or X-Rays.
• Mount in any orientation.
• IR gain selection of 0-699.
• UV gain selection of 0-99.
• 2 digital displays.
• Quick disconnect plug.
• Parameters stored in signal processor EEPROM.
• Ultraviolet and infrared with electronic shutter.
• Ambient Temperature: -40°F to +149°F (-40°C to +65°C)
• 22-26 VDC supplied by signal processor.
• CSA Rated IP64 Enclosure.
• Used with P532, P532, P531, P531, P522, P522 signal processors.
Application: Flame Detector for All fuels multiple burners
Mounting: 1" NPTF burner front with 1/2" purge connection
Electrical Ratings: 22 to 26Vdc from signal processor
Sight Pipe (NPT): 1 in.
Purge Air Pipe (NPT): 1/2 in.
Dimensions: 4.1 in. wide x 8.1 in. deep x 5.4 in. high (104 mm wide x
206 mm deep x 137 mm high)
Ambient Temperature Range: -40 to 158°F (-40 to 70°C)
Approvals, CSA: Approved CSA
Approvals, Others: SIL3 (Temp rating -40 to 149°F/ -40 to 65°C)
IECEx IEC: Approved
Approvals, Factory Mutual: Approved
Environmental, Electrical, or Ingress Protection Rating: IP64
Used With: P522, P531 and P532 Processors
Material Number Type Electrical
Connections
Shutter UV Gain
Adjustment
IR Gain
Adjustment
Digital
Displays
Comments Required Components
Flame Detector for All fuels multiple burners
S550BE Quick disconnect
plug
Electronic
of IR only
0-99 0-699 Yes (2) 2 digit display
for UV and IR
Use with molded cable
ASY55XBE or ASY55XBE-200.
P522 or P532 signal
processor.
S550BE-PF UV/IR Viewing Head 10 foot pigtail Electronic
of IR only
0-99 0-699 Yes (2) 2 digit display
for UV and IR
Factory installed 10' cable.
P522 or P532 signal
processor.
Flame Detector for Gas multiple Burners
S556BE UV Viewing Head with
Digital Display
Quick disconnect
plug
0-99 Yes (1) 2 digit display
for UV
Use with molded cable
ASY55XBE or ASY55XBE-200.
P522 or P532 signal
processor.
S556BE-PF UV Viewing Head with
Digital Display
10 foot