ECC or Buildings Branch | Flame Safeguard part 1 This is honeywells catalog of parts. Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC7820 PROGRAMMER RELAY MODULES: M15516G SELECT A SUBBASE SELECT A PURGE CARD SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7820A1026 EC7820A1034 DESCRIPTION ONE IGNITION ATTEMPT FIVE IGNITION ATTEMPTS O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE - CE APPROVAL O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4, KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7061A, F, M** C7061A, F, M** C7076A, F SELECT A FLAME AMPLIFIER * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012 A,C. ** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 1.) 2.) 3.) 4.) 5.) 70-6910 737 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7830 PROGRAMMER RELAY MODULES: M15517H SELECT A SUBBASE SELECT A PURGE CARD SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7830A1033 EC7830A1041 EC7830A1066 120VAC 50/60 HZ RM7830A1003 RM7830A1029 RM7830A1011 O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DESCRIPTION POST-PURGE 2 SECONDS POST-PURGE 30 SECONDS POST-PURGE 15 SECONDS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE - CE APPROVAL O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7061A, F, M** C7061A, F, M** C7076A, F SELECT A FLAME AMPLIFIER * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012 A,C. ** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 1.) 2.) 3.) 4.) 5.) 738 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7850 PROGRAMMER RELAY MODULES: M15519G SELECT A SUBBASE SELECT A PURGE CARD SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7850A1064 EC7850A1072 EC7850A1080 EC7850A1122 120VAC 50/60 HZ RM7850A1001 RM7850A1027 RM7850A1019 O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DESCRIPTION DYNAMIC AIR DAMPER CHECK POST-PURGE 2 SECONDS POST-PURGE 30 SECONDS POST-PURGE 15 SECONDS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE - CE APPROVAL O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7061A, F, M** C7061A, F, M** C7076A, F SELECT A FLAME AMPLIFIER * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. ** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 1.) 2.) 3.) 4.) 5.) 70-6910 739 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7823 FLAME SWITCH RELAY MODULES: M15520F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7823A1004 120VAC 50/60 HZ RM7823A1016 O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION *** 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E,F** C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M** C7061A, F, M** C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. ** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 740 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7824A 24VDC PRIMARY CONTROL RELAY MODULES: M15521D SELECT A SUBBASE SELECT A FLAME AMPLIFIER SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE RM7824A1006 24VDC O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7824C1002 R7851B1000 R7851B1018 R7852A1001 R7852B1009 DESCRIPTION 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT CHECKING DYNAMIC SELF-CHECK AMPLICHECK® AMPLICHECK® NONE AMPLICHECK® O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH C7024E, F C7927, C7962 C7927, C7962 C7915 C7915 1.) 2.) 3.) 4.) 70-6910 741 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7885 MANUAL START PRIMARY RELAY MODULES: M15522F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 120VAC 50/60 HZ RM7885A1015 DESCRIPTION SEMI AUTOMATIC PRIMARY O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION*** 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 742 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7888A SPECIAL FUNCTION PRIMARY CONTROL RELAY MODULES: M15523F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 120VAC 50/60 HZ RM7888A1019 RM7888A1027 DESCRIPTION INDUSTRIAL PRIMARY CONTROL (COMPONENT UL APPROVED) INDUSTRIAL PRIMARY CONTROL (COMPONENT UL APPROVED) O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 743 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7890 ON/OFF PRIMARY CONTROL RELAY MODULES: M15524G SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7890A1011 EC7890B1010 120VAC 50/60 HZ RM7890A1015 RM7890A1031 RM7890A1056 RM7890A1064‡ RM7890B1014 RM7890B1030 RM7890B1048 RM7890B1055++ RM7890C1005 RM7890D1004 DESCRIPTION 30 SECOND PFEP FOR VALVE PROVING APPLICATIONS WITH SHUTTER DRIVE WITH SHUTTER DRIVE AND FULL PFEP WITH SHUTTER DRIVE - FOR VALVE PROVING APPLICATIONS WITH SHUTTER DRIVE STANDING PILOT APPLICATIONS WITH FLAME RODS ONLY INFRARED HEATER ONLY 15 OR 30 PREF O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VP TIMINGS) SPANISH (REQUIRED TO PROGRAM VP TIMINGS) O.S. NO. S7810A1009 S7810M1003 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE MODBUS MODULE - CE APPROVED O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION*** 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F** C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M** C7061A, F, M** C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. ** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. *** FFRT FOR CE APPROVED CONTROLS 1 SEC. OR 2 SEC. ‡ CE APPROVED ++ NORTH AMERICAN AND CE APPROVED 744 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7895 ON/OFF WITH PURGE PRIMARY RELAY MODULES: M15525F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7895A1010 EC7895C1000 120VAC 50/60 HZ RM7895A1014 RM7895A1048 RM7895B1013 RM7895C1012 RM7895C1020 RM7895D1011 RM7895E1002 DESCRIPTION EARLY SPARK TERMINATION DYNAMIC AIRFLOW SWITCH CHECK EARLY SPARK TERMINATION DYNAMIC AIRFLOW SWITCH CHECK INFRARED HEATER APPLICATIONS, 15/30 SECOND PFEP O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) INTERRUPTED PILOT INTERMITTENT PILOT SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7851A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION*** 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F** C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M** C7061A, F, M** C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. ** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 70-6910 745 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7896 ON/OFF WITH PRE- AND POST-PURGE PRIMARY RELAY MODULES: M13908B SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 120VAC 50/60 HZ RM7896A1012 RM7896B1011 RM7896C1010 RM7896D1019 RM7896D1027 DESCRIPTION DYNAMIC AIRFLOW SWITCH CHECK DYNAMIC AIRFLOW SWITCH CHECK 5 SEC EARLY SPARK TERMINATION, DYNAMIC AIRFLOW SWITCH CHECK AND 60 SEC POST-PURGE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) INTERRUPTED PILOT INTERMITTENT PILOT SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7851A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION*** 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 746 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7897 ON/OFF WITH PRE- AND PROGRAMMABLE POST-PURGE PRIMARY RELAY MODULES: M15526H SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION INTERMITTENT/INTERRUPTED PILOT AND PROOF OF CLOSURE INTERRUPTED PILOT WITH DELAYED MV2 AND PROOF OF CLOSURE INTERRUPTED PILOT WITH DELAYED MV2 AND PROOF OF CLOSURE 5 SEC MFEP O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO SET POST PURGE TIME) SPANISH (REQUIRED TO SET POST PURGE TIME) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7897A1002 RM7897C1000 RM7897C1018 O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 747 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7898 ON/OFF WITH PRE- AND PROGRAMMABLE POST-PURGE PRIMARY RELAY MODULES FOR VALVE PROVING APPLICATIONS: M23254C SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION INTERMITTENT/INTERRUPTED PILOT AND PROOF OF CLOSURE INTERMITTENT/INTERRUPTED PILOT WITH EARLY SPARK TERMINATION AND PROOF OF CLOSURE O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) SPANISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7898A1000 RM7898A1018 O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 748 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7838A MANUAL START WITH PURGE INDUSTRIAL PRIMARY RELAY MODULE: M15527F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7838A1014 O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 749 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7838B MANUAL START INDUSTRIAL PROGRAMMER RELAY MODULE: SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION SEMI-AUTOMATIC PROGRAMMER WITH: S7800A1001 KEYBOARD DISPLAY STANDARD S7800A1142 KEYBOARD DISPLAY STANDARD - HAS VALVE PROVING FEATURE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK M15528F O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7838B1013* RM7838B1021* SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * ALARM SOUNDS UNTIL FLAME SENSED * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 750 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7838C MANUAL START INDUSTRIAL PROGRAMMER RELAY MODULE: SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION SEMI-AUTOMATIC PROGRAMMER WITH: S7800A1001 KEYBOARD DISPLAY STANDARD S7800A1142 KEYBOARD DISPLAY STANDARD - DEVICE HAS VALVE PROVING FEATURE S7800A1001 KEYBOARD DISPLAY STANDARD O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK M18830F O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) SPANISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E,E C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800C1003 ST7800C1011 ST7800C1029 ST7800C1037 ST7800C1045 ST7800C1052 DESCRIPTION TIMING: 7 SECOND TIMING: 20 SECOND TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 8 MINUTE TIMING: 10 MINUTE O.S. NO. ST7800C1086 ST7800C1102 ST7800C1128 ST7800C1136 ST7800C1144 DESCRIPTION TIMING: 16 MINUTE TIMING: 20 MINUTE TIMING: 24 MINUTE TIMING: 30 MINUTE TIMING: 45 MINUTE 120 VAC 50/60 HZ RM7838C1004* RM7838C1012* RM7838C1020*+ SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * ALARM OUTPUT - LOCKOUT ONLY +NORTH AMERICAN AND CE APPROVED * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 751 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR UL/CSA RM78XXG,M PROGRAMMER RELAY MODULE: M15529F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGEUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120VAC 50/60 HZ RM7800G1018 RM7840G1014 RM7840G1022 RM7800M1011 RM7840M1017 DESCRIPTION MODULATING BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULE STANDARD MODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE MODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE - FOR VALVE PROVING ON-OFF BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULE STANDARD ON-OFF BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 752 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE: M34645 SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120VAC 50/60 HZ RM7845A1001 DESCRIPTION WITHOUT KEYBOARD DISPLAY (LESS IGNITION AND 15 SECOND MFEP PILOT TERMINALS) SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 753 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE: M15530G SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C FLAME ROD FLAME ROD FLAME ROD* FLAME ROD*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120VAC 50/60 HZ RM7800E1010 RM7840E1016 RM7800L1012 RM7840L1018 RM7800L1053 RM7840L1026 RM7800L1087 RM7840L1075 DESCRIPTION ENERGY SAVING PURGE, S7800A1001 KEYBOARD DISPLAY STANDARD ENERGY SAVING PURGE WITHOUT KEYBOARD DISPLAY S7800A1001 KEYBOARD DISPLAY STANDARD WITHOUT KEYBOARD DISPLAY INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD INTERMITTENT PILOT WITHOUT KEYBOARD DISPLAY S7800A1142 KEYBOARD DISPLAY STANDARD - WITH VALVE PROVING FEATURE WITHOUT KEYBOARD DISPLAY - WITH VALVE PROVING FEATURE SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) * FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 754 70-6910 Microprocessor Burner Controls EC7820 Primary Control Meeting European Community Timings Integrated burner control for automatically fired gas, oil, or combination, single burner atmospheric with fan applications. Has automatic burner sequencing, flame supervising system status indication, system or self-diagnostics, and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. Interchangeable plug-in amplifiers. • Local or remote annunciation of operation and fault information (optional). • Non-volatile memory retains history files and lockout status after loss   of power. • Compatible with existing Honeywell flame detectors. Application: Primary Control Interlocks: Lockout Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 5 sec Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 60 Hz (±10%), 50 Hz AirFlow Check: User selectable Second Stage Pilot Valve: Intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Approvals, Gastec/European: GASTEC: CE-63AP3070/1, Approved to EN298. Dimensions in inches (millimeters) 5 5 BURNER CONTROL 5 1/2 M12821 1 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. Material Number Voltage Pilot Type Flame Establishing Period - Main Flame Establishing Period - Pilot Comments EC7820A1026/U 220 to 240 Vac (+10, -15%) interrupted 5 sec, or 8 sec, or Intermittent 5 sec or 10 sec 1 ignition attempt, Includes Modulation w/ Fan Output EC7820A1034/U 220 to 240 Vac (+10, -15%) interrupted 5 sec, or 8 sec, or Intermittent 5 sec or 10 sec 5 ignition attempts, Includes Modulation w/ Fan Output 70-6910 755 Commercial/Industrial Combustion Controls Microprocessor Burner Controls EC7830; EC7850; RM7830; RM7850 Programming Control Meeting European Community Timings Microprocessor-based integrated burner control for full modulation applications. Provides automatic burner sequencing, flame supervision, system status indication, system or selfdiagnostics, and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in amplifiers. • Local or remote annunciation of operation and fault information (optional). • Non-volatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. Application: Programming Control Flame Establishing Period - Main: 3 sec, or 5 sec, or Intermittent Flame Establishing Period - Pilot: 3 sec or 5 sec Interlocks: Lockout Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card Early Spark Termination: Yes, 5 sec Required Components: Q7800A,B Universal Wiring Subbases. R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. AirFlow Check: User selectable Second Stage Pilot Valve: Intermittent Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: EC7830, EC7850, RM7830-Report No. 1V9AO.AF; RM7850-Report No. J.I. OYOA9.AF Approvals, Gastec/European: GASTEC: CE-63AP3070/1, Approved to EN298. Dimensions in inches (millimeters) 5 (127) 5 (127) BURNER CONTROL 1 5-1/4 (133) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. M15532A 6-3/32 (155) 1 Material Number Voltage Frequency PostPurge Comments EC7830A1033/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec On/Off Power Burner EC7830A1041/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec On/Off Power Burner EC7830A1066/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 15 sec On/Off Power Burner EC7850A1064/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec LHL-LF & HF Proven; Dynamic damper check EC7850A1072/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec LHL-LF & HF Proven EC7850A1080/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec LHL-LF & HF Proven EC7850A1122/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 15 sec LHL-LF & HF Proven EC7850A1148/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec LHL-LF & HF Proven RM7830A1003/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 2 sec On/Off Power Burner RM7830A1011/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 15 sec On/Off Power Burner RM7830A1029/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 30 sec On/Off Power Burner RM7850A1001/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 2 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC). RM7850A1019/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 15 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC). RM7850A1027/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 30 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC). 756 70-6910 Microprocessor Burner Controls RM7800 Programmers Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information (optional). • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. • Includes Keyboard Display Module. Application: Programming Control Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Second Stage Pilot Valve Interlocks Comments RM7800E1010/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800 Display, LHL-LF & HF Proven RM7800G1018/U 120 Vac (+10, -15%) 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec selectable Running Includes S7800 Display, LHL-LF Proven RM7800L1012/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800 Display, LHL-LF & HF Proven RM7800L1053/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Intermittent Lockout Includes S7800 Display, LHL-LF & HF Proven RM7800M1011/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Intermittent Running Includes S7800 Display, On/Off-LF proven 70-6910 757 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7800 Programmers with VPS Integrated burner control for gas, oil, coal or combination fuel single burner uses. With Valve Proving Feature. RM7800L comes standard with S7800A1142 Keyboard Display. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. Power LED blinks fault code on Lockout. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information (optional). • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. • RM7800 comes with S7800A1142 Keyboard Display Module. • Keyboard required to setup Valve Proving Feature and change post purge time. Application: Programming Control w/VPS Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Factory Mutual: Report No. 1V9AO.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Second Stage Pilot Valve Interlocks Comments RM7800L1087/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800A1142 Display, LHL-LF & HF Proven 758 70-6910 Microprocessor Burner Controls RM7823; EC7823 Flame Switch Dimensions in inches (millimeters) POWER FLAME ALARM RESET 5 (127) 5 (127) M2649 BURNER CONTROL 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) Microprocessor-based integrated flame switch for detecting a flame using rectification, ultraviolet (UV) or infrared (IR) source. Provides level of safety, functional capability and features beyond conventional controls. • Can be fitted with any 7800 Series Amplifier to provide relay action from two single pole, double throw (SPDT) relays when flame is present or not present. RM7823A and EC7823 are a flame detector relays only. • Suitable primary control must be used to provide safe-start check, safety lockout, load switching and other functions required in flame safeguard systems. • Three LEDs to indicate power, flame and alarm. • Access for external electrical voltage checks. • Nonvolatile memory. • Shutter drive output. • Compatible with existing Honeywell flame detectors. Application: Flame Switch Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Swiss RE: Acceptable Comments: two SPDT outputs Material Number Voltage Frequency Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, FCC Approvals, Factory Mutual EC7823A1004/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz Report No. OY0A9.AF. RM7823A1016/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. FCC Part 15, Class B, Emissions. Report No. OX4A5.AF. 70-6910 759 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7824 On-Off Primary Control Dimensions in inches (millimeters) 5 (127) 5 (127) M5872 BURNER CONTROL 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 24 Vdc microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications. Provides level of safety, functional capability and features beyond the capacity of conventional controls. • For use with R7824C Amplifier with C7024E, F Flame Detectors; R7848A, B with C7015A Flame Detectors; R7851B with C7927, C7962 Flame Detectors; or R7852A, B with C7915 Flame Detectors. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Five LEDs provide sequence information. • Selectable recycle or lockout on loss of flame. • Shutter drive output for use with dynamic self-check flame detectors. • Access for external electrical voltage checks. • Plug-in flame amplifier. • Nonvolatile memory retains history files and lockout status after loss of power. Application: Primary Control 24 Vdc Required Components: Q7800A, B Universal Wiring Subbases. R7824 or R7848 Flame Signal Amplifier. Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot RM7824A1006/U 24 Vdc (+10, -15%) Intermittent 4 sec or 10 sec 760 70-6910 Microprocessor Burner Controls RM7838A Manual Start Industrial Primary Control with Purge Microprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include purge, burner pilot startup, flame supervision, system status indication, system or self diagnosis and troubleshooting. • Delays admission of fuel to combustion chamber until pilot flame has been proven and then monitors the flame through the run period while providing system status indication. • Includes Keyboard Display Module. • Five LEDs provide sequence information. • Intermittent pilot valve. • Interchangeable plug-in flame amplifier. • Access for external electrical voltage checks. • Nonvolatile memory retains history files and lockout status after loss of power. • Selectable pilot flame establishing period. • Provides application flexibility and optional communication interface capability. • Compatible with existing Honeywell flame detectors. Application: Semi Automatic Primary Control with Purge Interlocks: Running PrePurge: Determined by ST7800A Purge Timer Card Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7838A1014/U 120 Vac (+10, -15%) Intermittent 4 sec or 10 sec Includes S7800 Display 70-6910 761 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7838B, C Manual Start Industrial Programmers Microprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include purge, burner pilot startup, flame supervision, system status indication, system or self diagnosis and troubleshooting. • Delays admission of fuel to combustion chamber until pilot flame has been proven and then monitors the flame through the run period while providing system status indication. • Includes Keyboard Display Module. • Five LEDs provide sequence information. • Intermittent pilot valve. • Interchangeable plug-in flame amplifier. • Access for external electrical voltage checks. • Nonvolatile memory retains history files and lockout status after loss of power. • Selectable pilot flame establishing period. • Provides application flexibility and optional communication interface capability. • Compatible with existing Honeywell flame detectors. Application: Semi Automatic Programming Control Interlocks: Lockout Preignition: Yes Early Spark Termination: Yes, 5 sec Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot PrePurge Required Components Approvals, Gastec/European Comments RM7838B1013/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800A Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Includes S7800 Display RM7838C1004/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800C Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800C Plug-in Purge Timer Card. Includes S7800 Display RM7838C1020/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800C Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800C Plug-in Purge Timer Card. Gastec EN268 Report 1156791 Includes S7800 Display 762 70-6910 Microprocessor Burner Controls RM7838B, C Manual Start Industrial Programmers with VPS Integrated burner control for industrial semi-automatically fired gas, oil, coal or combination fuel single burner applications. Includes Valve Proving Feature with S7800A1142 Keyboard Display. • Functions include purge, burner pilot startup, flame supervision, system status indication, system or self diagnosis and troubleshooting. • Delays admission of fuel to combustion chamber until pilot flame has been proven and then monitors the flame through the run period while providing system status indication. • Includes S7800A1142 Keyboard Display Module. • Five LEDs provide sequence information. • Intermittent pilot valve. • Interchangeable plug-in flame amplifier. • Access for external electrical voltage checks. • Nonvolatile memory retains history files and lockout status after loss of power. • Selectable pilot flame establishing period. • Provides application flexibility and optional communication interface capability. • Compatible with existing Honeywell flame detectors. • With Valve Proving Feature and Programmable Post Purge Time. • Power LED blinks a fault code on system lockout. Application: Semi Automatic Programming Control w/VPS Interlocks: Lockout Preignition: Yes PostPurge: programmed with S7800A1142 display Early Spark Termination: Yes, 5 sec Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot PrePurge Required Components Comments RM7838B1021/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800A Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Includes programmable VPS (Valve Proving Switch) check feature and blinking LED fault annunciation RM7838C1012/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800C Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800C Plug-in Purge Timer Card. Includes programmable VPS (Valve Proving Switch) check feature and blinking LED fault annunciation 70-6910 763 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7840 Programmers Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of RM7840 operation and fault information. • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. Application: Programming Control Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Interlocks Second Stage Pilot Valve Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7840E1016/U Lockout Interrupted 10 sec or 15 sec 4 sec or 10 sec LHL-LF & HF Proven RM7840G1014/U Running selectable 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec LHL-LF Proven RM7840L1018/U Lockout Interrupted 10 sec or 15 sec 4 sec or 10 sec LHL-LF & HF Proven RM7840L1026/U Lockout Intermittent 10 sec or Intermittent 4 sec or 10 sec LHL-LF & HF Proven RM7840M1017/U Running Intermittent 10 sec or Intermittent 4 sec or 10 sec On/Off-LF Proven 764 70-6910 Microprocessor Burner Controls RM7840 Programmers with VPS Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Integrated burner control for gas, oil, coal or combination fuel single burner uses. Provides safety, functional capability and features beyond normal controls. With Valve Proving Feature. Requires S7800A1142 Keyboard Display. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. Power LED blinks fault code on Lockout. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information (optional). • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. • RM7800 comes with S7800A1142 Keyboard Display Module. • Keyboard required to setup Valve Proving Feature and change post purge time. Application: Programming Control w/VPS Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Second Stage Pilot Valve: selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, FCC: FCC Part 15, Class B, Emissions. Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Interlocks Comments Approvals, Underwriters Laboratories Inc. Approvals, Factory Mutual EC7840L1014/U 220 to 240 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Lockout Requires S7800A1142 Display, LHL-LF & HF Proven RM7840G1022/U 120 Vac (+10, -15%) 10 sec, 15 sec, 30 sec, or Intermittent 4 sec or 10 sec Running Requires S7800A1142 Display, LHL-LF Proven Component Recognized, File No. MP268; Guide No. MCCZ. Report No. 1V9AO.AF. RM7840L1075/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Lockout Requires S7800A1142 Display, LHL-LF & HF Proven Component Recognized, File No. MP268; Guide No. MCCZ. Report No. 1V9AO.AF. 70-6910 765 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7845 Programmers Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of RM7840 operation and fault information. • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. Application: Programming Control Interlocks: Lockout Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7845A1001/U 10 sec 4 sec or 10 sec LHL-LF & HF Proven RM7885; EC7885 Manual Start Industrial Primary Control Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Adaptable to continuous firing, high-low or modulating firing rate for semi-automatic burner sequencing. • Operates with the following: Torch-ignited main burner or torchignited pilot using S445A Start-Stop Station, or conventional knee or foot operated station. • Direct-ignition oil burner or electrically ignited pilot, using S445A Start-Stop Station. • Five LEDs provide sequence information. • Nonvolatile memory. • Flame signal check during standby. • Shutter drive output. • Compatible with existing Honeywell flame detectors. • Terminal provided for external alarm to sound on flame failure. Application: Semi Automatic Primary Control Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot RM7885A1015/U 120 Vac (+10, -15%) Intermittent 15 min 766 70-6910 Microprocessor Burner Controls RM7888 PLC Adaptable Primary Control Dimensions in inches (millimeters) BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET SCROLL MODE SAVE 5 (127) 5 (127) M9494 5-1/4 (133) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 Integrated burner control for industrial process semi-automatically fired gas, oil, coal, or combination fuels for single and multiple burner applications. PLC Adaptable. • Functions include automatic burner startup sequencing, five user selectable run sequences, four line-voltage sequence control inputs, flame supervision, system status indication, system or selfdiagnostics and troubleshooting. • Requires a relay module, subbase, and amplifier for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display mounting, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Use with master system control which determines purge timing and confirms air supply and air flow. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. Application: Primary Control - PLC Adaptable Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: selectable Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, CSA: Certified Approvals, Factory Mutual: Approved. Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7888A1019/U 15 sec 4 sec Selectable sequences RM7888A1027/U 15 sec 10 sec For 10 sec DSI applications, selectable sequences 70-6910 767 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7890 On-Off Primary Control with VPS Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Integrated on/off primary burner control for automatically fired gas, oil or combination fuel single burner applications. Contains Valve Proving Feature. Requires S7800A1142 Display to program VPS feature. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Subbase and amplifier are required for operation. • Power LED blinks Fault Code on lockout. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Optional local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable relight or lockout on loss of flame. • Contains Valve Proving Feature - require S7800A1142 Keyboard Display (not provided) to set up. Application: On-Off Primary Control w/VPS Preignition: Yes Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7890A1056/U Intermittent 4 sec or 10 sec Includes programmable VPS (Valve Proving Switch) check feature and blinking LED fault annunciation RM7890B1048/U Intermittent 4 sec or 10 sec Includes Shutter Drive Capability, VPS (Valve Proving Switch) check and blinking LED fault annunciation 768 70-6910 Microprocessor Burner Controls RM7890; EC7890 On-Off Primary Controls Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated primary burner control for automatically fired gas, oil or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Subbase and amplifier are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Optional local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable relight or lockout on loss of flame. Application: On-Off Primary Control Flames Establishing Period - Main: Intermittent Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Swiss RE: Acceptable Material Number Voltage Flame Establishing Period - Pilot Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual Approvals, Gastec/ European Comments EC7890A1011/U 220 to 240 Vac (+10, -15%) 4 sec or 10 sec Report No. 1D0A1.AF EC7890B1010/U 220 to 240 Vac (+10, -15%) 4 sec or 10 sec Report No. 1D0A1.AF Includes Shutter Drive Capability EC7890B1028/U 220 to 240 Vac (+10, -15%) 4 sec or 10 sec Report No. 1V9AO.AF. Includes Shutter Drive Capability RM7890A1015/U 120 Vac (+10, -15%) 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. RM7890A1031/U 120 Vac (+10, -15%) 30 sec fixed Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. RM7890A1064/U 120 Vac (+10, -15%) 4 sec or 10 sec Report No. 1D0A1.AF GASTEC: CE-63AP3070/1, Approved to EN298. RM7890B1014/U 120 Vac (+10, -15%) 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Includes Shutter Drive Capability RM7890B1030/U 120 Vac (+10, -15%) Fixed 4 sec or 10 sec PFEP Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Includes Shutter Drive Capability, Alarm sounds when Reset pushed. RM7890B1055/U 120 Vac (+10, -15%) 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Gastec EN268 Report 1156791 Includes Shutter Drive Capability RM7890D1004/U 120 Vac (+10, -15%) 15 sec or 30 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Higher Flame Sensor Voltage for Infra Red Heater Applications 70-6910 769 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7895; EC7895 On-Off Primary Control with Prepurge Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Subbase, amplifier, and prepurge timer are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Optional local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. Selectable relight or lockout on loss of flame. • Airflow switch check. Application: On-Off Primary Control with Prepurge Interlocks: Selectable PrePurge: Determined by ST7800A Purge Timer Card Required Components: Q7800 Universal Wiring Subbases, Flame Signal Amplifier and ST7800A Plug-in Purge Timer Card Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Swiss RE: Acceptable Used With: 7800 Series Amplifiers (Except RM7895E1002/U uses R7847 ONLY) Material Number Voltage Pilot Type AirFlow Check Delayed Main Valve Flame Establishing Period - Main Flame Establishing Period - Pilot Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Control Safety Devices Approvals, Factory Mutual Comments EC7895A1010/U 220 to 240 Vac (+10, -15%) intermittent No Intermittent 4 sec or 10 sec Report No. 1D0A1.AF EC7895C1000/U 220 to 240 Vac (+10, -15%) interrupted Yes 10 sec 4 sec or 10 sec Report No. 1D0A1.AF RM7895A1014/U 120 Vac (+10, -15%) intermittent No Intermittent 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895A1048/U 120 Vac (+10, -15%) intermittent No Intermittent 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF Includes ignition cut-out during PFEP and special sequence for early spark termination RM7895B1013/U 120 Vac (+10, -15%) intermittent Dynamic No Intermittent 4 sec to 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895C1012/U 120 Vac (+10, -15%) interrupted Yes 10 sec 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895C1020/U 120 Vac (+10, -15%) interrupted Yes 10 sec 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF Includes ignition cut-out during PFEP and special sequence for early spark termination RM7895D1011/U 120 Vac (+10, -15%) interrupted Dynamic Yes 10 sec 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895E1002/U 120 Vac (+10, -15%) intermittent No Intermittent 15 sec or 30 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF Higher Flame Sensor Voltage for Infra Red Heater Applications 770 70-6910 Microprocessor Burner Controls RM7896 On-Off Primary Control with Pre- and Post-Purge Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated full-function primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Subbase, amplifier and purge card are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • 15 second postpurge. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable recycle or lockout on loss of airflow or flame. • Shutter drive output. • Airflow switch check. • Delayed main valve. Application: On-Off Primary Control with Pre- and Post-purge Interlocks: Selectable PrePurge: Determined by ST7800A Purge Timer Card Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Pilot Type AirFlow Check Flame Establishing Period - Main Flame Establishing Period - Pilot Delayed Main Valve PostPurge Comments RM7896A1012/U intermittent Intermittent 4 sec or 10 sec No 15 sec Includes Pre- and Post-Purge. RM7896C1010/U interrupted 10 sec 4 sec or 10 sec Yes 15 sec Includes Pre- and Post-Purge. RM7896D1019/U interrupted Dynamic 10 sec 4 sec or 10 sec Yes 15 sec Includes Pre- and Post-Purge. RM7896D1027/U interrupted Dynamic 10 sec 4 sec or 10 sec Yes 60 sec Blinking Fault code LED, early spark termination when flame sensed, pre- and post-purge 70-6910 771 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7897 Automatic Primary Control with Programmable Post-Purge Microprocessor-based integrated full-function primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Programmable Post-Purge. Requires S7800A1142 Display to program post-purge feature. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Subbase, amplifier and purge card are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. Power LED blinks fault code on Safety Shutdown. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable recycle or lockout on loss of airflow or flame. • Shutter drive output. • Airflow switch check. • Delayed main valve. • Programmable post-purge using S7800A1142 Keyboard Display (not provided). Application: On-Off Primary Control with Pre- and Programmable Post-purge Flame Establishing Period - Pilot: 4 sec or 10 sec Interlocks: Selectable Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Pilot Type Delayed Main Valve Comments Used With RM7897A1002/U 120 Vac (+10, -15%) selectable Includes blinking LED fault annunciation feature 7800 Series Amplifiers RM7897C1000/U 120 Vac (+10, -15%) selectable Yes Includes blinking LED fault annunciation feature 7800 Series Amplifiers 772 70-6910 Microprocessor Burner Controls RM7898 On-Off Primary Control with VPS Integrated full-function primary burner control for gas, oil, or combination fuel single burner applications. Include Programmable Post-Purge and Valve Proving Feature. Requires S7800A1142 Display to program VPS and post-purge features. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Subbase, amplifier and purge card are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Programmable post-purge. • Five LEDs provide sequence information. Power LED Blinks Fault code on safety shutdown. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable recycle or lockout on loss of airflow or flame. • Shutter drive output. • Airflow switch check. • Programmable post-purge and Valve Proving feature with S7800A1142 Keyboard Display (not supplied). Application: On-Off Primary Control w/VPS Flame Establishing Period - Pilot: 4 sec or 10 sec Interlocks: Selectable Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: selectable Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Pending Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Early Spark Terminations Comments Used With RM7898A1000/U 120 Vac (+10, -15%) Includes blinking LED fault annunciation feature 7800 Series Amplifiers RM7898A1018/U 120 Vac (+10, -15%) Special Sequence Includes blinking LED fault annunciation feature, with early spark termination 7800 Series Amplifiers 70-6910 773 Commercial/Industrial Combustion Controls Microprocessor Burner Controls R7120M Fireye M Series Replacement Control The Honeywell R7120M Burner Control Modules are microprocessor-based integrated burner controls. It is a plug in replacement of Fireye M series controls for automatically fired gas, oil or combination fuel on/off single burner applications. • Functions provided by the R7120M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Plug in replacement for Fireye M series controls using the existing Fireye wiring subbase. • Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement. Application: Replacement Primary Control for Fireye M Series - Intermittent Pilot Interlocks: Running PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Required Components: R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +135°F (-40°C to +57°C) Approximate, Dimensions: 7 in. wide x 6 5/32 in. high x 5 3/4 in. deep (177 mm wide x 156 mm high x 146 mm deep) Weight lb. (kg): 3 lb 1 oz (1.4 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, FCC: FCC Part 15, Class B, Emissions. Material Number Voltage Pilot Type AirFlow Check Flame Establishing Period - Main Flame Establishing Period - Pilot Comments R7120M1001/U 120 Vac (+10, -15%) intermittent User selectable Intermittent 4 sec or 10 sec On/Off R7120M1019/U 120 Vac (+10, -15%) interrupted User selectable 10 sec 4 sec or 10 sec On/Off 774 70-6910 Microprocessor Burner Controls R7140 Programmers Dimensions in inches (millimeters) 5-3/4 (146) 1-1/4 (32) RESET POWER PILOT FLAME MAIN ALARM S _ + 5 (127) 5 (127) 7 (177) 6-5/32 (156) BURNER CONTROL M22604A The Honeywell R7140G, L, M Burner Control Modules are microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications. • Functions provided by the R7140G, L, M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Upgrade replacement for BC7000 or R4140 legacy Programmer controls. • Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement. Application: Upgrade Replacement Programming Control for R4140 or BC7000 Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Early Spark Termination: Yes, 5 sec Required Components: R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 7 in. wide x 6 5/32 in. high x 5 3/4 in. deep (177 mm wide x 156 mm high x 146 mm deep) Weight lb. (kg): 3 lb 1 oz (1.4 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, FCC: FCC Part 15, Class B, Emissions. Material Number Pilot Type Flame Establishing Period - Main Flame Establishing Period - Pilot Second Stage Pilot Valve Interlocks Comments R7140G1000/U Interrupted or Intermittent 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec selectable Running LHL-LF Proven R7140G2008/U Interrupted or Intermittent 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec Running LHL-LF Proven R7140L1009/U interrupted 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout LHL-LF & HF Proven R7140L2007/U interrupted 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout LHL-LF & HF Proven R7140M1007/U Interrupted or Intermittent 10 sec or Intermittent 4 sec or 10 sec Intermittent Running On/Off-LF Proven 70-6910 775 Commercial/Industrial Combustion Controls Microprocessor Burner Controls Q7800 22 Terminal Universal Wiring Subbases Burner, panel or wall mount subbases for 7800 SERIES relay modules and S7830A Expanded Annunciator. • Makes electrical connections for 7800 SERIES relay modules or S7830A Expanded Annunciator through bifurcated contacts. • Provides terminals for field wiring. • Twenty-two terminals. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approvals, CSA: Certified, File No. LR95329-3. Material Number Application Approximate, Dimensions Weight lb. (kg) Approvals, Underwriters Laboratories Inc. Comments Used With Q7800A1005/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in. deep (126 mm wide x 126 mm high x 36 mm deep) 7 oz (0.20 kg) Component Recognized, File No. MP268; Guide No. MCCZ2. Panel mount Q7800B1003/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in. deep (126 mm wide x 126 mm high x 36 mm deep) 1 lb 3 oz (0.54 kg) Component Recognized, File No. MP268; Guide No. MCCZ. Burner/wall mount 2 knockouts each end Q7800B1011/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 3 in. deep (126 mm wide x 126 mm high x 76 mm deep) 1 lb 3 oz (0.54 kg) Component Recognized, File No. MP268; Guide No. MCCZ. Burner/wall mount 3 knockouts each end Q7800F1004/U Wiring Adapter Subbase 5 in. high x 5 in. wide x 1 3/4 in. deep (127 mm high x 127 mm wide x 44 mm deep) 15 oz (0.43 kg) Component Recognized, File No. MP268; Guide No. MCCZ2. Burner/wall mount adapter subbase for RA890 RM7890 Q7800F1012/U Wiring Adapter Subbase 5 in. high x 5 in. wide x 1 3/4 in. deep (127 mm high x 127 mm wide x 44 mm deep) 15 oz (0.43 kg) Component Recognized, File No. MP268; Guide No. MCCZ2. Burner/wall mount adapter subbase for R4795 RM7895 Q7800A dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F USE NO. 6 MOUNTING SCREWS (4) M1968D 1 OPTIONAL TERMINAL TEST ACCESS COVER. 4-31/32 (126) 2-1/2 (64) 1-11/32 (34) 1-11/32 (34) 2-9/32 (58) 4-31/32 (126) 1-13/32 (36) 1 Q7800F dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F (11) 5 (127) 5 (127) M5648A 1-3/4 (44) 1/4 (6) 776 70-6910 Microprocessor Burner Controls Q7800B1003 dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F 7/8 in. DIA. KNOCKOUTS (7) FOR 1/2 in. CONDUIT USE NO. 6 MOUNTING SCREWS (4) 1 (25) 1 (25) M1966B REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 1 2-1/8 (54) 2-1/4 (64) 1-11/32 (34) 1-11/32 (34) 1-13/32 (36) 4-31/32 (126) 4-31/32 (126) 1-5/8 (41) 27/32 (21) 2-9/32 (58) 23/32 (18) 3/4 (19) 2-1/8 (54) 2-7/32 (56) 23/32 (18) 1/2 (12) Q7800B1011 dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F 7/8 in. (22) KNOCKOUTS (9) FOR 1/2 in. CONDUIT USE NO. 6 MOUNTING SCREWS (4) 1 (25) 1 (25) M9883 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 1 2-1/8 (54) 2-1/4 (64) 1-11/32 (34) 1-11/32 (34) 1-13/32 (36) 4-31/32 (126) 4-31/32 (126) 1-5/8 (41) 27/32 (21) 2-9/32 (58) 23/32 (18) 3/4 (19) 3/4 (19) 2-1/8 (54) 3 (76) 23/32 (18) 3/4 (19) 3/4 (19) 70-6910 777 Commercial/Industrial Combustion Controls Microprocessor Burner Controls S7800 Keyboard Display Module Dimensions in inches (millimeters) 2 -1 /3 2 (5 2 ) BURNER CONTROL 29/32 (23) 19/32 (15) 1-1/4 (32) 1-1/32 (26) 5/32 (4) 5/16 (8) M22870 1/2 (13) 7/16 (11) 1-5/16 (49) 2-7/16 (62) 29/32 (23) 5/32 (4) 15/32 (12) 3-7/8 (99) 5/16 13/ (8) 32 (11) BACK ENTER Edit: - + 4-27/32 (123) 4-3/32 (104) 2-3/4 (69) Provides current status of burner sequence, timing information, hold information and lockout information, as well as selectable or preemptive messages. • Application flexibility. • First-out annunciation and system diagnostics provided by 2 row by 20 column Vacuum Fluorescent Display (VFD). • S7800A1001 offers “Call Service” (Business Card) programmable message displayed when system lockout occurs. • S7800A1001 series 5 and greater has selectable ModBus Feature. • Local or remote annunciation of operation and fault information. • First out expanded annunciation with 24 limit and interlock LEDs enhances keyboard display module information. • Remote reset. Application: Keyboard Display Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Comments S7800A1001/U 13 Vdc peak fullwave rectified (+20/-15%). English Language S7800A1035/U 13 Vdc peak fullwave rectified (+20/-15%). French Language S7800A1043/U 13 Vdc peak fullwave rectified (+20/-15%). German Language S7800A1050/U 13 Vdc peak fullwave rectified (+20/-15%). Italian Language S7800A1068/U 13 Vdc peak fullwave rectified (+20/-15%). Spanish Language S7800A1118/U 13 Vdc peak fullwave rectified (+20/-15%). Japanese Language S7800A1126/U 13 Vdc peak fullwave rectified (+20/-15%). Portuguese Language 778 70-6910 Microprocessor Burner Controls S7800 Keyboard Display Module for VP Programming Dimensions in inches (millimeters) 2 -1 /3 2 (5 2 ) BURNER CONTROL 29/32 (23) 19/32 (15) 1-1/4 (32) 1-1/32 (26) 5/32 (4) 5/16 (8) M22870 1/2 (13) 7/16 (11) 1-5/16 (49) 2-7/16 (62) 29/32 (23) 5/32 (4) 15/32 (12) 3-7/8 (99) 5/16 13/ (8) 32 (11) BACK ENTER Edit: - + 4-27/32 (123) 4-3/32 (104) 2-3/4 (69) Provides current status of burner sequence, timing information, hold information and lockout information, as well as selectable or preemptive messages. • Application flexibility. • First-out annunciation and system diagnostics provided by 2 row by 20 column Vacuum Fluorescent Display (VFD). • “Call Service” (Business Card) programmable message displayed when system lockout occurs. • Local or remote annunciation of operation and fault information. • First out expanded annunciation with 24 limit and interlock LEDs enhances keyboard display module information. Display can be Programmed to customize the expanded annunciator messages to the system. • Required to program Valve Proving and Post Purge feature on selected 7800 Series devices. • Can be setup for ModBus Communication. • Provides burner controller data. • Remote reset. Application: Keyboard Display for VP setup Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Comments S7800A1142/U 13 Vdc peak fullwave rectified (+20/-15%). English Language, Capable of displaying special “Call Service” messages, allows setup of S7830A1005 Expanded Annunciator messages, used for VPS programming, and programming Post Purge on select 7800 Devices S7800A1167/U 13 Vdc peak fullwave rectified (+20/-15%). Spanish Language with Valve Proving, Post-purge, “Call Service”, and Expanded Annunciator programming ability 70-6910 779 Commercial/Industrial Combustion Controls Microprocessor Burner Controls S7810A Data ControlBus™ Module Dimensions in inches (millimeters) M1986A BURNER CONTROL 2-3/4 (69) 29/32 (23) 5/32 (4) 4-27/32 (123) Supports remote mounting of S7800 Keyboard Display Module, personal computer communications interface and remote reset. • Use with remotely mounted S7800 Keyboard Display Module. • Installs directly on the front of 7800 SERIES Relay Modules. • Provides communications bus interface and remote reset. Application: ControlBus™ Module Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 3 11/32 in. high x 29/32 in. deep (123 mm wide x 84 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Comments S7810A1009/U 13 Vdc peak fullwave rectified (+20/-15%). Includes 203541 5-wire Connector S7810M ModBus Module Dimensions in inches (millimeters) 1-1/8 (29) M11349B 7/16 (11) 2-3/4 (69) 5/32 (4) 4-27/32 (123) 29/32 (23) BURNER CONTROL MODE S7810M ModBus Module operates as ModBus RTU slave device. • Provides ability to remotely mount the S7800 Keyboard Display Module. • Installs directly on the front of 7800 SERIES Relay Modules. • Provides ModBus communications bus interface. • Remote reset. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Application Comments Approvals, Gastec/European S7810M1003/U 13 Vdc peak fullwave rectified (+20/-15%). ControlBus™ Module-MODBUS Includes 208727 8 pin electrical connector S7810M1029/U 13 Vdc peak fullwave rectified (+20/-15%). ControlBus™ Module-MODBUS - CE Certified (no reset allowed) Includes 208727 8 pin electrical connector Gastec EN268 Report 1156791 780 70-6910 Microprocessor Burner Controls S7820 Remote Reset Module Dimensions in inches (millimeters) M1986A BURNER CONTROL 2-3/4 (69) 29/32 (23) 5/32 (4) 4-27/32 (123) Serves as link between remote reset pushbutton and relay module. Allows 7800 SERIES relay module to be reset from a remote location. • Reset button can be installed up to 1000 feet away. • Installs directly on the front of 7800 SERIES relay module. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 3 oz (0.09 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Application Comments S7820A1007/U Remote Reset Module Includes 203541 5-wire Connector 70-6910 781 Commercial/Industrial Combustion Controls Microprocessor Burner Controls S7830 First Out Expanded Annunciator Microprocessor-based expanded annunciator to support the 7800 SERIES relay modules for first-out annunciation, sequencing, system or self-diagnostics and troubleshooting. • Twenty-six status LEDs. • Front panel LED array-arranged to indicate flow of line-voltage through string of limits, controls and interlocks. • Selectable current and first-out LED array display status. • Twenty-one monitored contact points. • Access for external electrical voltage checks. Required Components: 7800 Series Relay Modules and Q7800A, B Subbases Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 6 oz (0.62 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MH17367; Guide No. MJAT. Approvals, CSA: Certified, File No. LR95329. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Dimensions in inches (millimeters) 5 (127) 5-5/16 (135) 5 (127) EXPANDED ANNUNCIATOR M5182 Proof of Closure Preignition Interlocks L1 Burner Switch Power Operating Control Auxiliary Limit 1 Auxiliary Limit 2 Low Water Cutoff High Limit Atomizing Limit 3 Oil Select High Oil Pressure Low Oil Pressure High Oil Temperature Low Oil Temperature Select Atomizing Switch Gas Select High Gas Pressure Low Gas Pressure System Lockout First Out Current Airflow Switch Auxiliary Interlock 4 Auxiliary Interlock 5 Reset Interlocks a b c Fuel Selection 22 21 20 19 18 17 16 15 14 13 12 Material Number Voltage Application S7830A1005/U 120 Vac (+10, -15%) Expanded Annunciator 782 70-6910 Microprocessor Burner Controls ST7800 Plug In Purge Timer Provides the prepurge timing for select 7800 SERIES relay modules. ST7800C used with the RM7838C only. Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Approved: Report No. 2X0A1.AF. Material Number PrePurge Application ST7800A1005/U 2 seconds Purge Timer ST7800A1013/U 7 seconds Purge Timer ST7800A1021/U 10 seconds Purge Timer ST7800A1039/U 30 seconds Purge Timer ST7800A1047/U 40 seconds Purge Timer ST7800A1054/U 60 seconds Purge Timer ST7800A1062/U 90 seconds Purge Timer ST7800A1070/U 2.5 minutes Purge Timer ST7800A1088/U 4.0 minutes Purge Timer ST7800A1096/U 6.0 minutes Purge Timer ST7800A1104/U 9.0 minutes Purge Timer ST7800A1112/U 12.0 minutes Purge Timer ST7800A1120/U 15.0 minutes Purge Timer ST7800A1138/U 22.0 minutes Purge Timer ST7800A1146/U 30.0 minutes Purge Timer ST7800C1003/U 7 seconds Purge Timer for RM7838C Only ST7800C1011/U 20 seconds Purge Timer for RM7838C Only ST7800C1029/U 4.0 minutes Purge Timer for RM7838C Only ST7800C1037/U 6.0 minutes Purge Timer for RM7838C Only ST7800C1045/U 8.0 minutes Purge Timer for RM7838C Only ST7800C1052/U 10.0 minutes Purge Timer for RM7838C Only ST7800C1086/U 16.0 minutes Purge Timer for RM7838C Only ST7800C1102/U 20.0 minutes Purge Timer for RM7838C Only ST7800C1128/U 24.0 minutes Purge Timer for RM7838C Only ST7800C1136/U 30.0 minutes Purge Timer for RM7838C Only 70-6910 783 Commercial/Industrial Combustion Controls Microprocessor Burner Controls 7800 Series Accessories or Parts Application: Accessory or Replacement Part Material Number Comments Used With 203541/U S7800 Display 203765/U Includes 203541 5-wire Connector S7800 Display 204718A/U Includes 203541 5-wire Connector S7800 Display 204718B/U Includes 203541 5-wire Connector S7800 Display 204718C/U Includes 203541 5-wire Connector S7800 Display 205321B/U Includes 203541 5-wire Connector S7800 Display 206311/U Carrying Case for S7800 Display S7800 Display 208727/U S7810B, S7810M 221729A/U 7800 Relay Modules 221818A/U S7800 Display 221818C/U S7800 Display 50023821-001/U Includes 203541 5-wire Connector S7800 Display 50023821-002/U Includes 203541 5-wire Connector S7800 Display 784 70-6910 SOLA Controllers SOLA™ Hydronic Control Dimensions in inches (millimeters) M27583 9-21/64 (237) MAX [2] 8-21/32 (220) 6-21/64 (161) [2] 5-19/64 (135) [4] Ø 3/16 (5) MAX 2-19/32 (66) The R7910A SOLA HC is a hydronic boiler control system that provides heat control, flame supervision, circulation pump control, fan control, boiler control, and electric ignition function. It will also provide boiler status and error reporting. • Frost Protection, Slow Start, Anti-condensate, Boiler Delta-T, Stack Limit, Boiler Limit, DHW Limit, Outlet T-Rise Limit • Primary Flame Safeguard Control • Internal or external spark generator. • Analog NTC Sensor Inputs (10 kohm or 12 kohm). • Other Analog Inputs • PID Load Control • Digital Inputs • Digital Outputs • Analog Outputs • Algorithm Prioritization • Two Temperature Loops of Control (CH and DHW) • High Limit Control-CH, DHW, & Stack (Meets UL 353) using dual 10 kohm NTC sensors. • Fifteen Item Fault Code History including equipment status at time of lockout • Fifteen Item Alert Code Status including equipment status at time of internal alerts • 24 Vac Device Power • 24 or 120 Vac Digital I/O models available. • Flame Signal test jacks (Vdc) • Three Status LEDs. • UV or Flame rod Flame Sensing. Application: Hydronic Frequency: 50-60 Hz ± 5% Approximate, Dimensions: 9 21/64 in. x 6 21/64 in. x 2 19/32 in. (237 mm x 161 mm x 66 mm) Comments: Includes Programmable features Approvals, Control Safety Devices: Acceptable Approvals, FCC: Part 15, Class B Emissions Material Number Enclosure Rating Firing Rate Switch Flame Sensor Type Modulation Output Voltage Approvals, Underwriters Laboratories Inc. R7910A1001/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 24 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1019/U NEMA 1/IP 40 High Fire Switch; Low Fire Switch FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1027/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1084/U NEMA 1/IP 40 FR Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 24 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1118/U NEMA I/IP 40 FR, High Energy Spark Yes (PWM) 24 Vac Operating; 24 Vac Load UL, cUL Component File No. MH20613 (MCCZ) 70-6910 785 Commercial/Industrial Combustion Controls SOLA Controllers SOLA™ Steam Control Dimensions in inches (millimeters) [2] 5-19/64 (135) 9-21/64 (237) MAX [4] Ø 3/16 (5) MAX 2-19/32 (66) 6-21/64 (161) [2] 8-21/32 (220) M27063 The R7911A SOLA SC is a steam boiler control system that provides heat control, flame supervision, fan control, boiler control, and electric ignition function. It will also provide boiler status and error reporting. • Slow Start, Stack Limit, Boiler Limit • Primary Flame Safeguard Control • Internal or external spark generator. • Analog Stack Temp NTC Sensor Inputs (10kohm or 12kohm). • Other Analog Inputs • PID Load Control • Digital Inputs • Digital Outputs • Analog Outputs • Algorithm Prioritization • High Limit Control - Stack (Meets UL 353) using dual 10 kohm NTC sensors. • Fifteen Item Fault Code History including equipment status at time of lockout • Fifteen Item Alert Code Status including equipment status at time of internal alerts • 24 Vac Device Power • 24 or 120 Vac Digital I/O models available. • Flame Signal test jacks (Vdc) • Three Status LEDs. • UV or Flame rod Flame Sensing. Application: Steam Frequency: 50-60 Hz ± 5% Approximate, Dimensions: 9 21/64 in. x 6 21/64 in. x 2 19/32 in. (237 mm x 161 mm x 66 mm) Comments: Includes Programmable features Approvals, Control Safety Devices: Acceptable Approvals, FCC: Part 15, Class B Emissions Approvals, Underwriters Laboratories Inc.: UL, cUL: Component Recognized: File Number MH20613 (MCCZ) Material Number Enclosure Rating Firing Rate Switch Flame Sensor Type Modulation Output Voltage R7911A1000/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load R7911A1026/U NEMA 1/IP 40 High Fire Switch; Low Fire Switch FR/UV No (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load 786 70-6910 SOLA Controllers S7910 SOLA™ Keyboard Display Dimensions in inches (millimeters) NOTE: STICKS OUT BACK 1/4 INCH (6). M27094 2-45/64 (69) 1-1/2 (38) 2-9/32 (58) 4-3/4 (121) 5-21/32 (144) 4-1/16 (103) 4X Ø 3/16 (5) ± 1/64 (0) The S7910 Local Keyboard display interface provides setpoint and control adjustments to parameters of the R7910 SOLA Hydronic Control. The S7910 includes four function buttons, and all data is displayed on an LCD with backlight. • Burner control state, sequence • Rate control manual adjustment • Lockout code • Alert and Hold Reason • CH, CH TOD, DHW, and DHW TOD setpoints • Communication interface with R7910. • First out and system status and diagnostics provided through the LCD. • Local communication of operation and fault information. • Control DHW, Inlet, Outlet, Delta T (Outlet-Inlet), and Stack Temperatures • Set-up • Diagnostics • Blue, includes (future feature: TOD), only “talks” to Commercial R7910A, Flame Signal Vdc, pilot hold function, screw mounting Ambient Temperature Range: 32°F to 120°F (0°C to 49°C) Shipping and Storage Temperature Range: -60°F to +150°F (-51°C to +66°C) Approximate, Dimensions: 4-1/6 in. high x 5-21/32 in. wide (103 mm high x 144 mm wide) Operating Humidity Range (% RH): 85% relative humidity continuous, noncondensing Weight: 4 oz (124 g) Approvals, FCC: Part 15, Class B emissions. Approvals, Underwriters Laboratories Inc.: UL, cUL: Component Recognized: File Number MH20613 (MCCZ) Material Number Electrical Ratings Vibration Description Used With S7910A1008/U 24 VAC powered from R7910A 0.5 G environment Keyboard Display Module R7910 70-6910 787 Commercial/Industrial Combustion Controls SOLA Controllers S7999D SOLA™ System Operator Interface The S7999D can be used to monitor an individual boiler and also used for multiple boiler applications in a lead/lag arrangement. It consists of 2 RS485 ports and a USB port. The S7999D display can be flush front or mounted behind in a panel cutout. Wiring connections are through a removable 8-pin wiring connector. • Individual boiler status, configuration, history and diagnostics • Allows configuration and monitoring of the Sola Controls (R7910 Hydronic Controls or R7911 Steam Control) burner control sequence, flame signal, diagnostics, historical files, and faults • Allows switching view between multiple boilers and lead-lag master/ slaves • Real-time data trending analysis and transferring saved trend data to Excel spreadsheet • 7” 800 x 480, 24 bit high resolution color LCD touch screen for clarity • Audio output with integral speaker for sound output. • Adjustable backlight control • Real time clock with coin-cell battery back-up (CR2032) • Volume control • Screen Capture function to capture screen images • USB port for file transfers and software updates • 2 RS-485 (COM1 & 2) ports for Modbus™ interface to Sola controls and BAS Gateway. • Windows® CE 6.0 Operating System • 8-pin connector, back-up battery and mounting hardware are provided Application: Interface Display Frequency: 50-60 Hz ± 5% Ambient Temperature Range: 14°F to 122°F (-10°C to 50°C) Shipping and Storage Temperature Range: -13°F to 155°F (-25°C to 60°C) Approximate, Dimensions: 9-13/32 in. wide x 6-21/32 in. high x 1-9/16 in. deep (239 mm wide x 169 mm high x 40 mm deep) Operating Humidity Range (% RH): 85% RH continuous, noncondensing Comments: Black Plastic Border Approvals, FCC: FCC Part 15, Class A digital device Approvals, Canadian Underwriters Inc.: Component Recognized: File Number MH20613 (MCCZ) Approvals, Underwriters Laboratories Inc.: Component Recognized: File Number MH20613 (MCCZ) Material Number Voltage Description Used With S7999D1006/U 24 Vac System Operator Interface with Black Plastic Border R7910/R7911 788 70-6910 SOLA Controllers PM7910 Program Module The PM7910 Program Module is an optional plug-in for the R7910 SOLA HC and R7911 Sola SC. From the system level the S7999 System Operator Interface can direct the R7910/R7911 to transfer or retrieve parameter information with the Program Module. • Can be removed or installed while the R7910 or R7911 is powered. • Facilitate multiple controller setups. • Backup and restore the R7910 programmable data including: — Non-safety parameter values — Parameter Control Blocks (information on how the parameter values may be modified.) Material Number Application Comments PM7910A1013/U Support backup and restore Indicator LEDs - One (Status LED) Blinking LED indicated the Program Module is properly seated and powered from the R7910/R7911 SOLA™ Accessories or Parts Application: Single element sensor with 6" leadwire with socket. Material Number Application 32003971-002/U 10K Ohm Single element sensor with 6" Leadwire with Socket 32003971-003/U 10K Ohm Single element sensor with 42" leadwires, includes wire nuts (2), #8 mounting screws (3), anchors (2), sensor clip (1), tie strap (2) 50001464-006/U 10K Ohm Dual Element Sensor with 6" leadwires with Female Socket 50001464-007/U 10K Ohm Dual Element Sensor with 42" leadwires without connector 50032893-001/U Bag of connectors for R7910 and R7911 Controllers 70-6910 789 Commercial/Industrial Combustion Controls ControLinks Fuel Air Control System R7999A ControLinks™ Fuel Air Controller 1-15/16 (48) 5-3/16 (131) 7-3/16 (182) 2-13/16 (71) 3 (76) INSTALLED ON Q7999 M16548C R7999 Q7999 1 DDL PORT (RS485). 1 Uses microprocessor-based technology to control the ML7999 Universal Parallel Positioning Actuators. This represents a value added replacement of mechanical cam and linkage assembly controlling the relationship between fuel, airflow and flue gas recirculation (if used) on a power burner. The ControLinks Fuel Air Control System consists of the R7999 Fuel Air Controller, Q7999 Wiring Subbase, ML7999 Universal Parallel Positioning Actuator and ZM7999 Configuration Software. The R7999, with one communications port, provides communications capabilities similar to those found in the 7800 SERIES controls. • Fast burner setup via PC or laptop • Fuel, air, FGR profile download capability • Two independent fuel profiles with or without FGR • 7 to 24 point profiles • Programmable behaviors of all actuators during Purge and Standby • Programmable behavior of non-selected fuel actuator • Independent light off and minimum modulation positions • Wide power voltage input range (100 to 120 Vac, 50/60 Hz Auto/Manual input) • Manual mode firing rate input • Pluggable controller to wiring subbase • Multipurpose communications port • Field-configurable device • Integrated boiler shock protection algorithms: Water temperature low fire hold • Stack temperature low fire hold. FGR and low fire hold • Selectable FGR hold based on stack temperature • Programmable behavior of FGR actuator during purge • Maximum modulation limit capability • Remote reset input • Automated actuator endpoint seeking process • CSD-1 and NFPA acceptable Voltage: 100 to 120 Vac Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approvals, Underwriters Laboratories Inc.: Listed: Report No. MH17367 Operating Humidity Range (% RH): 90% RH maximum, noncondensing Replacement Parts: 32002515-001/U – 3 pin electrical connector, for R7999 Material Number Frequency Description R7999A1005/U 50 Hz; 60 Hz Fuel Air Ratio Controller, 100 to 120 Vac, 50/60 Hz. 790 70-6910 ControLinks Fuel Air Control System S7999 ControLinks™ System Display With the S7999. Each burner control, fuel/air ratio control, expanded annunciator other Modbus devices present on the burner system can be viewed individually to determine its status. • Color (7" diagonal). Touch Screen User Interface • Flush Mounting • Allows setup and monitoring of R7999 ControLinks • Two RS485 and one USB communication ports • Screen saver, contrast control and volume control • Modbus communication allows monitoring up to 99 different controls • Allows Programmable Expanded Annunciator terminal naming • Allows R7999 ControLinks EEPROM backup and restore • Battery backup prevents losing date and time Application: Interface Display Temperature Range: Ambient - 14°F to 122°F (Ambient - -10°C to 50°C) Shipping and Storage Temperature Range: -13°F to 155°F (-25°C to 60°C) Approvals, Underwriters Laboratories Inc.: Component Listed Approvals, FCC: FCC Part 15, Class A digital device Used With: R7999 Operating Humidity Range (% RH): 85% RH continuous, noncondensing Material Number Voltage Description S7999D1048/U 24 Vac S7999D System Display for R7999 ControLinks Configuration and System Monitoring Q7999A ControLinks™ Fuel Air Control Wiring Subbase Provides terminals for field wiring for the R7999A ControLinks™ Fuel Air Controller. Terminals on the R7999A, B Controller engage the Q7999 contacts to make electrical connections. The Q7999A Subbase is panel-mounted. • Quick-mount wiring subbase for R7999A, B Fuel Air Ratio Controllers. • Allows wiring of control system before installation of controller. • Panel-mounted. • NEMA 1 enclosure. Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +150°F (-40°C to +65°C) Approvals, Underwriters Laboratories Inc.: Listed: Report No. MH17367 Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Weight oz. (k): 10 oz (0.28 kg) Material Number Voltage Frequency Description Q7999A1006/U 100 to 120 Vac 50 Hz; 60 Hz Fuel Air Ratio Controller Wiring Subbase Q7999A1014/U 100 to 120 Vac 50 Hz; 60 Hz Fuel Air Ratio Controller Wiring Subbase 70-6910 791 Commercial/Industrial Combustion Controls ControLinks Fuel Air Control System ML7999A Universal Parallel-Positioning Actuator ML7294 Non-Spring Return Direct Coupled Actuators control dampers or valves in HVAC applications. The ML7294 Non-Spring Return DCA accepts a current or voltage signal from an electronic controller to position a damper or valve. • Password protected using eight-digit hexadecimal identification signal • Separate wiring compartment between line voltage power wiring and low voltage control • Couples directly to a 1/2-in. shaft with no additional parts required; couples directly to 5/16-in. and 3/8-in. shafts using self-centering shaft reduction accessories • Shaft coupler assembly available for shafts larger than 1/2-in. • Bracket accessory kit available for mounting to Honeywell V51 butterfly gas valves • Visual indication of actuator position • NEMA 2 • IF54 with weatherproof kit Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +150°F (-40°C to +65°C) Approvals, Underwriters Laboratories Inc.: Meets UL873 Approvals, CSA: Certified Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Approvals, CE: Certified Material Number Voltage Frequency Description ML7999A2001/U 15 VA, 100 to 240 Vac 50 Hz; 60 Hz Universal Parallel-Positioning Actuator. Medium torque electronic actuator with a precision feedback potentiometer and integral power supply capable of direct line voltage connection. Must be used with a Series 2 R7999. ML7999B Universal Direct Coupled Actuator Dimensions in inches (millimeters) 4 (102) 7/8 (22) 1-7/8 (47) 1/2 (13) 3-1/2 (89) 1-5/8 (41) 5-1/2 (140) 6 (153) M16466 1/4-28 unF Honeywell ML7999B universal direct coupled actuator provides 100 lb-in. torque, 4 to 20 mA control input to control combustion air dampers and modulation valves. Includes precision drive shaft control and integral power supply. • Separate wiring compartment between line voltage power wiring and low voltage control • Programmable actuator stroke against 4-20 mA input • Couples directly to 1/2-in. shaft with no additional parts required; couples directly to 5/16- and 3/8-in. shafts using available selfcentering shaft reduction accessories • Shaft coupler assembly available for shafts larger than 1/2-in. • Bracket accessory kit available for mounting to Honeywell V51 butterfly gas valves • Visual indication of actuator position • NEMA 2 • IF54 with weatherproof kit Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +150°F (-40°C to +65°C) Approvals, Underwriters Laboratories Inc.: Meets UL873 Approvals, CSA: Certified Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Approvals, CE: Certified Accessories: 32002935-001/U – Weatherproofing kit for actuator, ML7999 ControLinks (NEMA 3). Material Number Voltage Frequency Description ML7999B1002/U 15 VA, 100 to 240 Vac 50 Hz; 60 Hz Universal Parallel-Positioning Actuator. Medium torque electronic actuator with a precision feedback potentiometer and integral power supply capable of direct line voltage connection. 792 70-6910 ControLinks Fuel Air Control System ML7999 Accessories Material Number Description 201391/U Shaft Adapter for 3/8 in. round or square valve shaft 32002935-001/U Weatherproofing kit for actuator, ML7999 ControLinks (NEMA 3). 32003167-001/U Shaft Adapter for 5/16 in. round or square shaft 32003168-001/U Shaft Adapter for 3/4 in. round shaft only 32003168-002/U Shaft Adapter for 5/8 in. round shaft only 32003168-003/U Shaft Adapter for 9/16 in. round shaft only 32003396-002/U V51E Mounting Kit for ML7999 Actuator (2-1/2, 3 & 4 in. valves). Includes angle bracket, mounting bracket, screws, nuts and washers, and instructions. 50036542-001/U Auxiliary Switch Mounting Plate for ML7999B for 201052A or 201052B Auxiliary switch assembly ZM7999A ControLinks Fuel Air Control System Configuration Software The ZM7999 Software Configuration Tool reduces burner setup time by letting you create an R7999 Controlinks burner modulation curve. The software assists you through the commissioning process and when it’s complete, you can monitor the system realtime. • Minimum Hardware Requirements: PC or laptop with a Pentium© processor. • Windows® 95 or Windows® 98. • 16 MB of RAM. • 1G hard drive with 100 MB of free memory. • 4X (or higher) CD-ROM drive. • Mouse. • Super VGA color monitor (800 x 600 resolution suggested). Material Number Description Used With ZM7999A1006/U Configuration Software R7999 ControLinks Accessories Material Number Description Used With 32002515-001/U 3 pin electrical connector, for R7999 R7999 50020034-001/U 9 pin electrical connector, for S7999B S7999B 70-6910 793 Commercial/Industrial Combustion Controls Network Interface Communications QM4520A Data Acquisition Module The QM4520A RS-232 to RS485 Converter allows a PC to communicate with multiple devices on a single bus, over greater distances. • Mount on DIN rail, panel or in a piggyback stack. • Uses unregulated power between +10 Vdc and +30 Vdc. • Transmit data on single twisted pair (RS-485). • Plug-in screw terminal blocks assure simple installation, maintenance and modification. • Clean and reliable communications assured by noise-suppressing special circuitry. • RS-485 communications reduce the number of required cables, connectors and conditioners. • Modules can be remotely mounted up to 4,000 ft (1.2 km) away. Electrical Connections: Plug-in screw terminal block. Ambient Temperature Range: 32°F to 158°F (0°C to 70°C) Voltage: Unregulated +10 Vdc to +30 Vdc - Power supply not provided. Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Approximate, Dimensions: 2 11/32 in. x 4 13/16 in. x 1 3/16 in. (60 mm x 122 mm x 30 mm) Material Number Connection Type Description Used With QM4520A1004/U RS-232 (4-wire: TX, RX, RTS, GND) (Null modem may be required.) RS-232 to RS-485 Converter ZM7850 or ZM7999 software 794 70-6910 Flame Amplifiers 7800 SERIES and R7140 Flame Signal Amplifiers Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules. • Flame failure response time of 0.8 or 3.0 seconds (1.0 or 2.0 for CE approved devices). • Flame signal strength ranges from 0.0 to 5.0 Vdc. • Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation. • Flame signal test jacks to measure amplifier flame signal voltage. • Color-coded labels identify flame detection type. • Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system. • Ampli-check tests the amplifier and 7800 SERIES Relay. • None (standard) is just tested at normal system startup. • 7800 SERIES relay module locks out on safety shutdown with flame detection system failure. • Compatible with existing Honeywell flame detectors (order separately). Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. LR95329-3 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 1V9A0.AF Material Number Type Flame Failure Response Time (sec) Self Checking Use With Primary Safety Control Use With Flame Sensor Comments R7824C1002/U Ultraviolet 3.0 sec Dynamic Self-Check RM7824 C7024E, F Flame Detector Color: Green R7847A1025/U Rectification 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179 Color: Green R7847A1033/U Rectification 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179; Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C Color: Green R7847A1074/U Rectification 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847A1082/U Rectification 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847B1023/U Rectification 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179 Color: Green R7847B1031/U Rectification 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179; Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C Color: Green R7847B1064/U Rectification 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847B1072/U Rectification 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847C1005/U Rectification 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7012E, F Color: Green R7848A1008/U Infrared 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7015 Color: Red R7848B1006/U Infrared 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7015 Color: Red R7849A1015/U Ultraviolet 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7849A1023/U Ultraviolet 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7849B1013/U Ultraviolet 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7849B1021/U Ultraviolet 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7851B1000/U Optical 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil, Coal: Optical (UV, Visible Light) C7927, C7962 Color: White R7851B1018/U Optical 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil, Coal: Optical (UV, Visible Light) C7927, C7962 Color: White R7851C1008/U Optical 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Optical (UV only) C7961E, F Color: White R7852A1001/U Infrared 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7915 Color: Red/White R7852B1009/U Infrared 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7915 Color: Red/White R7861A1026/U Ultraviolet 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7061 Color: Purple R7861A1034/U Ultraviolet 0.8 sec or 1.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7061 Color: Purple R7886A1001/U Ultraviolet 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Adjustable Sensitivity Ultraviolet Flame Sensor C7076 Color: Blue 70-6910 795 Commercial/Industrial Combustion Controls Flame Amplifiers R7247; R7248; R7249; R7476 Flame Amplifiers Solid state plug-in units respond to flame detector signal and indicate presence of flame. • Use with BC7000; R4140; R4075C, D, E; R4138C, D Flame Safeguard controls and appropriate flame detector and FSP5075A1, FSP5075A3 Flame Amplifier Modules. Use With Primary Safety Control: R4140; BC7000; R4075C, D, E; R4138C, D; FSP5075 Approvals, Factory Mutual: Approved: Report No. 24181.01 Material Number Type Flame Failure Response Time (sec) Self Checking Use With Flame Sensor Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Control Safety Devices Approvals, Swiss RE Comments R7247B1003/U Rectification 2 to 4 sec Ampli-Check Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179; Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C Listed: File No. MP268, Guide No. MCCZ2 Certified: File No. LR1620, Guide No. 140-A-2 Acceptable (CSD-1) Acceptable Color: Green R7247C1001/U Rectification 2 to 4 sec Dynamic Self-Check Gas, oil, coal: Ultraviolet Flame Sensor C7012E, F Listed: File No. MP268, Guide No. MCCZ2 Certified: File No. LR1620, Guide No. 140-A-2 Acceptable (CSD-1) Acceptable Color: Green R7248A1004/U Infrared 2 to 4 sec None (standard) Gas, oil, coal: Infrared (lead sulfide) C7015 Listed: File No. MP268, Guide No. MCCZ Certified: File No. LR1620, Guide No. 140-A-2 (gas), 300-I-0.2 (oil) Acceptable (CSD-1) Acceptable Color: Red R7249A1003/U Ultraviolet 2 to 4 sec None (standard) Gas, oil, coal: Ultraviolet (Minipeeper) C7027, C7035 Listed: File No. MP268, Guide No. MCCZ2 Certified: File No. LR1620, Guide No. 140-A-2 Acceptable (CSD-1) Acceptable Color: Purple R7476A1007/U Ultraviolet 2 to 4 sec Dynamic Self-Check Gas, oil, coal: Adjustable Sensitivity Ultraviolet Flame Sensor C7076 Listed: File No. MP268, Guide No. MCCZ Certified: File No. LR1620, Guide No. 140-A-2 (gas), 300-I-0.2 (oil) Color: Blue R7476A1015/U Ultraviolet 2 sec max. Dynamic Self- Check Gas, oil, coal: Adjustable Sensitivity Ultraviolet Flame Sensor C7076 Listed: File No. MP268, Guide No. MCCZ Certified: File No. LR1620, Guide No. 140-A-2 (gas), 300-I-0.2 (oil) Color: Blue Flame Amplifier Accessories Material Number Description Used With 32005301-001/U T Filter for Rectification Applications R7847, R7247 796 70-6910 Flame Rods and Flame Rod Holders C7007 Flame Rod Holder Used to apply flame rod in gas-fired system controlled by rectification type flame safeguard control. • Use with pressurized fire boxes. • Hold flame rods firmly over the pilot or burner with a chuck and setscrew arrangement. • Provide electrical connection through a terminal screw. • Allow ventilation to cool the unit or to minimize soot deposit through a 1/2 in. • NPT tapping. • Mount easily with sleeve or thread type mounting adapters, and a straight or angle body. Type: Flame Rod Application: Gas fired pilot or gas fired system. Approximate, Dimensions: 1 15/16 in. high x 2 3/16 in. diameter x 3 3/16 in. long (49 mm high x 56 mm diameter x 81 mm long) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. L95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Material Number Electrical Connections Mounting Required Components Comments Used With C7007A1001/U Terminal screw 1/2 in.-14 NPT male 102709A -12 in. Flame Rod; 102709B -18 in. Flame Rod; 102709C -24 in. Flame Rod; 102709D -36 in. Flame Rod; or 102709E -48 in. Flame Rod Holder only, order Kanthal flame rod separately. Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008 Flame Rod Holder Miniature “spark plug” type flame rod holder with threaded base, snap-on cover and Kanthal A-1 Flame Rod. • Use with Honeywell Flame Safeguard controls requiring rectificationtype flame detection. • Use only with gas. • Install with or without cover. • Comes in several different lengths and can be cut to exact desired length. • Uses Rajah electrical connector. Type: Flame Rod Application: Gas fired pilot or gas fired system. Approximate, Dimensions: Holder: 7/8 in. diameter x 3 3/4 in. long (Holder: 22 mm diameter x 95 mm long) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. L95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Material Number Electrical Connections Mounting Includes Used With C7008A1000/U Rajah electrical connector 1/4 in. NPT male 6" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1018/U Rajah electrical connector 1/4 in. NPT male 12" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1026/U Rajah electrical connector 1/4 in. NPT male 18" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1034/U Rajah electrical connector 1/4 in. NPT male 24" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1174/U Rajah electrical connector 1/4 in. NPT male 12" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1182/U Rajah electrical connector 1/4 in. NPT male 24" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 70-6910 797 Commercial/Industrial Combustion Controls Flame Rods and Flame Rod Holders C7009 Flame Rod Holder Subminiature “spark plug” type flame rod holder with flame rod. • Use on industrial flame-retention gas burner nozzles. • Works with Honeywell Flame Safeguard controls requiring rectification type flame detector. • Mounts in areas with limited space because flame rod can be cut to desired length. • Uses Rajah electrical connector. Type: Flame Rod Application: Gas fired pilot or gas fired system. Approximate, Dimensions: Holder: 3/8 in. diameter x 2 3/8 in. long (Holder: 10 mm diameter x 60 mm long) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. L95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Material Number Electrical Connections Mounting Includes Comments Used With C7009A1009/U Rajah electrical connector 1/8 in. NPT male Flame rod and holder 4 in. (102 mm) flame rod Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7009A1025/U Rajah electrical connector 1/8 in. NPT male Flame rod and holder 12 in. (305 mm) flame rod Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 Flame Rod Detector Accessories or Parts Material Number Description 102709B/U Kanthal Flame Rod - 18 in. (.182" diameter) for C7004B, C7007A, C7011A 102709C/U Kanthal Flame Rod - 24 in. (.182" diameter) for C7004B, C7007A, C7011A 102709D/U Kanthal Flame Rod - 36 in. (.182" diameter) for C7004B, C7007A, C7011A 105478A/U Kanthal Flame Rod - 6 in. (.182" diameter-threaded 6-32) for C7008 105478B/U Kanthal Flame Rod - 12 in. (.182" diameter-threaded 6-32) for C7008 105478C/U Kanthal Flame Rod - 18 in. (.182" diameter-threaded 6-32) for C7008 105478D/U Kanthal Flame Rod - 24 in. (.182" diameter-threaded 6-32) for C7008 798 70-6910