# Honeywell # ECC or Buildings Branch | Flame Safeguard part 1 This is honeywells catalog of parts. Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC7820 PROGRAMMER RELAY MODULES: M15516G SELECT A SUBBASE SELECT A PURGE CARD SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7820A1026 EC7820A1034 DESCRIPTION ONE IGNITION ATTEMPT FIVE IGNITION ATTEMPTS O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE - CE APPROVAL O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4, KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7061A, F, M\*\* C7061A, F, M\*\* C7076A, F SELECT A FLAME AMPLIFIER \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012 A,C. \*\* EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 1.) 2.) 3.) 4.) 5.) 70-6910 737 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7830 PROGRAMMER RELAY MODULES: M15517H SELECT A SUBBASE SELECT A PURGE CARD SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7830A1033 EC7830A1041 EC7830A1066 120VAC 50/60 HZ RM7830A1003 RM7830A1029 RM7830A1011 O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DESCRIPTION POST-PURGE 2 SECONDS POST-PURGE 30 SECONDS POST-PURGE 15 SECONDS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE - CE APPROVAL O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7061A, F, M\*\* C7061A, F, M\*\* C7076A, F SELECT A FLAME AMPLIFIER \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012 A,C. \*\* EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 1.) 2.) 3.) 4.) 5.) 738 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7850 PROGRAMMER RELAY MODULES: M15519G SELECT A SUBBASE SELECT A PURGE CARD SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7850A1064 EC7850A1072 EC7850A1080 EC7850A1122 120VAC 50/60 HZ RM7850A1001 RM7850A1027 RM7850A1019 O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT 2 SECOND FFRT 1 SECOND FFRT 2 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DESCRIPTION DYNAMIC AIR DAMPER CHECK POST-PURGE 2 SECONDS POST-PURGE 30 SECONDS POST-PURGE 15 SECONDS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE - CE APPROVAL O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7061A, F, M\*\* C7061A, F, M\*\* C7076A, F SELECT A FLAME AMPLIFIER \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. \*\* EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 1.) 2.) 3.) 4.) 5.) 70-6910 739 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7823 FLAME SWITCH RELAY MODULES: M15520F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7823A1004 120VAC 50/60 HZ RM7823A1016 O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION \*\*\* 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E,F\*\* C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M\*\* C7061A, F, M\*\* C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. \*\* EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 740 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7824A 24VDC PRIMARY CONTROL RELAY MODULES: M15521D SELECT A SUBBASE SELECT A FLAME AMPLIFIER SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE RM7824A1006 24VDC O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7824C1002 R7851B1000 R7851B1018 R7852A1001 R7852B1009 DESCRIPTION 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT CHECKING DYNAMIC SELF-CHECK AMPLICHECK® AMPLICHECK® NONE AMPLICHECK® O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH C7024E, F C7927, C7962 C7927, C7962 C7915 C7915 1.) 2.) 3.) 4.) 70-6910 741 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7885 MANUAL START PRIMARY RELAY MODULES: M15522F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 120VAC 50/60 HZ RM7885A1015 DESCRIPTION SEMI AUTOMATIC PRIMARY O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION\*\*\* 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 742 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7888A SPECIAL FUNCTION PRIMARY CONTROL RELAY MODULES: M15523F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 120VAC 50/60 HZ RM7888A1019 RM7888A1027 DESCRIPTION INDUSTRIAL PRIMARY CONTROL (COMPONENT UL APPROVED) INDUSTRIAL PRIMARY CONTROL (COMPONENT UL APPROVED) O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 743 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7890 ON/OFF PRIMARY CONTROL RELAY MODULES: M15524G SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7890A1011 EC7890B1010 120VAC 50/60 HZ RM7890A1015 RM7890A1031 RM7890A1056 RM7890A1064‡ RM7890B1014 RM7890B1030 RM7890B1048 RM7890B1055++ RM7890C1005 RM7890D1004 DESCRIPTION 30 SECOND PFEP FOR VALVE PROVING APPLICATIONS WITH SHUTTER DRIVE WITH SHUTTER DRIVE AND FULL PFEP WITH SHUTTER DRIVE - FOR VALVE PROVING APPLICATIONS WITH SHUTTER DRIVE STANDING PILOT APPLICATIONS WITH FLAME RODS ONLY INFRARED HEATER ONLY 15 OR 30 PREF O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VP TIMINGS) SPANISH (REQUIRED TO PROGRAM VP TIMINGS) O.S. NO. S7810A1009 S7810M1003 S7810M1029 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE MODBUS MODULE - CE APPROVED O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION\*\*\* 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F\*\* C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M\*\* C7061A, F, M\*\* C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. \*\* EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. \*\*\* FFRT FOR CE APPROVED CONTROLS 1 SEC. OR 2 SEC. ‡ CE APPROVED ++ NORTH AMERICAN AND CE APPROVED 744 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR EC/RM7895 ON/OFF WITH PURGE PRIMARY RELAY MODULES: M15525F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 220-240 VAC 50/60 HZ EC7895A1010 EC7895C1000 120VAC 50/60 HZ RM7895A1014 RM7895A1048 RM7895B1013 RM7895C1012 RM7895C1020 RM7895D1011 RM7895E1002 DESCRIPTION EARLY SPARK TERMINATION DYNAMIC AIRFLOW SWITCH CHECK EARLY SPARK TERMINATION DYNAMIC AIRFLOW SWITCH CHECK INFRARED HEATER APPLICATIONS, 15/30 SECOND PFEP O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) INTERRUPTED PILOT INTERMITTENT PILOT SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7851A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION\*\*\* 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F\*\* C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M\*\* C7061A, F, M\*\* C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. \*\* EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER. 70-6910 745 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7896 ON/OFF WITH PRE- AND POST-PURGE PRIMARY RELAY MODULES: M13908B SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE 120VAC 50/60 HZ RM7896A1012 RM7896B1011 RM7896C1010 RM7896D1019 RM7896D1027 DESCRIPTION DYNAMIC AIRFLOW SWITCH CHECK DYNAMIC AIRFLOW SWITCH CHECK 5 SEC EARLY SPARK TERMINATION, DYNAMIC AIRFLOW SWITCH CHECK AND 60 SEC POST-PURGE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) INTERRUPTED PILOT INTERMITTENT PILOT SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7851A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION\*\*\* 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 746 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7897 ON/OFF WITH PRE- AND PROGRAMMABLE POST-PURGE PRIMARY RELAY MODULES: M15526H SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION INTERMITTENT/INTERRUPTED PILOT AND PROOF OF CLOSURE INTERRUPTED PILOT WITH DELAYED MV2 AND PROOF OF CLOSURE INTERRUPTED PILOT WITH DELAYED MV2 AND PROOF OF CLOSURE 5 SEC MFEP O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO SET POST PURGE TIME) SPANISH (REQUIRED TO SET POST PURGE TIME) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7897A1002 RM7897C1000 RM7897C1018 O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 747 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7898 ON/OFF WITH PRE- AND PROGRAMMABLE POST-PURGE PRIMARY RELAY MODULES FOR VALVE PROVING APPLICATIONS: M23254C SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION INTERMITTENT/INTERRUPTED PILOT AND PROOF OF CLOSURE INTERMITTENT/INTERRUPTED PILOT WITH EARLY SPARK TERMINATION AND PROOF OF CLOSURE O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) SPANISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7898A1000 RM7898A1018 O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 748 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7838A MANUAL START WITH PURGE INDUSTRIAL PRIMARY RELAY MODULE: M15527F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7838A1014 O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 749 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7838B MANUAL START INDUSTRIAL PROGRAMMER RELAY MODULE: SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION SEMI-AUTOMATIC PROGRAMMER WITH: S7800A1001 KEYBOARD DISPLAY STANDARD S7800A1142 KEYBOARD DISPLAY STANDARD - HAS VALVE PROVING FEATURE O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK M15528F O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120 VAC 50/60 HZ RM7838B1013\* RM7838B1021\* SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* ALARM SOUNDS UNTIL FLAME SENSED \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 750 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR RM7838C MANUAL START INDUSTRIAL PROGRAMMER RELAY MODULE: SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS DESCRIPTION SEMI-AUTOMATIC PROGRAMMER WITH: S7800A1001 KEYBOARD DISPLAY STANDARD S7800A1142 KEYBOARD DISPLAY STANDARD - DEVICE HAS VALVE PROVING FEATURE S7800A1001 KEYBOARD DISPLAY STANDARD O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK M18830F O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) SPANISH (REQUIRED TO PROGRAM POST PURGE AND VP TIMINGS) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E,E C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E,F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800C1003 ST7800C1011 ST7800C1029 ST7800C1037 ST7800C1045 ST7800C1052 DESCRIPTION TIMING: 7 SECOND TIMING: 20 SECOND TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 8 MINUTE TIMING: 10 MINUTE O.S. NO. ST7800C1086 ST7800C1102 ST7800C1128 ST7800C1136 ST7800C1144 DESCRIPTION TIMING: 16 MINUTE TIMING: 20 MINUTE TIMING: 24 MINUTE TIMING: 30 MINUTE TIMING: 45 MINUTE 120 VAC 50/60 HZ RM7838C1004\* RM7838C1012\* RM7838C1020\*+ SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* ALARM OUTPUT - LOCKOUT ONLY +NORTH AMERICAN AND CE APPROVED \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 751 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR UL/CSA RM78XXG,M PROGRAMMER RELAY MODULE: M15529F SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGEUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120VAC 50/60 HZ RM7800G1018 RM7840G1014 RM7840G1022 RM7800M1011 RM7840M1017 DESCRIPTION MODULATING BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULE STANDARD MODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE MODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE - FOR VALVE PROVING ON-OFF BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULE STANDARD ON-OFF BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 752 70-6910 Product Selection Matrix PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE: M34645 SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120VAC 50/60 HZ RM7845A1001 DESCRIPTION WITHOUT KEYBOARD DISPLAY (LESS IGNITION AND 15 SECOND MFEP PILOT TERMINALS) SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 70-6910 753 Commercial/Industrial Combustion Controls Product Selection Matrix PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE: M15530G SELECT A SUBBASE SELECT OPTIONAL COMPONENTS KEYBOARD DISPLAY MODULE COMMUNICATIONS MISCELLANEOUS SELECT A RELAY MODULE O.S. NO. Q7800A1005 Q7800B1003 Q7800B1011 DESCRIPTION PANEL MOUNT BURNER/WALL MOUNT BURNER/WALL MOUNT WITH 3 KNOCKOUTS O.S. NO. R7847A1025 R7847A1033 R7847A1074 R7847A1082 R7847B1023 R7847B1031 R7847B1064 R7847B1072 R7847C1005 R7849A1015 R7849A1023 R7849B1013 R7849B1021 R7851B1000 R7851B1018 R7851C1008 R7852A1001 R7852B1009 R7861A1026 R7861A1034 R7886A1001 DESCRIPTION 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 3.0 SECOND FFRT 0.8 SECOND FFRT 3.0 SECOND FFRT CHECKING NONE NONE NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE NONE AMPLICHECK® AMPLICHECK® AMPLICHECK® AMPLICHECK® DYNAMIC SELF-CHECK NONE AMPLICHECK® DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK DYNAMIC SELF-CHECK O.S. NO. S7800A1001 S7800A1035 S7800A1043 S7800A1050 S7800A1068 S7800A1118 S7800A1126 S7800A1142 S7800A1167 DESCRIPTION ENGLISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ITALIAN LANGUAGE SPANISH LANGUAGE KATAKANA (JAPANESE) LANGUAGE PORTUGUESE LANGUAGE ENGLISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) SPANISH (REQUIRED TO PROGRAM VALVE PROVING FEATURE) O.S. NO. S7810A1009 S7810M1003 DESCRIPTION DATA CONTROLBUS® MODULE (IF NO KEYBOARD DISPLAY IS USED) MODBUS MODULE O.S. NO. S7820A1007 S7830A1005 203541 203765 221729 50023821-001 204718B 50023821-002 205321B 221818A 221818C DESCRIPTION REMOTE RESET MODULE EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ) DATA CONTROLBUS CONNECTOR, 5-WIRE REMOTE DISPLAY MOUNTING BRACKET DUST COVER, RELAY MODULE KEYBOARD DISPLAY MODULE COVER, NEMA 4 KEYBOARD DISPLAY MODULE COVER, CLEAR KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTON FLUSH DISPLAY MOUNTING KIT EXTENSION CABLE, DISPLAY 5FT (1524MM) EXTENSION CABLE, DISPLAY 10FT (3048MM) USE WITH FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C FLAME ROD FLAME ROD FLAME ROD\* FLAME ROD\*, C7012A, C C7012E, F C7027, C7035 C7027, C7035 C7027, C7035 C7027, C7035 C7927, C7962 C7927, C7962 C7961E, F C7915 C7915 C7061A, F, M C7061A, F, M C7076A, D SELECT A PURGE CARD O.S. NO. ST7800A1005 ST7800A1013 ST7800A1021 ST7800A1039 ST7800A1047 ST7800A1054 ST7800A1062 DESCRIPTION TIMING: 2 SECOND TIMING: 7 SECOND TIMING: 10 SECOND TIMING: 30 SECOND TIMING: 40 SECOND TIMING: 60 SECOND TIMING: 90 SECOND O.S. NO. ST7800A1070 ST7800A1088 ST7800A1096 ST7800A1104 ST7800A1112 ST7800A1120 ST7800A1138 ST7800A1146 DESCRIPTION TIMING: 2.5 MINUTE TIMING: 4 MINUTE TIMING: 6 MINUTE TIMING: 9 MINUTE TIMING: 12 MINUTE TIMING: 15 MINUTE TIMING: 22 MINUTE TIMING: 30 MINUTE 120VAC 50/60 HZ RM7800E1010 RM7840E1016 RM7800L1012 RM7840L1018 RM7800L1053 RM7840L1026 RM7800L1087 RM7840L1075 DESCRIPTION ENERGY SAVING PURGE, S7800A1001 KEYBOARD DISPLAY STANDARD ENERGY SAVING PURGE WITHOUT KEYBOARD DISPLAY S7800A1001 KEYBOARD DISPLAY STANDARD WITHOUT KEYBOARD DISPLAY INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD INTERMITTENT PILOT WITHOUT KEYBOARD DISPLAY S7800A1142 KEYBOARD DISPLAY STANDARD - WITH VALVE PROVING FEATURE WITHOUT KEYBOARD DISPLAY - WITH VALVE PROVING FEATURE SELECT A FLAME AMPLIFIER 1.) 2.) 3.) 4.) 5.) \* FLAME ROD LEADWIRE RUNS GREATER THAN 50FT (1524 CM) OR PARALLEL C7012A,C. 754 70-6910 Microprocessor Burner Controls EC7820 Primary Control Meeting European Community Timings Integrated burner control for automatically fired gas, oil, or combination, single burner atmospheric with fan applications. Has automatic burner sequencing, flame supervising system status indication, system or self-diagnostics, and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. Interchangeable plug-in amplifiers. • Local or remote annunciation of operation and fault information (optional). • Non-volatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. Application: Primary Control Interlocks: Lockout Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 5 sec Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 60 Hz (±10%), 50 Hz AirFlow Check: User selectable Second Stage Pilot Valve: Intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Approvals, Gastec/European: GASTEC: CE-63AP3070/1, Approved to EN298. Dimensions in inches (millimeters) 5 5 BURNER CONTROL 5 1/2 M12821 1 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. Material Number Voltage Pilot Type Flame Establishing Period \- Main Flame Establishing Period \- Pilot Comments EC7820A1026/U 220 to 240 Vac (+10, -15%) interrupted 5 sec, or 8 sec, or Intermittent 5 sec or 10 sec 1 ignition attempt, Includes Modulation w/ Fan Output EC7820A1034/U 220 to 240 Vac (+10, -15%) interrupted 5 sec, or 8 sec, or Intermittent 5 sec or 10 sec 5 ignition attempts, Includes Modulation w/ Fan Output 70-6910 755 Commercial/Industrial Combustion Controls Microprocessor Burner Controls EC7830; EC7850; RM7830; RM7850 Programming Control Meeting European Community Timings Microprocessor-based integrated burner control for full modulation applications. Provides automatic burner sequencing, flame supervision, system status indication, system or selfdiagnostics, and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in amplifiers. • Local or remote annunciation of operation and fault information (optional). • Non-volatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. Application: Programming Control Flame Establishing Period - Main: 3 sec, or 5 sec, or Intermittent Flame Establishing Period - Pilot: 3 sec or 5 sec Interlocks: Lockout Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card Early Spark Termination: Yes, 5 sec Required Components: Q7800A,B Universal Wiring Subbases. R7847, R7849, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. AirFlow Check: User selectable Second Stage Pilot Valve: Intermittent Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: EC7830, EC7850, RM7830-Report No. 1V9AO.AF; RM7850-Report No. J.I. OYOA9.AF Approvals, Gastec/European: GASTEC: CE-63AP3070/1, Approved to EN298. Dimensions in inches (millimeters) 5 (127) 5 (127) BURNER CONTROL 1 5-1/4 (133) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. M15532A 6-3/32 (155) 1 Material Number Voltage Frequency PostPurge Comments EC7830A1033/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec On/Off Power Burner EC7830A1041/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec On/Off Power Burner EC7830A1066/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 15 sec On/Off Power Burner EC7850A1064/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec LHL-LF & HF Proven; Dynamic damper check EC7850A1072/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec LHL-LF & HF Proven EC7850A1080/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 30 sec LHL-LF & HF Proven EC7850A1122/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 15 sec LHL-LF & HF Proven EC7850A1148/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz 2 sec LHL-LF & HF Proven RM7830A1003/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 2 sec On/Off Power Burner RM7830A1011/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 15 sec On/Off Power Burner RM7830A1029/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 30 sec On/Off Power Burner RM7850A1001/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 2 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC). RM7850A1019/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 15 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC). RM7850A1027/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) 30 sec LHL-LF & HF Proven; Complies with Gas Appliance Directive (90/396/EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/EEC). 756 70-6910 Microprocessor Burner Controls RM7800 Programmers Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information (optional). • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. • Includes Keyboard Display Module. Application: Programming Control Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period \- Main Flame Establishing Period - Pilot Second Stage Pilot Valve Interlocks Comments RM7800E1010/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800 Display, LHL-LF & HF Proven RM7800G1018/U 120 Vac (+10, -15%) 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec selectable Running Includes S7800 Display, LHL-LF Proven RM7800L1012/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800 Display, LHL-LF & HF Proven RM7800L1053/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Intermittent Lockout Includes S7800 Display, LHL-LF & HF Proven RM7800M1011/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Intermittent Running Includes S7800 Display, On/Off-LF proven 70-6910 757 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7800 Programmers with VPS Integrated burner control for gas, oil, coal or combination fuel single burner uses. With Valve Proving Feature. RM7800L comes standard with S7800A1142 Keyboard Display. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. Power LED blinks fault code on Lockout. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information (optional). • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. • RM7800 comes with S7800A1142 Keyboard Display Module. • Keyboard required to setup Valve Proving Feature and change post purge time. Application: Programming Control w/VPS Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Factory Mutual: Report No. 1V9AO.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Second Stage Pilot Valve Interlocks Comments RM7800L1087/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout Includes S7800A1142 Display, LHL-LF & HF Proven 758 70-6910 Microprocessor Burner Controls RM7823; EC7823 Flame Switch Dimensions in inches (millimeters) POWER FLAME ALARM RESET 5 (127) 5 (127) M2649 BURNER CONTROL 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) Microprocessor-based integrated flame switch for detecting a flame using rectification, ultraviolet (UV) or infrared (IR) source. Provides level of safety, functional capability and features beyond conventional controls. • Can be fitted with any 7800 Series Amplifier to provide relay action from two single pole, double throw (SPDT) relays when flame is present or not present. RM7823A and EC7823 are a flame detector relays only. • Suitable primary control must be used to provide safe-start check, safety lockout, load switching and other functions required in flame safeguard systems. • Three LEDs to indicate power, flame and alarm. • Access for external electrical voltage checks. • Nonvolatile memory. • Shutter drive output. • Compatible with existing Honeywell flame detectors. Application: Flame Switch Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Swiss RE: Acceptable Comments: two SPDT outputs Material Number Voltage Frequency Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, FCC Approvals, Factory Mutual EC7823A1004/U 220 to 240 Vac (+10, -15%) 60 Hz (±10%), 50 Hz Report No. OY0A9.AF. RM7823A1016/U 120 Vac (+10, -15%) 50 Hz; 60 Hz (±10%) Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. FCC Part 15, Class B, Emissions. Report No. OX4A5.AF. 70-6910 759 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7824 On-Off Primary Control Dimensions in inches (millimeters) 5 (127) 5 (127) M5872 BURNER CONTROL 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 24 Vdc microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications. Provides level of safety, functional capability and features beyond the capacity of conventional controls. • For use with R7824C Amplifier with C7024E, F Flame Detectors; R7848A, B with C7015A Flame Detectors; R7851B with C7927, C7962 Flame Detectors; or R7852A, B with C7915 Flame Detectors. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Five LEDs provide sequence information. • Selectable recycle or lockout on loss of flame. • Shutter drive output for use with dynamic self-check flame detectors. • Access for external electrical voltage checks. • Plug-in flame amplifier. • Nonvolatile memory retains history files and lockout status after loss of power. Application: Primary Control 24 Vdc Required Components: Q7800A, B Universal Wiring Subbases. R7824 or R7848 Flame Signal Amplifier. Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot RM7824A1006/U 24 Vdc (+10, -15%) Intermittent 4 sec or 10 sec 760 70-6910 Microprocessor Burner Controls RM7838A Manual Start Industrial Primary Control with Purge Microprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include purge, burner pilot startup, flame supervision, system status indication, system or self diagnosis and troubleshooting. • Delays admission of fuel to combustion chamber until pilot flame has been proven and then monitors the flame through the run period while providing system status indication. • Includes Keyboard Display Module. • Five LEDs provide sequence information. • Intermittent pilot valve. • Interchangeable plug-in flame amplifier. • Access for external electrical voltage checks. • Nonvolatile memory retains history files and lockout status after loss of power. • Selectable pilot flame establishing period. • Provides application flexibility and optional communication interface capability. • Compatible with existing Honeywell flame detectors. Application: Semi Automatic Primary Control with Purge Interlocks: Running PrePurge: Determined by ST7800A Purge Timer Card Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7838A1014/U 120 Vac (+10, -15%) Intermittent 4 sec or 10 sec Includes S7800 Display 70-6910 761 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7838B, C Manual Start Industrial Programmers Microprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include purge, burner pilot startup, flame supervision, system status indication, system or self diagnosis and troubleshooting. • Delays admission of fuel to combustion chamber until pilot flame has been proven and then monitors the flame through the run period while providing system status indication. • Includes Keyboard Display Module. • Five LEDs provide sequence information. • Intermittent pilot valve. • Interchangeable plug-in flame amplifier. • Access for external electrical voltage checks. • Nonvolatile memory retains history files and lockout status after loss of power. • Selectable pilot flame establishing period. • Provides application flexibility and optional communication interface capability. • Compatible with existing Honeywell flame detectors. Application: Semi Automatic Programming Control Interlocks: Lockout Preignition: Yes Early Spark Termination: Yes, 5 sec Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot PrePurge Required Components Approvals, Gastec/European Comments RM7838B1013/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800A Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Includes S7800 Display RM7838C1004/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800C Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800C Plug-in Purge Timer Card. Includes S7800 Display RM7838C1020/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800C Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800C Plug-in Purge Timer Card. Gastec EN268 Report 1156791 Includes S7800 Display 762 70-6910 Microprocessor Burner Controls RM7838B, C Manual Start Industrial Programmers with VPS Integrated burner control for industrial semi-automatically fired gas, oil, coal or combination fuel single burner applications. Includes Valve Proving Feature with S7800A1142 Keyboard Display. • Functions include purge, burner pilot startup, flame supervision, system status indication, system or self diagnosis and troubleshooting. • Delays admission of fuel to combustion chamber until pilot flame has been proven and then monitors the flame through the run period while providing system status indication. • Includes S7800A1142 Keyboard Display Module. • Five LEDs provide sequence information. • Intermittent pilot valve. • Interchangeable plug-in flame amplifier. • Access for external electrical voltage checks. • Nonvolatile memory retains history files and lockout status after loss of power. • Selectable pilot flame establishing period. • Provides application flexibility and optional communication interface capability. • Compatible with existing Honeywell flame detectors. • With Valve Proving Feature and Programmable Post Purge Time. • Power LED blinks a fault code on system lockout. Application: Semi Automatic Programming Control w/VPS Interlocks: Lockout Preignition: Yes PostPurge: programmed with S7800A1142 display Early Spark Termination: Yes, 5 sec Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Dimensions in inches (millimeters) M15518B BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 (133) 1 6-3/32 (155) MODULE WITH SUBBASE Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot PrePurge Required Components Comments RM7838B1021/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800A Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Includes programmable VPS (Valve Proving Switch) check feature and blinking LED fault annunciation RM7838C1012/U 120 Vac (+10, -15%) 10 sec or Intermittent 4 sec or 10 sec Determined by ST7800C Purge Timer Card Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800C Plug-in Purge Timer Card. Includes programmable VPS (Valve Proving Switch) check feature and blinking LED fault annunciation 70-6910 763 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7840 Programmers Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of RM7840 operation and fault information. • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. Application: Programming Control Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Interlocks Second Stage Pilot Valve Flame Establishing Period \- Main Flame Establishing Period \- Pilot Comments RM7840E1016/U Lockout Interrupted 10 sec or 15 sec 4 sec or 10 sec LHL-LF & HF Proven RM7840G1014/U Running selectable 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec LHL-LF Proven RM7840L1018/U Lockout Interrupted 10 sec or 15 sec 4 sec or 10 sec LHL-LF & HF Proven RM7840L1026/U Lockout Intermittent 10 sec or Intermittent 4 sec or 10 sec LHL-LF & HF Proven RM7840M1017/U Running Intermittent 10 sec or Intermittent 4 sec or 10 sec On/Off-LF Proven 764 70-6910 Microprocessor Burner Controls RM7840 Programmers with VPS Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Integrated burner control for gas, oil, coal or combination fuel single burner uses. Provides safety, functional capability and features beyond normal controls. With Valve Proving Feature. Requires S7800A1142 Keyboard Display. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. Power LED blinks fault code on Lockout. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information (optional). • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. • RM7800 comes with S7800A1142 Keyboard Display Module. • Keyboard required to setup Valve Proving Feature and change post purge time. Application: Programming Control w/VPS Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Early Spark Termination: Yes, 5 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Second Stage Pilot Valve: selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, FCC: FCC Part 15, Class B, Emissions. Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot Interlocks Comments Approvals, Underwriters Laboratories Inc. Approvals, Factory Mutual EC7840L1014/U 220 to 240 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Lockout Requires S7800A1142 Display, LHL-LF & HF Proven RM7840G1022/U 120 Vac (+10, -15%) 10 sec, 15 sec, 30 sec, or Intermittent 4 sec or 10 sec Running Requires S7800A1142 Display, LHL-LF Proven Component Recognized, File No. MP268; Guide No. MCCZ. Report No. 1V9AO.AF. RM7840L1075/U 120 Vac (+10, -15%) 10 sec or 15 sec 4 sec or 10 sec Lockout Requires S7800A1142 Display, LHL-LF & HF Proven Component Recognized, File No. MP268; Guide No. MCCZ. Report No. 1V9AO.AF. 70-6910 765 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7845 Programmers Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Access for external electrical voltage checks. • Application flexibility and communication interface capability. • Five LEDs provide sequence information. • Five function Run/Test Switch. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of RM7840 operation and fault information. • Nonvolatile memory retains history files and lockout status after loss of power. • Compatible with existing Honeywell flame detectors. Application: Programming Control Interlocks: Lockout Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Pilot Type: interrupted Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7845A1001/U 10 sec 4 sec or 10 sec LHL-LF & HF Proven RM7885; EC7885 Manual Start Industrial Primary Control Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Adaptable to continuous firing, high-low or modulating firing rate for semi-automatic burner sequencing. • Operates with the following: Torch-ignited main burner or torchignited pilot using S445A Start-Stop Station, or conventional knee or foot operated station. • Direct-ignition oil burner or electrically ignited pilot, using S445A Start-Stop Station. • Five LEDs provide sequence information. • Nonvolatile memory. • Flame signal check during standby. • Shutter drive output. • Compatible with existing Honeywell flame detectors. • Terminal provided for external alarm to sound on flame failure. Application: Semi Automatic Primary Control Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Flame Establishing Period - Main Flame Establishing Period - Pilot RM7885A1015/U 120 Vac (+10, -15%) Intermittent 15 min 766 70-6910 Microprocessor Burner Controls RM7888 PLC Adaptable Primary Control Dimensions in inches (millimeters) BURNER CONTROL POWER PILOT FLAME MAIN ALARM RESET SCROLL MODE SAVE 5 (127) 5 (127) M9494 5-1/4 (133) 1 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 Integrated burner control for industrial process semi-automatically fired gas, oil, coal, or combination fuels for single and multiple burner applications. PLC Adaptable. • Functions include automatic burner startup sequencing, five user selectable run sequences, four line-voltage sequence control inputs, flame supervision, system status indication, system or selfdiagnostics and troubleshooting. • Requires a relay module, subbase, and amplifier for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display mounting, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Use with master system control which determines purge timing and confirms air supply and air flow. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. Application: Primary Control - PLC Adaptable Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: selectable Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 10 oz (0.7 kg) Approvals, CSA: Certified Approvals, Factory Mutual: Approved. Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7888A1019/U 15 sec 4 sec Selectable sequences RM7888A1027/U 15 sec 10 sec For 10 sec DSI applications, selectable sequences 70-6910 767 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7890 On-Off Primary Control with VPS Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Integrated on/off primary burner control for automatically fired gas, oil or combination fuel single burner applications. Contains Valve Proving Feature. Requires S7800A1142 Display to program VPS feature. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Subbase and amplifier are required for operation. • Power LED blinks Fault Code on lockout. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Optional local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable relight or lockout on loss of flame. • Contains Valve Proving Feature - require S7800A1142 Keyboard Display (not provided) to set up. Application: On-Off Primary Control w/VPS Preignition: Yes Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Flame Establishing Period - Main Flame Establishing Period - Pilot Comments RM7890A1056/U Intermittent 4 sec or 10 sec Includes programmable VPS (Valve Proving Switch) check feature and blinking LED fault annunciation RM7890B1048/U Intermittent 4 sec or 10 sec Includes Shutter Drive Capability, VPS (Valve Proving Switch) check and blinking LED fault annunciation 768 70-6910 Microprocessor Burner Controls RM7890; EC7890 On-Off Primary Controls Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated primary burner control for automatically fired gas, oil or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Subbase and amplifier are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Optional local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable relight or lockout on loss of flame. Application: On-Off Primary Control Flames Establishing Period - Main: Intermittent Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: intermittent Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 13 oz (0.8 kg) Approvals, Swiss RE: Acceptable Material Number Voltage Flame Establishing Period - Pilot Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual Approvals, Gastec/ European Comments EC7890A1011/U 220 to 240 Vac (+10, -15%) 4 sec or 10 sec Report No. 1D0A1.AF EC7890B1010/U 220 to 240 Vac (+10, -15%) 4 sec or 10 sec Report No. 1D0A1.AF Includes Shutter Drive Capability EC7890B1028/U 220 to 240 Vac (+10, -15%) 4 sec or 10 sec Report No. 1V9AO.AF. Includes Shutter Drive Capability RM7890A1015/U 120 Vac (+10, -15%) 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. RM7890A1031/U 120 Vac (+10, -15%) 30 sec fixed Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. RM7890A1064/U 120 Vac (+10, -15%) 4 sec or 10 sec Report No. 1D0A1.AF GASTEC: CE-63AP3070/1, Approved to EN298. RM7890B1014/U 120 Vac (+10, -15%) 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Includes Shutter Drive Capability RM7890B1030/U 120 Vac (+10, -15%) Fixed 4 sec or 10 sec PFEP Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Includes Shutter Drive Capability, Alarm sounds when Reset pushed. RM7890B1055/U 120 Vac (+10, -15%) 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Gastec EN268 Report 1156791 Includes Shutter Drive Capability RM7890D1004/U 120 Vac (+10, -15%) 15 sec or 30 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Report No. OX4A5.AF. Higher Flame Sensor Voltage for Infra Red Heater Applications 70-6910 769 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7895; EC7895 On-Off Primary Control with Prepurge Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting. • Subbase, amplifier, and prepurge timer are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Optional local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. Selectable relight or lockout on loss of flame. • Airflow switch check. Application: On-Off Primary Control with Prepurge Interlocks: Selectable PrePurge: Determined by ST7800A Purge Timer Card Required Components: Q7800 Universal Wiring Subbases, Flame Signal Amplifier and ST7800A Plug-in Purge Timer Card Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Swiss RE: Acceptable Used With: 7800 Series Amplifiers (Except RM7895E1002/U uses R7847 ONLY) Material Number Voltage Pilot Type AirFlow Check Delayed Main Valve Flame Establishing Period - Main Flame Establishing Period - Pilot Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Control Safety Devices Approvals, Factory Mutual Comments EC7895A1010/U 220 to 240 Vac (+10, -15%) intermittent No Intermittent 4 sec or 10 sec Report No. 1D0A1.AF EC7895C1000/U 220 to 240 Vac (+10, -15%) interrupted Yes 10 sec 4 sec or 10 sec Report No. 1D0A1.AF RM7895A1014/U 120 Vac (+10, -15%) intermittent No Intermittent 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895A1048/U 120 Vac (+10, -15%) intermittent No Intermittent 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF Includes ignition cut-out during PFEP and special sequence for early spark termination RM7895B1013/U 120 Vac (+10, -15%) intermittent Dynamic No Intermittent 4 sec to 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895C1012/U 120 Vac (+10, -15%) interrupted Yes 10 sec 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895C1020/U 120 Vac (+10, -15%) interrupted Yes 10 sec 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF Includes ignition cut-out during PFEP and special sequence for early spark termination RM7895D1011/U 120 Vac (+10, -15%) interrupted Dynamic Yes 10 sec 4 sec or 10 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF RM7895E1002/U 120 Vac (+10, -15%) intermittent No Intermittent 15 sec or 30 sec Component Recognized, File No. MP268; Guide No. MCCZ. Certified, File No. LR95329-3. Acceptable: CSD-1 Report No. OX4A5.AF Higher Flame Sensor Voltage for Infra Red Heater Applications 770 70-6910 Microprocessor Burner Controls RM7896 On-Off Primary Control with Pre- and Post-Purge Dimensions in inches (millimeters) POWER PILOT FLAME MAIN ALARM RESET 5 (127) 5 (127) M5003B (133) BURNER CONTROL REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 5-1/4 1 Microprocessor-based integrated full-function primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Subbase, amplifier and purge card are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • 15 second postpurge. • Five LEDs provide sequence information. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable recycle or lockout on loss of airflow or flame. • Shutter drive output. • Airflow switch check. • Delayed main valve. Application: On-Off Primary Control with Pre- and Post-purge Interlocks: Selectable PrePurge: Determined by ST7800A Purge Timer Card Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Pilot Type AirFlow Check Flame Establishing Period - Main Flame Establishing Period - Pilot Delayed Main Valve PostPurge Comments RM7896A1012/U intermittent Intermittent 4 sec or 10 sec No 15 sec Includes Pre- and Post-Purge. RM7896C1010/U interrupted 10 sec 4 sec or 10 sec Yes 15 sec Includes Pre- and Post-Purge. RM7896D1019/U interrupted Dynamic 10 sec 4 sec or 10 sec Yes 15 sec Includes Pre- and Post-Purge. RM7896D1027/U interrupted Dynamic 10 sec 4 sec or 10 sec Yes 60 sec Blinking Fault code LED, early spark termination when flame sensed, pre- and post-purge 70-6910 771 Commercial/Industrial Combustion Controls Microprocessor Burner Controls RM7897 Automatic Primary Control with Programmable Post-Purge Microprocessor-based integrated full-function primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Programmable Post-Purge. Requires S7800A1142 Display to program post-purge feature. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Subbase, amplifier and purge card are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Five LEDs provide sequence information. Power LED blinks fault code on Safety Shutdown. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable recycle or lockout on loss of airflow or flame. • Shutter drive output. • Airflow switch check. • Delayed main valve. • Programmable post-purge using S7800A1142 Keyboard Display (not provided). Application: On-Off Primary Control with Pre- and Programmable Post-purge Flame Establishing Period - Pilot: 4 sec or 10 sec Interlocks: Selectable Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Control Safety Devices: Acceptable: CSD-1 Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Pilot Type Delayed Main Valve Comments Used With RM7897A1002/U 120 Vac (+10, -15%) selectable Includes blinking LED fault annunciation feature 7800 Series Amplifiers RM7897C1000/U 120 Vac (+10, -15%) selectable Yes Includes blinking LED fault annunciation feature 7800 Series Amplifiers 772 70-6910 Microprocessor Burner Controls RM7898 On-Off Primary Control with VPS Integrated full-function primary burner control for gas, oil, or combination fuel single burner applications. Include Programmable Post-Purge and Valve Proving Feature. Requires S7800A1142 Display to program VPS and post-purge features. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Subbase, amplifier and purge card are required for operation. • Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software. • Programmable post-purge. • Five LEDs provide sequence information. Power LED Blinks Fault code on safety shutdown. • Interchangeable plug-in flame amplifiers. • Local or remote annunciation of operation and fault information. • Nonvolatile memory retains history files and sequencing status after power loss. • Optional remote reset capability. • Optional report generation. • Selectable recycle or lockout on loss of airflow or flame. • Shutter drive output. • Airflow switch check. • Programmable post-purge and Valve Proving feature with S7800A1142 Keyboard Display (not supplied). Application: On-Off Primary Control w/VPS Flame Establishing Period - Pilot: 4 sec or 10 sec Interlocks: Selectable Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Required Components: Q7800A, B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz (±10%) Pilot Type: selectable Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 15 oz (0.9 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Pending Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. OX4A5.AF. Material Number Voltage Early Spark Terminations Comments Used With RM7898A1000/U 120 Vac (+10, -15%) Includes blinking LED fault annunciation feature 7800 Series Amplifiers RM7898A1018/U 120 Vac (+10, -15%) Special Sequence Includes blinking LED fault annunciation feature, with early spark termination 7800 Series Amplifiers 70-6910 773 Commercial/Industrial Combustion Controls Microprocessor Burner Controls R7120M Fireye M Series Replacement Control The Honeywell R7120M Burner Control Modules are microprocessor-based integrated burner controls. It is a plug in replacement of Fireye M series controls for automatically fired gas, oil or combination fuel on/off single burner applications. • Functions provided by the R7120M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Plug in replacement for Fireye M series controls using the existing Fireye wiring subbase. • Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement. Application: Replacement Primary Control for Fireye M Series - Intermittent Pilot Interlocks: Running PrePurge: Determined by ST7800A Purge Timer Card PostPurge: programmed with S7800A1142 display Required Components: R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card. Frequency: 50 Hz; 60 Hz Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +135°F (-40°C to +57°C) Approximate, Dimensions: 7 in. wide x 6 5/32 in. high x 5 3/4 in. deep (177 mm wide x 156 mm high x 146 mm deep) Weight lb. (kg): 3 lb 1 oz (1.4 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, FCC: FCC Part 15, Class B, Emissions. Material Number Voltage Pilot Type AirFlow Check Flame Establishing Period \- Main Flame Establishing Period \- Pilot Comments R7120M1001/U 120 Vac (+10, -15%) intermittent User selectable Intermittent 4 sec or 10 sec On/Off R7120M1019/U 120 Vac (+10, -15%) interrupted User selectable 10 sec 4 sec or 10 sec On/Off 774 70-6910 Microprocessor Burner Controls R7140 Programmers Dimensions in inches (millimeters) 5-3/4 (146) 1-1/4 (32) RESET POWER PILOT FLAME MAIN ALARM S \_ + 5 (127) 5 (127) 7 (177) 6-5/32 (156) BURNER CONTROL M22604A The Honeywell R7140G, L, M Burner Control Modules are microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications. • Functions provided by the R7140G, L, M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. • Upgrade replacement for BC7000 or R4140 legacy Programmer controls. • Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement. Application: Upgrade Replacement Programming Control for R4140 or BC7000 Preignition: Yes PrePurge: Determined by ST7800A Purge Timer Card PostPurge: 15 sec Early Spark Termination: Yes, 5 sec Required Components: R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card. Voltage: 120 Vac (+10, -15%) Frequency: 50 Hz; 60 Hz (±10%) AirFlow Check: User selectable Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 7 in. wide x 6 5/32 in. high x 5 3/4 in. deep (177 mm wide x 156 mm high x 146 mm deep) Weight lb. (kg): 3 lb 1 oz (1.4 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, FCC: FCC Part 15, Class B, Emissions. Material Number Pilot Type Flame Establishing Period \- Main Flame Establishing Period \- Pilot Second Stage Pilot Valve Interlocks Comments R7140G1000/U Interrupted or Intermittent 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec selectable Running LHL-LF Proven R7140G2008/U Interrupted or Intermittent 10 sec, or 15 sec, or 30 sec, or Intermittent 4 sec or 10 sec Running LHL-LF Proven R7140L1009/U interrupted 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout LHL-LF & HF Proven R7140L2007/U interrupted 10 sec or 15 sec 4 sec or 10 sec Interrupted Lockout LHL-LF & HF Proven R7140M1007/U Interrupted or Intermittent 10 sec or Intermittent 4 sec or 10 sec Intermittent Running On/Off-LF Proven 70-6910 775 Commercial/Industrial Combustion Controls Microprocessor Burner Controls Q7800 22 Terminal Universal Wiring Subbases Burner, panel or wall mount subbases for 7800 SERIES relay modules and S7830A Expanded Annunciator. • Makes electrical connections for 7800 SERIES relay modules or S7830A Expanded Annunciator through bifurcated contacts. • Provides terminals for field wiring. • Twenty-two terminals. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approvals, CSA: Certified, File No. LR95329-3. Material Number Application Approximate, Dimensions Weight lb. (kg) Approvals, Underwriters Laboratories Inc. Comments Used With Q7800A1005/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in. deep (126 mm wide x 126 mm high x 36 mm deep) 7 oz (0.20 kg) Component Recognized, File No. MP268; Guide No. MCCZ2. Panel mount Q7800B1003/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 1 13/32 in. deep (126 mm wide x 126 mm high x 36 mm deep) 1 lb 3 oz (0.54 kg) Component Recognized, File No. MP268; Guide No. MCCZ. Burner/wall mount 2 knockouts each end Q7800B1011/U Wiring Subbase 4 31/32 in. wide x 4 31/32 in. high x 3 in. deep (126 mm wide x 126 mm high x 76 mm deep) 1 lb 3 oz (0.54 kg) Component Recognized, File No. MP268; Guide No. MCCZ. Burner/wall mount 3 knockouts each end Q7800F1004/U Wiring Adapter Subbase 5 in. high x 5 in. wide x 1 3/4 in. deep (127 mm high x 127 mm wide x 44 mm deep) 15 oz (0.43 kg) Component Recognized, File No. MP268; Guide No. MCCZ2. Burner/wall mount adapter subbase for RA890 RM7890 Q7800F1012/U Wiring Adapter Subbase 5 in. high x 5 in. wide x 1 3/4 in. deep (127 mm high x 127 mm wide x 44 mm deep) 15 oz (0.43 kg) Component Recognized, File No. MP268; Guide No. MCCZ2. Burner/wall mount adapter subbase for R4795 RM7895 Q7800A dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F USE NO. 6 MOUNTING SCREWS (4) M1968D 1 OPTIONAL TERMINAL TEST ACCESS COVER. 4-31/32 (126) 2-1/2 (64) 1-11/32 (34) 1-11/32 (34) 2-9/32 (58) 4-31/32 (126) 1-13/32 (36) 1 Q7800F dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F (11) 5 (127) 5 (127) M5648A 1-3/4 (44) 1/4 (6) 776 70-6910 Microprocessor Burner Controls Q7800B1003 dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F 7/8 in. DIA. KNOCKOUTS (7) FOR 1/2 in. CONDUIT USE NO. 6 MOUNTING SCREWS (4) 1 (25) 1 (25) M1966B REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 1 2-1/8 (54) 2-1/4 (64) 1-11/32 (34) 1-11/32 (34) 1-13/32 (36) 4-31/32 (126) 4-31/32 (126) 1-5/8 (41) 27/32 (21) 2-9/32 (58) 23/32 (18) 3/4 (19) 2-1/8 (54) 2-7/32 (56) 23/32 (18) 1/2 (12) Q7800B1011 dimensions in inches (millimeters) 12 13 14 15 16 17 18 19 20 21 22 G L2(N) 3 4 5 6 7 8 9 10 F 7/8 in. (22) KNOCKOUTS (9) FOR 1/2 in. CONDUIT USE NO. 6 MOUNTING SCREWS (4) 1 (25) 1 (25) M9883 REMOVE ONLY FOR TERMINAL TEST ACCESS. 1 1 2-1/8 (54) 2-1/4 (64) 1-11/32 (34) 1-11/32 (34) 1-13/32 (36) 4-31/32 (126) 4-31/32 (126) 1-5/8 (41) 27/32 (21) 2-9/32 (58) 23/32 (18) 3/4 (19) 3/4 (19) 2-1/8 (54) 3 (76) 23/32 (18) 3/4 (19) 3/4 (19) 70-6910 777 Commercial/Industrial Combustion Controls Microprocessor Burner Controls S7800 Keyboard Display Module Dimensions in inches (millimeters) 2 -1 /3 2 (5 2 ) BURNER CONTROL 29/32 (23) 19/32 (15) 1-1/4 (32) 1-1/32 (26) 5/32 (4) 5/16 (8) M22870 1/2 (13) 7/16 (11) 1-5/16 (49) 2-7/16 (62) 29/32 (23) 5/32 (4) 15/32 (12) 3-7/8 (99) 5/16 13/ (8) 32 (11) BACK ENTER Edit: - + 4-27/32 (123) 4-3/32 (104) 2-3/4 (69) Provides current status of burner sequence, timing information, hold information and lockout information, as well as selectable or preemptive messages. • Application flexibility. • First-out annunciation and system diagnostics provided by 2 row by 20 column Vacuum Fluorescent Display (VFD). • S7800A1001 offers “Call Service” (Business Card) programmable message displayed when system lockout occurs. • S7800A1001 series 5 and greater has selectable ModBus Feature. • Local or remote annunciation of operation and fault information. • First out expanded annunciation with 24 limit and interlock LEDs enhances keyboard display module information. • Remote reset. Application: Keyboard Display Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Comments S7800A1001/U 13 Vdc peak fullwave rectified (+20/-15%). English Language S7800A1035/U 13 Vdc peak fullwave rectified (+20/-15%). French Language S7800A1043/U 13 Vdc peak fullwave rectified (+20/-15%). German Language S7800A1050/U 13 Vdc peak fullwave rectified (+20/-15%). Italian Language S7800A1068/U 13 Vdc peak fullwave rectified (+20/-15%). Spanish Language S7800A1118/U 13 Vdc peak fullwave rectified (+20/-15%). Japanese Language S7800A1126/U 13 Vdc peak fullwave rectified (+20/-15%). Portuguese Language 778 70-6910 Microprocessor Burner Controls S7800 Keyboard Display Module for VP Programming Dimensions in inches (millimeters) 2 -1 /3 2 (5 2 ) BURNER CONTROL 29/32 (23) 19/32 (15) 1-1/4 (32) 1-1/32 (26) 5/32 (4) 5/16 (8) M22870 1/2 (13) 7/16 (11) 1-5/16 (49) 2-7/16 (62) 29/32 (23) 5/32 (4) 15/32 (12) 3-7/8 (99) 5/16 13/ (8) 32 (11) BACK ENTER Edit: - + 4-27/32 (123) 4-3/32 (104) 2-3/4 (69) Provides current status of burner sequence, timing information, hold information and lockout information, as well as selectable or preemptive messages. • Application flexibility. • First-out annunciation and system diagnostics provided by 2 row by 20 column Vacuum Fluorescent Display (VFD). • “Call Service” (Business Card) programmable message displayed when system lockout occurs. • Local or remote annunciation of operation and fault information. • First out expanded annunciation with 24 limit and interlock LEDs enhances keyboard display module information. Display can be Programmed to customize the expanded annunciator messages to the system. • Required to program Valve Proving and Post Purge feature on selected 7800 Series devices. • Can be setup for ModBus Communication. • Provides burner controller data. • Remote reset. Application: Keyboard Display for VP setup Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ. Approvals, CSA: Certified, File No. LR95329-3. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Comments S7800A1142/U 13 Vdc peak fullwave rectified (+20/-15%). English Language, Capable of displaying special “Call Service” messages, allows setup of S7830A1005 Expanded Annunciator messages, used for VPS programming, and programming Post Purge on select 7800 Devices S7800A1167/U 13 Vdc peak fullwave rectified (+20/-15%). Spanish Language with Valve Proving, Post-purge, “Call Service”, and Expanded Annunciator programming ability 70-6910 779 Commercial/Industrial Combustion Controls Microprocessor Burner Controls S7810A Data ControlBus™ Module Dimensions in inches (millimeters) M1986A BURNER CONTROL 2-3/4 (69) 29/32 (23) 5/32 (4) 4-27/32 (123) Supports remote mounting of S7800 Keyboard Display Module, personal computer communications interface and remote reset. • Use with remotely mounted S7800 Keyboard Display Module. • Installs directly on the front of 7800 SERIES Relay Modules. • Provides communications bus interface and remote reset. Application: ControlBus™ Module Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 3 11/32 in. high x 29/32 in. deep (123 mm wide x 84 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Comments S7810A1009/U 13 Vdc peak fullwave rectified (+20/-15%). Includes 203541 5-wire Connector S7810M ModBus Module Dimensions in inches (millimeters) 1-1/8 (29) M11349B 7/16 (11) 2-3/4 (69) 5/32 (4) 4-27/32 (123) 29/32 (23) BURNER CONTROL MODE S7810M ModBus Module operates as ModBus RTU slave device. • Provides ability to remotely mount the S7800 Keyboard Display Module. • Installs directly on the front of 7800 SERIES Relay Modules. • Provides ModBus communications bus interface. • Remote reset. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 4 oz (0.11 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Voltage Application Comments Approvals, Gastec/European S7810M1003/U 13 Vdc peak fullwave rectified (+20/-15%). ControlBus™ Module-MODBUS Includes 208727 8 pin electrical connector S7810M1029/U 13 Vdc peak fullwave rectified (+20/-15%). ControlBus™ Module-MODBUS - CE Certified (no reset allowed) Includes 208727 8 pin electrical connector Gastec EN268 Report 1156791 780 70-6910 Microprocessor Burner Controls S7820 Remote Reset Module Dimensions in inches (millimeters) M1986A BURNER CONTROL 2-3/4 (69) 29/32 (23) 5/32 (4) 4-27/32 (123) Serves as link between remote reset pushbutton and relay module. Allows 7800 SERIES relay module to be reset from a remote location. • Reset button can be installed up to 1000 feet away. • Installs directly on the front of 7800 SERIES relay module. Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 4 27/32 in. wide x 2 29/32 in. high x 29/32 in. deep (123 mm wide x 73 mm high x 23 mm deep) Weight lb. (kg): 3 oz (0.09 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Report No. 1V9AO.AF. Material Number Application Comments S7820A1007/U Remote Reset Module Includes 203541 5-wire Connector 70-6910 781 Commercial/Industrial Combustion Controls Microprocessor Burner Controls S7830 First Out Expanded Annunciator Microprocessor-based expanded annunciator to support the 7800 SERIES relay modules for first-out annunciation, sequencing, system or self-diagnostics and troubleshooting. • Twenty-six status LEDs. • Front panel LED array-arranged to indicate flow of line-voltage through string of limits, controls and interlocks. • Selectable current and first-out LED array display status. • Twenty-one monitored contact points. • Access for external electrical voltage checks. Required Components: 7800 Series Relay Modules and Q7800A, B Subbases Frequency: 50 Hz; 60 Hz (±10%) Vibration: 0.5 G environment Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase) Weight lb. (kg): 1 lb 6 oz (0.62 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MH17367; Guide No. MJAT. Approvals, CSA: Certified, File No. LR95329. Approvals, FCC: FCC Part 15, Class B, Emissions. Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Report No. 1V9AO.AF. Dimensions in inches (millimeters) 5 (127) 5-5/16 (135) 5 (127) EXPANDED ANNUNCIATOR M5182 Proof of Closure Preignition Interlocks L1 Burner Switch Power Operating Control Auxiliary Limit 1 Auxiliary Limit 2 Low Water Cutoff High Limit Atomizing Limit 3 Oil Select High Oil Pressure Low Oil Pressure High Oil Temperature Low Oil Temperature Select Atomizing Switch Gas Select High Gas Pressure Low Gas Pressure System Lockout First Out Current Airflow Switch Auxiliary Interlock 4 Auxiliary Interlock 5 Reset Interlocks a b c Fuel Selection 22 21 20 19 18 17 16 15 14 13 12 Material Number Voltage Application S7830A1005/U 120 Vac (+10, -15%) Expanded Annunciator 782 70-6910 Microprocessor Burner Controls ST7800 Plug In Purge Timer Provides the prepurge timing for select 7800 SERIES relay modules. ST7800C used with the RM7838C only. Approvals, Underwriters Laboratories Inc.: Component Recognized, File No. MP268; Guide No. MCCZ2. Approvals, CSA: Certified, File No. LR95329-3. Approvals, Factory Mutual: Approved: Report No. 2X0A1.AF. Material Number PrePurge Application ST7800A1005/U 2 seconds Purge Timer ST7800A1013/U 7 seconds Purge Timer ST7800A1021/U 10 seconds Purge Timer ST7800A1039/U 30 seconds Purge Timer ST7800A1047/U 40 seconds Purge Timer ST7800A1054/U 60 seconds Purge Timer ST7800A1062/U 90 seconds Purge Timer ST7800A1070/U 2.5 minutes Purge Timer ST7800A1088/U 4.0 minutes Purge Timer ST7800A1096/U 6.0 minutes Purge Timer ST7800A1104/U 9.0 minutes Purge Timer ST7800A1112/U 12.0 minutes Purge Timer ST7800A1120/U 15.0 minutes Purge Timer ST7800A1138/U 22.0 minutes Purge Timer ST7800A1146/U 30.0 minutes Purge Timer ST7800C1003/U 7 seconds Purge Timer for RM7838C Only ST7800C1011/U 20 seconds Purge Timer for RM7838C Only ST7800C1029/U 4.0 minutes Purge Timer for RM7838C Only ST7800C1037/U 6.0 minutes Purge Timer for RM7838C Only ST7800C1045/U 8.0 minutes Purge Timer for RM7838C Only ST7800C1052/U 10.0 minutes Purge Timer for RM7838C Only ST7800C1086/U 16.0 minutes Purge Timer for RM7838C Only ST7800C1102/U 20.0 minutes Purge Timer for RM7838C Only ST7800C1128/U 24.0 minutes Purge Timer for RM7838C Only ST7800C1136/U 30.0 minutes Purge Timer for RM7838C Only 70-6910 783 Commercial/Industrial Combustion Controls Microprocessor Burner Controls 7800 Series Accessories or Parts Application: Accessory or Replacement Part Material Number Comments Used With 203541/U S7800 Display 203765/U Includes 203541 5-wire Connector S7800 Display 204718A/U Includes 203541 5-wire Connector S7800 Display 204718B/U Includes 203541 5-wire Connector S7800 Display 204718C/U Includes 203541 5-wire Connector S7800 Display 205321B/U Includes 203541 5-wire Connector S7800 Display 206311/U Carrying Case for S7800 Display S7800 Display 208727/U S7810B, S7810M 221729A/U 7800 Relay Modules 221818A/U S7800 Display 221818C/U S7800 Display 50023821-001/U Includes 203541 5-wire Connector S7800 Display 50023821-002/U Includes 203541 5-wire Connector S7800 Display 784 70-6910 SOLA Controllers SOLA™ Hydronic Control Dimensions in inches (millimeters) M27583 9-21/64 (237) MAX \[2\] 8-21/32 (220) 6-21/64 (161) \[2\] 5-19/64 (135) \[4\] Ø 3/16 (5) MAX 2-19/32 (66) The R7910A SOLA HC is a hydronic boiler control system that provides heat control, flame supervision, circulation pump control, fan control, boiler control, and electric ignition function. It will also provide boiler status and error reporting. • Frost Protection, Slow Start, Anti-condensate, Boiler Delta-T, Stack Limit, Boiler Limit, DHW Limit, Outlet T-Rise Limit • Primary Flame Safeguard Control • Internal or external spark generator. • Analog NTC Sensor Inputs (10 kohm or 12 kohm). • Other Analog Inputs • PID Load Control • Digital Inputs • Digital Outputs • Analog Outputs • Algorithm Prioritization • Two Temperature Loops of Control (CH and DHW) • High Limit Control-CH, DHW, & Stack (Meets UL 353) using dual 10 kohm NTC sensors. • Fifteen Item Fault Code History including equipment status at time of lockout • Fifteen Item Alert Code Status including equipment status at time of internal alerts • 24 Vac Device Power • 24 or 120 Vac Digital I/O models available. • Flame Signal test jacks (Vdc) • Three Status LEDs. • UV or Flame rod Flame Sensing. Application: Hydronic Frequency: 50-60 Hz ± 5% Approximate, Dimensions: 9 21/64 in. x 6 21/64 in. x 2 19/32 in. (237 mm x 161 mm x 66 mm) Comments: Includes Programmable features Approvals, Control Safety Devices: Acceptable Approvals, FCC: Part 15, Class B Emissions Material Number Enclosure Rating Firing Rate Switch Flame Sensor Type Modulation Output Voltage Approvals, Underwriters Laboratories Inc. R7910A1001/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 24 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1019/U NEMA 1/IP 40 High Fire Switch; Low Fire Switch FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1027/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1084/U NEMA 1/IP 40 FR Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 24 Vac Load UL, cUL: Component Recognized: File Number MH20613 (MCCZ) R7910A1118/U NEMA I/IP 40 FR, High Energy Spark Yes (PWM) 24 Vac Operating; 24 Vac Load UL, cUL Component File No. MH20613 (MCCZ) 70-6910 785 Commercial/Industrial Combustion Controls SOLA Controllers SOLA™ Steam Control Dimensions in inches (millimeters) \[2\] 5-19/64 (135) 9-21/64 (237) MAX \[4\] Ø 3/16 (5) MAX 2-19/32 (66) 6-21/64 (161) \[2\] 8-21/32 (220) M27063 The R7911A SOLA SC is a steam boiler control system that provides heat control, flame supervision, fan control, boiler control, and electric ignition function. It will also provide boiler status and error reporting. • Slow Start, Stack Limit, Boiler Limit • Primary Flame Safeguard Control • Internal or external spark generator. • Analog Stack Temp NTC Sensor Inputs (10kohm or 12kohm). • Other Analog Inputs • PID Load Control • Digital Inputs • Digital Outputs • Analog Outputs • Algorithm Prioritization • High Limit Control - Stack (Meets UL 353) using dual 10 kohm NTC sensors. • Fifteen Item Fault Code History including equipment status at time of lockout • Fifteen Item Alert Code Status including equipment status at time of internal alerts • 24 Vac Device Power • 24 or 120 Vac Digital I/O models available. • Flame Signal test jacks (Vdc) • Three Status LEDs. • UV or Flame rod Flame Sensing. Application: Steam Frequency: 50-60 Hz ± 5% Approximate, Dimensions: 9 21/64 in. x 6 21/64 in. x 2 19/32 in. (237 mm x 161 mm x 66 mm) Comments: Includes Programmable features Approvals, Control Safety Devices: Acceptable Approvals, FCC: Part 15, Class B Emissions Approvals, Underwriters Laboratories Inc.: UL, cUL: Component Recognized: File Number MH20613 (MCCZ) Material Number Enclosure Rating Firing Rate Switch Flame Sensor Type Modulation Output Voltage R7911A1000/U NEMA 1/IP 40 FR/UV Yes (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load R7911A1026/U NEMA 1/IP 40 High Fire Switch; Low Fire Switch FR/UV No (PWM); Yes (4-20 mA); Yes (0-10 Vdc) 24 Vac Operating; 120 Vac Load 786 70-6910 SOLA Controllers S7910 SOLA™ Keyboard Display Dimensions in inches (millimeters) NOTE: STICKS OUT BACK 1/4 INCH (6). M27094 2-45/64 (69) 1-1/2 (38) 2-9/32 (58) 4-3/4 (121) 5-21/32 (144) 4-1/16 (103) 4X Ø 3/16 (5) ± 1/64 (0) The S7910 Local Keyboard display interface provides setpoint and control adjustments to parameters of the R7910 SOLA Hydronic Control. The S7910 includes four function buttons, and all data is displayed on an LCD with backlight. • Burner control state, sequence • Rate control manual adjustment • Lockout code • Alert and Hold Reason • CH, CH TOD, DHW, and DHW TOD setpoints • Communication interface with R7910. • First out and system status and diagnostics provided through the LCD. • Local communication of operation and fault information. • Control DHW, Inlet, Outlet, Delta T (Outlet-Inlet), and Stack Temperatures • Set-up • Diagnostics • Blue, includes (future feature: TOD), only “talks” to Commercial R7910A, Flame Signal Vdc, pilot hold function, screw mounting Ambient Temperature Range: 32°F to 120°F (0°C to 49°C) Shipping and Storage Temperature Range: -60°F to +150°F (-51°C to +66°C) Approximate, Dimensions: 4-1/6 in. high x 5-21/32 in. wide (103 mm high x 144 mm wide) Operating Humidity Range (% RH): 85% relative humidity continuous, noncondensing Weight: 4 oz (124 g) Approvals, FCC: Part 15, Class B emissions. Approvals, Underwriters Laboratories Inc.: UL, cUL: Component Recognized: File Number MH20613 (MCCZ) Material Number Electrical Ratings Vibration Description Used With S7910A1008/U 24 VAC powered from R7910A 0.5 G environment Keyboard Display Module R7910 70-6910 787 Commercial/Industrial Combustion Controls SOLA Controllers S7999D SOLA™ System Operator Interface The S7999D can be used to monitor an individual boiler and also used for multiple boiler applications in a lead/lag arrangement. It consists of 2 RS485 ports and a USB port. The S7999D display can be flush front or mounted behind in a panel cutout. Wiring connections are through a removable 8-pin wiring connector. • Individual boiler status, configuration, history and diagnostics • Allows configuration and monitoring of the Sola Controls (R7910 Hydronic Controls or R7911 Steam Control) burner control sequence, flame signal, diagnostics, historical files, and faults • Allows switching view between multiple boilers and lead-lag master/ slaves • Real-time data trending analysis and transferring saved trend data to Excel spreadsheet • 7” 800 x 480, 24 bit high resolution color LCD touch screen for clarity • Audio output with integral speaker for sound output. • Adjustable backlight control • Real time clock with coin-cell battery back-up (CR2032) • Volume control • Screen Capture function to capture screen images • USB port for file transfers and software updates • 2 RS-485 (COM1 & 2) ports for Modbus™ interface to Sola controls and BAS Gateway. • Windows® CE 6.0 Operating System • 8-pin connector, back-up battery and mounting hardware are provided Application: Interface Display Frequency: 50-60 Hz ± 5% Ambient Temperature Range: 14°F to 122°F (-10°C to 50°C) Shipping and Storage Temperature Range: -13°F to 155°F (-25°C to 60°C) Approximate, Dimensions: 9-13/32 in. wide x 6-21/32 in. high x 1-9/16 in. deep (239 mm wide x 169 mm high x 40 mm deep) Operating Humidity Range (% RH): 85% RH continuous, noncondensing Comments: Black Plastic Border Approvals, FCC: FCC Part 15, Class A digital device Approvals, Canadian Underwriters Inc.: Component Recognized: File Number MH20613 (MCCZ) Approvals, Underwriters Laboratories Inc.: Component Recognized: File Number MH20613 (MCCZ) Material Number Voltage Description Used With S7999D1006/U 24 Vac System Operator Interface with Black Plastic Border R7910/R7911 788 70-6910 SOLA Controllers PM7910 Program Module The PM7910 Program Module is an optional plug-in for the R7910 SOLA HC and R7911 Sola SC. From the system level the S7999 System Operator Interface can direct the R7910/R7911 to transfer or retrieve parameter information with the Program Module. • Can be removed or installed while the R7910 or R7911 is powered. • Facilitate multiple controller setups. • Backup and restore the R7910 programmable data including: — Non-safety parameter values — Parameter Control Blocks (information on how the parameter values may be modified.) Material Number Application Comments PM7910A1013/U Support backup and restore Indicator LEDs - One (Status LED) Blinking LED indicated the Program Module is properly seated and powered from the R7910/R7911 SOLA™ Accessories or Parts Application: Single element sensor with 6" leadwire with socket. Material Number Application 32003971-002/U 10K Ohm Single element sensor with 6" Leadwire with Socket 32003971-003/U 10K Ohm Single element sensor with 42" leadwires, includes wire nuts (2), #8 mounting screws (3), anchors (2), sensor clip (1), tie strap (2) 50001464-006/U 10K Ohm Dual Element Sensor with 6" leadwires with Female Socket 50001464-007/U 10K Ohm Dual Element Sensor with 42" leadwires without connector 50032893-001/U Bag of connectors for R7910 and R7911 Controllers 70-6910 789 Commercial/Industrial Combustion Controls ControLinks Fuel Air Control System R7999A ControLinks™ Fuel Air Controller 1-15/16 (48) 5-3/16 (131) 7-3/16 (182) 2-13/16 (71) 3 (76) INSTALLED ON Q7999 M16548C R7999 Q7999 1 DDL PORT (RS485). 1 Uses microprocessor-based technology to control the ML7999 Universal Parallel Positioning Actuators. This represents a value added replacement of mechanical cam and linkage assembly controlling the relationship between fuel, airflow and flue gas recirculation (if used) on a power burner. The ControLinks Fuel Air Control System consists of the R7999 Fuel Air Controller, Q7999 Wiring Subbase, ML7999 Universal Parallel Positioning Actuator and ZM7999 Configuration Software. The R7999, with one communications port, provides communications capabilities similar to those found in the 7800 SERIES controls. • Fast burner setup via PC or laptop • Fuel, air, FGR profile download capability • Two independent fuel profiles with or without FGR • 7 to 24 point profiles • Programmable behaviors of all actuators during Purge and Standby • Programmable behavior of non-selected fuel actuator • Independent light off and minimum modulation positions • Wide power voltage input range (100 to 120 Vac, 50/60 Hz Auto/Manual input) • Manual mode firing rate input • Pluggable controller to wiring subbase • Multipurpose communications port • Field-configurable device • Integrated boiler shock protection algorithms: Water temperature low fire hold • Stack temperature low fire hold. FGR and low fire hold • Selectable FGR hold based on stack temperature • Programmable behavior of FGR actuator during purge • Maximum modulation limit capability • Remote reset input • Automated actuator endpoint seeking process • CSD-1 and NFPA acceptable Voltage: 100 to 120 Vac Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +140°F (-40°C to +60°C) Approvals, Underwriters Laboratories Inc.: Listed: Report No. MH17367 Operating Humidity Range (% RH): 90% RH maximum, noncondensing Replacement Parts: 32002515-001/U – 3 pin electrical connector, for R7999 Material Number Frequency Description R7999A1005/U 50 Hz; 60 Hz Fuel Air Ratio Controller, 100 to 120 Vac, 50/60 Hz. 790 70-6910 ControLinks Fuel Air Control System S7999 ControLinks™ System Display With the S7999. Each burner control, fuel/air ratio control, expanded annunciator other Modbus devices present on the burner system can be viewed individually to determine its status. • Color (7" diagonal). Touch Screen User Interface • Flush Mounting • Allows setup and monitoring of R7999 ControLinks • Two RS485 and one USB communication ports • Screen saver, contrast control and volume control • Modbus communication allows monitoring up to 99 different controls • Allows Programmable Expanded Annunciator terminal naming • Allows R7999 ControLinks EEPROM backup and restore • Battery backup prevents losing date and time Application: Interface Display Temperature Range: Ambient - 14°F to 122°F (Ambient - -10°C to 50°C) Shipping and Storage Temperature Range: -13°F to 155°F (-25°C to 60°C) Approvals, Underwriters Laboratories Inc.: Component Listed Approvals, FCC: FCC Part 15, Class A digital device Used With: R7999 Operating Humidity Range (% RH): 85% RH continuous, noncondensing Material Number Voltage Description S7999D1048/U 24 Vac S7999D System Display for R7999 ControLinks Configuration and System Monitoring Q7999A ControLinks™ Fuel Air Control Wiring Subbase Provides terminals for field wiring for the R7999A ControLinks™ Fuel Air Controller. Terminals on the R7999A, B Controller engage the Q7999 contacts to make electrical connections. The Q7999A Subbase is panel-mounted. • Quick-mount wiring subbase for R7999A, B Fuel Air Ratio Controllers. • Allows wiring of control system before installation of controller. • Panel-mounted. • NEMA 1 enclosure. Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +150°F (-40°C to +65°C) Approvals, Underwriters Laboratories Inc.: Listed: Report No. MH17367 Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Weight oz. (k): 10 oz (0.28 kg) Material Number Voltage Frequency Description Q7999A1006/U 100 to 120 Vac 50 Hz; 60 Hz Fuel Air Ratio Controller Wiring Subbase Q7999A1014/U 100 to 120 Vac 50 Hz; 60 Hz Fuel Air Ratio Controller Wiring Subbase 70-6910 791 Commercial/Industrial Combustion Controls ControLinks Fuel Air Control System ML7999A Universal Parallel-Positioning Actuator ML7294 Non-Spring Return Direct Coupled Actuators control dampers or valves in HVAC applications. The ML7294 Non-Spring Return DCA accepts a current or voltage signal from an electronic controller to position a damper or valve. • Password protected using eight-digit hexadecimal identification signal • Separate wiring compartment between line voltage power wiring and low voltage control • Couples directly to a 1/2-in. shaft with no additional parts required; couples directly to 5/16-in. and 3/8-in. shafts using self-centering shaft reduction accessories • Shaft coupler assembly available for shafts larger than 1/2-in. • Bracket accessory kit available for mounting to Honeywell V51 butterfly gas valves • Visual indication of actuator position • NEMA 2 • IF54 with weatherproof kit Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +150°F (-40°C to +65°C) Approvals, Underwriters Laboratories Inc.: Meets UL873 Approvals, CSA: Certified Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Approvals, CE: Certified Material Number Voltage Frequency Description ML7999A2001/U 15 VA, 100 to 240 Vac 50 Hz; 60 Hz Universal Parallel-Positioning Actuator. Medium torque electronic actuator with a precision feedback potentiometer and integral power supply capable of direct line voltage connection. Must be used with a Series 2 R7999. ML7999B Universal Direct Coupled Actuator Dimensions in inches (millimeters) 4 (102) 7/8 (22) 1-7/8 (47) 1/2 (13) 3-1/2 (89) 1-5/8 (41) 5-1/2 (140) 6 (153) M16466 1/4-28 unF Honeywell ML7999B universal direct coupled actuator provides 100 lb-in. torque, 4 to 20 mA control input to control combustion air dampers and modulation valves. Includes precision drive shaft control and integral power supply. • Separate wiring compartment between line voltage power wiring and low voltage control • Programmable actuator stroke against 4-20 mA input • Couples directly to 1/2-in. shaft with no additional parts required; couples directly to 5/16- and 3/8-in. shafts using available selfcentering shaft reduction accessories • Shaft coupler assembly available for shafts larger than 1/2-in. • Bracket accessory kit available for mounting to Honeywell V51 butterfly gas valves • Visual indication of actuator position • NEMA 2 • IF54 with weatherproof kit Vibration: 0.0 to 0.5g continuous Shipping and Storage Temperature Range: -40°F to +150°F (-40°C to +65°C) Approvals, Underwriters Laboratories Inc.: Meets UL873 Approvals, CSA: Certified Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Approvals, CE: Certified Accessories: 32002935-001/U – Weatherproofing kit for actuator, ML7999 ControLinks (NEMA 3). Material Number Voltage Frequency Description ML7999B1002/U 15 VA, 100 to 240 Vac 50 Hz; 60 Hz Universal Parallel-Positioning Actuator. Medium torque electronic actuator with a precision feedback potentiometer and integral power supply capable of direct line voltage connection. 792 70-6910 ControLinks Fuel Air Control System ML7999 Accessories Material Number Description 201391/U Shaft Adapter for 3/8 in. round or square valve shaft 32002935-001/U Weatherproofing kit for actuator, ML7999 ControLinks (NEMA 3). 32003167-001/U Shaft Adapter for 5/16 in. round or square shaft 32003168-001/U Shaft Adapter for 3/4 in. round shaft only 32003168-002/U Shaft Adapter for 5/8 in. round shaft only 32003168-003/U Shaft Adapter for 9/16 in. round shaft only 32003396-002/U V51E Mounting Kit for ML7999 Actuator (2-1/2, 3 & 4 in. valves). Includes angle bracket, mounting bracket, screws, nuts and washers, and instructions. 50036542-001/U Auxiliary Switch Mounting Plate for ML7999B for 201052A or 201052B Auxiliary switch assembly ZM7999A ControLinks Fuel Air Control System Configuration Software The ZM7999 Software Configuration Tool reduces burner setup time by letting you create an R7999 Controlinks burner modulation curve. The software assists you through the commissioning process and when it’s complete, you can monitor the system realtime. • Minimum Hardware Requirements: PC or laptop with a Pentium© processor. • Windows® 95 or Windows® 98. • 16 MB of RAM. • 1G hard drive with 100 MB of free memory. • 4X (or higher) CD-ROM drive. • Mouse. • Super VGA color monitor (800 x 600 resolution suggested). Material Number Description Used With ZM7999A1006/U Configuration Software R7999 ControLinks Accessories Material Number Description Used With 32002515-001/U 3 pin electrical connector, for R7999 R7999 50020034-001/U 9 pin electrical connector, for S7999B S7999B 70-6910 793 Commercial/Industrial Combustion Controls Network Interface Communications QM4520A Data Acquisition Module The QM4520A RS-232 to RS485 Converter allows a PC to communicate with multiple devices on a single bus, over greater distances. • Mount on DIN rail, panel or in a piggyback stack. • Uses unregulated power between +10 Vdc and +30 Vdc. • Transmit data on single twisted pair (RS-485). • Plug-in screw terminal blocks assure simple installation, maintenance and modification. • Clean and reliable communications assured by noise-suppressing special circuitry. • RS-485 communications reduce the number of required cables, connectors and conditioners. • Modules can be remotely mounted up to 4,000 ft (1.2 km) away. Electrical Connections: Plug-in screw terminal block. Ambient Temperature Range: 32°F to 158°F (0°C to 70°C) Voltage: Unregulated +10 Vdc to +30 Vdc - Power supply not provided. Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Approximate, Dimensions: 2 11/32 in. x 4 13/16 in. x 1 3/16 in. (60 mm x 122 mm x 30 mm) Material Number Connection Type Description Used With QM4520A1004/U RS-232 (4-wire: TX, RX, RTS, GND) (Null modem may be required.) RS-232 to RS-485 Converter ZM7850 or ZM7999 software 794 70-6910 Flame Amplifiers 7800 SERIES and R7140 Flame Signal Amplifiers Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules. • Flame failure response time of 0.8 or 3.0 seconds (1.0 or 2.0 for CE approved devices). • Flame signal strength ranges from 0.0 to 5.0 Vdc. • Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation. • Flame signal test jacks to measure amplifier flame signal voltage. • Color-coded labels identify flame detection type. • Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system. • Ampli-check tests the amplifier and 7800 SERIES Relay. • None (standard) is just tested at normal system startup. • 7800 SERIES relay module locks out on safety shutdown with flame detection system failure. • Compatible with existing Honeywell flame detectors (order separately). Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. LR95329-3 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 1V9A0.AF Material Number Type Flame Failure Response Time (sec) Self Checking Use With Primary Safety Control Use With Flame Sensor Comments R7824C1002/U Ultraviolet 3.0 sec Dynamic Self-Check RM7824 C7024E, F Flame Detector Color: Green R7847A1025/U Rectification 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179 Color: Green R7847A1033/U Rectification 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179; Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C Color: Green R7847A1074/U Rectification 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847A1082/U Rectification 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847B1023/U Rectification 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179 Color: Green R7847B1031/U Rectification 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179; Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C Color: Green R7847B1064/U Rectification 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847B1072/U Rectification 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas: Rectifying Flame Rods C7004, 5, 7, 8, or 9, Q179 for impedance matching for leadwire runs > 50' or Ultraviolet Flame Sensor C7012A, C Color: Green R7847C1005/U Rectification 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7012E, F Color: Green R7848A1008/U Infrared 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7015 Color: Red R7848B1006/U Infrared 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7015 Color: Red R7849A1015/U Ultraviolet 0.8 sec or 1.0 sec None (standard) 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7849A1023/U Ultraviolet 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7849B1013/U Ultraviolet 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7849B1021/U Ultraviolet 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil: Minipeeper C7027A, C7035A, C7044 Color: Purple R7851B1000/U Optical 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil, Coal: Optical (UV, Visible Light) C7927, C7962 Color: White R7851B1018/U Optical 0.8 sec or 1.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, Oil, Coal: Optical (UV, Visible Light) C7927, C7962 Color: White R7851C1008/U Optical 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Optical (UV only) C7961E, F Color: White R7852A1001/U Infrared 2.0 sec or 3.0 sec None (standard) 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7915 Color: Red/White R7852B1009/U Infrared 2.0 sec or 3.0 sec Ampli-Check 7800 SERIES Relay Modules Gas, oil, coal: Infrared (lead sulfide) C7915 Color: Red/White R7861A1026/U Ultraviolet 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7061 Color: Purple R7861A1034/U Ultraviolet 0.8 sec or 1.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Ultraviolet Flame Sensor C7061 Color: Purple R7886A1001/U Ultraviolet 2.0 sec or 3.0 sec Dynamic Self-Check 7800 SERIES Relay Modules Gas, oil, coal: Adjustable Sensitivity Ultraviolet Flame Sensor C7076 Color: Blue 70-6910 795 Commercial/Industrial Combustion Controls Flame Amplifiers R7247; R7248; R7249; R7476 Flame Amplifiers Solid state plug-in units respond to flame detector signal and indicate presence of flame. • Use with BC7000; R4140; R4075C, D, E; R4138C, D Flame Safeguard controls and appropriate flame detector and FSP5075A1, FSP5075A3 Flame Amplifier Modules. Use With Primary Safety Control: R4140; BC7000; R4075C, D, E; R4138C, D; FSP5075 Approvals, Factory Mutual: Approved: Report No. 24181.01 Material Number Type Flame Failure Response Time (sec) Self Checking Use With Flame Sensor Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Control Safety Devices Approvals, Swiss RE Comments R7247B1003/U Rectification 2 to 4 sec Ampli-Check Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179; Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C Listed: File No. MP268, Guide No. MCCZ2 Certified: File No. LR1620, Guide No. 140-A-2 Acceptable (CSD-1) Acceptable Color: Green R7247C1001/U Rectification 2 to 4 sec Dynamic Self-Check Gas, oil, coal: Ultraviolet Flame Sensor C7012E, F Listed: File No. MP268, Guide No. MCCZ2 Certified: File No. LR1620, Guide No. 140-A-2 Acceptable (CSD-1) Acceptable Color: Green R7248A1004/U Infrared 2 to 4 sec None (standard) Gas, oil, coal: Infrared (lead sulfide) C7015 Listed: File No. MP268, Guide No. MCCZ Certified: File No. LR1620, Guide No. 140-A-2 (gas), 300-I-0.2 (oil) Acceptable (CSD-1) Acceptable Color: Red R7249A1003/U Ultraviolet 2 to 4 sec None (standard) Gas, oil, coal: Ultraviolet (Minipeeper) C7027, C7035 Listed: File No. MP268, Guide No. MCCZ2 Certified: File No. LR1620, Guide No. 140-A-2 Acceptable (CSD-1) Acceptable Color: Purple R7476A1007/U Ultraviolet 2 to 4 sec Dynamic Self-Check Gas, oil, coal: Adjustable Sensitivity Ultraviolet Flame Sensor C7076 Listed: File No. MP268, Guide No. MCCZ Certified: File No. LR1620, Guide No. 140-A-2 (gas), 300-I-0.2 (oil) Color: Blue R7476A1015/U Ultraviolet 2 sec max. Dynamic Self- Check Gas, oil, coal: Adjustable Sensitivity Ultraviolet Flame Sensor C7076 Listed: File No. MP268, Guide No. MCCZ Certified: File No. LR1620, Guide No. 140-A-2 (gas), 300-I-0.2 (oil) Color: Blue Flame Amplifier Accessories Material Number Description Used With 32005301-001/U T Filter for Rectification Applications R7847, R7247 796 70-6910 Flame Rods and Flame Rod Holders C7007 Flame Rod Holder Used to apply flame rod in gas-fired system controlled by rectification type flame safeguard control. • Use with pressurized fire boxes. • Hold flame rods firmly over the pilot or burner with a chuck and setscrew arrangement. • Provide electrical connection through a terminal screw. • Allow ventilation to cool the unit or to minimize soot deposit through a 1/2 in. • NPT tapping. • Mount easily with sleeve or thread type mounting adapters, and a straight or angle body. Type: Flame Rod Application: Gas fired pilot or gas fired system. Approximate, Dimensions: 1 15/16 in. high x 2 3/16 in. diameter x 3 3/16 in. long (49 mm high x 56 mm diameter x 81 mm long) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. L95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Material Number Electrical Connections Mounting Required Components Comments Used With C7007A1001/U Terminal screw 1/2 in.-14 NPT male 102709A -12 in. Flame Rod; 102709B -18 in. Flame Rod; 102709C -24 in. Flame Rod; 102709D -36 in. Flame Rod; or 102709E -48 in. Flame Rod Holder only, order Kanthal flame rod separately. Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008 Flame Rod Holder Miniature “spark plug” type flame rod holder with threaded base, snap-on cover and Kanthal A-1 Flame Rod. • Use with Honeywell Flame Safeguard controls requiring rectificationtype flame detection. • Use only with gas. • Install with or without cover. • Comes in several different lengths and can be cut to exact desired length. • Uses Rajah electrical connector. Type: Flame Rod Application: Gas fired pilot or gas fired system. Approximate, Dimensions: Holder: 7/8 in. diameter x 3 3/4 in. long (Holder: 22 mm diameter x 95 mm long) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. L95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Material Number Electrical Connections Mounting Includes Used With C7008A1000/U Rajah electrical connector 1/4 in. NPT male 6" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1018/U Rajah electrical connector 1/4 in. NPT male 12" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1026/U Rajah electrical connector 1/4 in. NPT male 18" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1034/U Rajah electrical connector 1/4 in. NPT male 24" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1174/U Rajah electrical connector 1/4 in. NPT male 12" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7008A1182/U Rajah electrical connector 1/4 in. NPT male 24" Flame rod and holder Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 70-6910 797 Commercial/Industrial Combustion Controls Flame Rods and Flame Rod Holders C7009 Flame Rod Holder Subminiature “spark plug” type flame rod holder with flame rod. • Use on industrial flame-retention gas burner nozzles. • Works with Honeywell Flame Safeguard controls requiring rectification type flame detector. • Mounts in areas with limited space because flame rod can be cut to desired length. • Uses Rajah electrical connector. Type: Flame Rod Application: Gas fired pilot or gas fired system. Approximate, Dimensions: Holder: 3/8 in. diameter x 2 3/8 in. long (Holder: 10 mm diameter x 60 mm long) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. L95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Material Number Electrical Connections Mounting Includes Comments Used With C7009A1009/U Rajah electrical connector 1/8 in. NPT male Flame rod and holder 4 in. (102 mm) flame rod Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 C7009A1025/U Rajah electrical connector 1/8 in. NPT male Flame rod and holder 12 in. (305 mm) flame rod Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289 Flame Rod Detector Accessories or Parts Material Number Description 102709B/U Kanthal Flame Rod - 18 in. (.182" diameter) for C7004B, C7007A, C7011A 102709C/U Kanthal Flame Rod - 24 in. (.182" diameter) for C7004B, C7007A, C7011A 102709D/U Kanthal Flame Rod - 36 in. (.182" diameter) for C7004B, C7007A, C7011A 105478A/U Kanthal Flame Rod - 6 in. (.182" diameter-threaded 6-32) for C7008 105478B/U Kanthal Flame Rod - 12 in. (.182" diameter-threaded 6-32) for C7008 105478C/U Kanthal Flame Rod - 18 in. (.182" diameter-threaded 6-32) for C7008 105478D/U Kanthal Flame Rod - 24 in. (.182" diameter-threaded 6-32) for C7008 798 70-6910 # ECC or Buildings Branch | Flame Safeguard part 2 Flame Detectors C7012 Solid State Purple Peeper® Ultraviolet Flame Detector Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels. • Mount horizontally, vertically or at any angle in between. • Provide quick electrical hookup with threaded conduit fitting and color-coded leadwires. • Reduced nuisance shutdowns by wiring two in parallel. • C7012E1278 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • C7012A, E meets NEMA 4 standards with viewing window rated to 20 psi. • C7012C, F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper Application: Gas, Oil or Coal fired burners Lead Length: 96 in. (2438 mm) Power Consumption: 2.5 W Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 14740.01 Material Number Frequency Weight NEMA Rating Electrical Connections Mounting Electrical Ratings Ambient Temperature Range Approvals, Underwriters Laboratories Inc. Approvals, Others Includes Used With C7012A1145/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, R7847A, R7257; Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1152/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 1 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1160/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 1 in. NPT 120 Vac -40°F to +175°F (-40°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1186/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 208 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1194/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 240 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012A1202/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 100 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, R7847A, R7257 C7012A1210/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 4 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover Flame Amplifiers: R7247A, R7847A, R7257 C7012C1042/U 50 Hz; 60 Hz 14.5 lb (6.6 kg) Explosion Proof 4 NEC Class 1 Colorcoded lead wires. 1 in. NPT 120 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. E34649, Guide No. ZTSZ Flame Amplifiers: R7247A, B; R7847A, B; R7257 C7012G1019/U 50 Hz 4.25 lb (1.9 kg) NEMA 4 5 NEC Class 1 Colorcoded lead wires. 3/4 in. NPT 220 Vac 25°F to 175°F (-4°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Meets DIN Standards Cast case and cover Flame Amplifiers: R7247C, R7847C 70-6910 799 Commercial/Industrial Combustion Controls Flame Detectors Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) 800 70-6910 Flame Detectors C7012 Solid State Purple Peeper® Ultraviolet Flame Detector (Self-Checking) Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels. • Mount horizontally, vertically or at any angle in between. • Provide quick electrical hookup with threaded conduit fitting and color-coded leadwires. • Reduced nuisance shutdowns by wiring two in parallel. • C7012E1278 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • C7012A, E meets NEMA 4 standards with viewing window rated to 20 psi. • C7012C, F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper, Self-Checking Application: Gas, Oil or Coal fired burners Lead Length: 96 in. (2438 mm) Power Consumption: 7.0 W Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 14740.01 Used With: Flame Amplifiers: R7247C, R7847C Material Number Frequency Weight NEMA Rating Electrical Connections Mounting Electrical Ratings Ambient Temperature Range Approvals, Underwriters Laboratories Inc. Approvals, Others Includes C7012E1104/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1112/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 1 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1120/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 1 in. NPT 120 Vac -40°F to +175°F (-40°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1146/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 208 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover, with Hot refractory tube C7012E1153/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 240 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012E1187/U 50 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 220 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ DIN (Europe) Cast case and cover C7012E1195/U 50 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 110 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ BGC (Europe) Cast case and cover C7012E1203/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 6 NEC Class 1 Color-coded lead wires. 3/4 in. NPT 240 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ BGC (Europe) Cast case and cover C7012E1278/U 50 Hz; 60 Hz 4.25 lb (1.9 kg) NEMA 4 Brad Harrison type number 41310 connector 1 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. MP268, Guide No. MCCZ Cast case and cover C7012F1052/U 50 Hz; 60 Hz 14.5 lb (6.6 kg) Explosion Proof 6 NEC Class 1 Color-coded lead wires. 1 in. NPT 120 Vac -20°F to +175°F (-20°C to +79°C) Listed: File No. E34649, Guide No. ZTSZ Explosion-proof, two piece, violet, cast aluminum enclosure Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) 70-6910 801 Commercial/Industrial Combustion Controls Flame Detectors C7024 Solid State Purple Peeper® Ultraviolet Flame Detector 24 Vdc solid state electronic flame detectors for sensing the ultraviolet radiation emitted by the combustion of most carbon containing fuels, such as natural gas, LP gases, and oil. • Use with R7824C Dynamic Self-Check Flame Signal Amplifier. • Circuitry provides low power consumption and high reliability. • Mount horizontally, vertically or at any angle in between. • Field-replaceable UV radiation sensing tube and quartz viewing window. • Quick electrical installation with threaded conduit fitting and colorcoded leadwires. • Reduce nuisance shutdowns by wiring two in parallel. • Oscillating shutter interrupts UV radiation using the R7824C amplifier. • C7024E meets NEMA 4 standards with viewing window rated to 20 psi. • C7024F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper, Self-Checking Application: Coal fired burners; Gas fired burners; Oil fired burners Lead Length: 96 in. (2438 mm) Electrical Connections: Six NEC CLASS 1 color-coded leaders Electrical Ratings: 24 Vdc Power Consumption: 7.8 W maximum. Ambient Temperature Range: -20°F to +175°F (-20°C to +79°C) Approvals, CSA: Certified: Master Report LR95329-3 Used With: Flame Amplifiers: R7824C Accessories: 190971G/U – 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961 Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) Material Number NEMA Rating Mounting Approximate, Dimensions Weight Approvals, Underwriters Laboratories Inc. Includes Comments C7024E1001/U NEMA 4 3/4 in. NPT 5 1/4 in. diameter (includes mounting flange) x 7 7/32 in. long (133 mm diameter (includes mounting flange) x 183 mm long) 4.25 lb (1.9 kg) Component Recognized: File No. MP268 Cast case and cover Flame Amplifiers: R7824C C7024F1009/U Explosion Proof 1 in. NPT 8 in. diameter x 12 in. long (203 mm diameter x 305 mm long) 14.5 lb (6.6 kg) Component Recognized: For use in hazardous locations; Class 1 Groups C and D; Class 2, Groups E, F and G; File no. E34649 Flame Amplifiers: R7824C 802 70-6910 Flame Detectors C7027; C7044 Minipeeper Ultraviolet Flame Detector Compact Flame Detector for use with flame safeguard controls with ultraviolet amplifiers. • Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection. • C7027 mounts on a 1/2 in. sighting pipe by using an integral collar. • Detectors can be wired in parallel for difficult sighting applications. • C7027 seals against pressures up to 5 psi (34.5 kPa) when correctly installed. • Allows for blast tube mounting due to compact size. • C7044 mounts with a two screw bracket. • The C7044 UV sensor tube is enclosed in a stainless steel housing. • C7044 has the capability of side or end viewing in flame monitoring applications. Type: Ultraviolet, Minipeeper Electrical Connections: 2 NEC Class 1 leadwires Vibration: 0.5 G max Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290 Material Number Application Lead Length Mounting Ambient Temperature Range Approvals, Others Includes Comments C7027A1023/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) Detects ultraviolet radiation in flames C7027A1031/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) Detects ultraviolet radiation in flames C7027A1049/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1056/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) DIN (Europe) Detects ultraviolet radiation in flames C7027A1064/U Coal fired burners; Gas fired burners; Oil fired burners 288 in. (7315 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1072/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1080/U Coal fired burners; Gas fired burners; Oil fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) 136733 Heat Block and 390427B bushing Detects ultraviolet radiation in flames C7027A1114/U Coal fired burners; Gas fired burners; Oil fired burners 44 in. (1118 mm) Integral nut for 1/2 in. sighting pipe. 0°F to 215°F (-18°C to +102°C) installed 22" flexible conduit Detects ultraviolet radiation in flames C7027A1122/U Oil fired burners; Gas fired burners; Coal fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to 215°F (-40°C to 102°C) 1/2 in. NPT threaded spud connector. Detects ultraviolet radiation in flames C7027A1130/U Gas fired burners; Oil fired burners; Coal fired burners 96 in. (2438 mm) Integral nut for 1/2 in. sighting pipe. -40°F to +215°F (-40°C to +102°C) Detects ultraviolet radiation in flames C7044A1006/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) Mounting Bracket provided 0°F to 215°F (-18°C to +102°C) Mounting bracket Detects ultraviolet radiation in flames \- Side Viewing Dimensiions in inches (millimeters) COLLAR WITH 1/2-14 NPSM INTERNAL THREADS 4 (102) 8 FOOT (2.44 METER) LEADWIRES (2) M1943G C7027A1064 HAS 24 FOOT (7.32 METER) LEADWIRES. C7027A1114 HAS 44 IN. (1.118 M) LEADWIRES WITH 22 IN. (558 MM) FLEXIBLE CONDUIT. 1 2 2 3-1/2 (89) 1-1/16 (27) 1 MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL THREADS) INSTEAD OF CLAMP TYPE CONNECTOR. 6 FOOT \[1.83 METER\] LEAD WIRES (2) 3-5/8 (92) 1/2 (13) 1-27/64 (36) 3/8 (10) 7/8 (22) 9/16 (14) M1944D MOUNTING BRACKET 70-6910 803 Commercial/Industrial Combustion Controls Flame Detectors C7035 Minipeeper Ultraviolet Flame Detector Dimensiions in inches (millimeters) 1/2-14 NPSM INTERNAL THREADS COLLAR WITH 2 (51) 2 1 - 11-1/2 NPSM INTERNAL THREADS 1 1 DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL MOUNTING THREADS. DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL MOUNTING THREADS. C7035A1056 HAS 12 FOOT (3.66 METER) LEADWIRES. 2 3 INSERTION DEPTH 6 FOOT \[1.83 METER\] LEADWIRES (2) 3 M1945E 2-5/8 (67) 1-1/2 (38) 31/32 (25) 4-1/8 (105) 1-3/16 (30) Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers. • Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection. • Mounts on a 1 in. sighting pipe by using an integral collar. • Protects the sensing tube with a shield. • Meets outdoor rain tight requirements of Underwriters Laboratories Inc., NEMA 4 and NEMA 4X. • Wires in parallel for difficult sighting applications. • Seals against pressures as high as 5 psi (34.5 kPa) when correctly installed. • Field-replaceable ultraviolet sensing tube. Type: Ultraviolet, Minipeeper NEMA Ratings: NEMA 3 and NEMA 4 Electrical Connections: 2 NEC Class 1 leadwires Vibration: 0.5 G max Mounting: Integral nut for 1 in. sighting pipe. Approximate, Dimensions: 1 1/2 in. diameter x 4 1/8 in. long (38 mm diameter x 105 mm long) Weight: 6 oz (0.17 kg) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Comments: Detects ultraviolet radiation in flames Used With: Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290 Material Number Application Lead Length Ambient Temperature Range Approvals, Others Includes C7035A1023/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) C7035A1031/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C) C7035A1049/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) DIN (Europe) C7035A1056/U Coal fired burners; Gas fired burners; Oil fired burners 144 in. (3658 mm) -40°F to +250°F (-40°C to +121°C) C7035A1064/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C) C7035A1080/U Coal fired burners; Gas fired burners; Oil fired burners 72 in. (1829 mm) 0°F to 250°F (-18°C to +121°C) 600F leads C7035A1098/U Oil fired burners; Gas fired burners; Coal fired burners 72 in. (1829 mm) -40°F to +250°F (-40°C to +121°C) 804 70-6910 Flame Detectors C7061 Dynamic Self-Check Ultraviolet Flame Detector Dynamic self-checking flame detector used with R7861 Dynamic Self-check Amplifiers for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels. • Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the UV sensor tube checking function. • Can be mounted horizontally, vertically or at any angle in between. • The detector requires faceplate alignment and has integral locating reference points to assure proper operation of the shutter mechanism. • Field replaceable ultraviolet sensing tube and quartz viewing window. • Models with threaded conduit fitting and color-coded leadwires allow rapid electrical installation. • C7061A1038 or A1046 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • Two detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications. • Protective heat block built into mounting flange. • -40°F (-40°C) rated ultraviolet sensing tube is supplied. • C7061E meets NEMA 4 standards with viewing window rated to 20 psi. • C7061F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Purple Peeper, Self-Checking Application: Gas fired burners; Oil fired burners Comments: Dynamic self-checking flame detector Used With: Flame Amplifiers: R7861 Approvals, Underwriters Laboratories Inc.: C7061A, M-Listed: File No. MP268, Guide No. MCCZ; C7061F-Recognized: For use in hazardous locations, Class 1 Groups C and D; class 2, Groups E, F and G; File no. E34649 Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 14740.01 Material Number NEMA Rating Lead Length Electrical Connections Mounting Electrical Ratings Frequency Ambient Temperature Range Approvals, Others C7061A1004/U NEMA 4 77 in. (1981 mm) PVC jacketed cable 3/4 in. NPT 120 Vac 50 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1012/U NEMA 4 96 in. (2438 mm) Color-coded leadwires 3/4 in. NPT 120 Vac 51 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1020/U NEMA 4 Terminal block 3/4 in. NPT 120 or 230 Vac 52 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1038/U NEMA 4 Brad Harrison type number 41310 connector 3/4 in. NPT 120 Vac 53 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1046/U NEMA 4 Brad Harrison type number 41310 connector 1 in. NPT 120 Vac 54 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061A1053/U NEMA 4 96 in. (2438 mm) Color-coded leadwires 1 in. NPT 120 Vac 55 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061F1003 Explosion Proof Terminal block 1 in. NPT 120 or 230 Vac 56 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) CE and conforms to EEXD IIc C7061F2001/U Explosion Proof 96 in. (2438 mm) Color-coded leadwires 1 in. NPT 120 Vac 57 Hz; 60 Hz -40°F to +175°F (-40°C to +79°C) C7061M1008/U NEMA 4 96 in. (2438 mm) Color-coded leadwires 1 in. NPT 120 Vac 58 Hz; 60 Hz -4°F to +175°F (-20°C to +79°C) C7061M1016/U NEMA 4 Brad Harrison type number 41310 connector 1 in. NPT 120 Vac 59 Hz; 60 Hz -4°F to +175°F (-20°C to +79°C) Dimensions for C7061A in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. Dimensions for C7061F in inches (millimeters) M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) 70-6910 805 Commercial/Industrial Combustion Controls Flame Detectors Dimensions for C7061M in inches (millimeters) M29114A 2-9/64 (55) 13/16 (21) 2-21/32 (68) 3-15/32 (88) 1-33/64 (39) PARALLEL PIPETHREAD 1-11/2 NPSM 33/64 (13) 2-9/64 (55) 1-35/64 (40) CONDUIT TUBE CONNECTION PORT 1/2 NPSM 806 70-6910 Flame Detectors C7076 Adjustable Sensitivity Ultraviolet Flame Detector Solid state dynamic self check flame detectors for use with BC7000, R4140 or FSP5075 with R7476 Amplifier and 7800 SERIES with R7886 Amplifier. • Use Honeywell Flame Safeguard primary safety controls requiring adjustable sensitivity ultraviolet flame detection. • Detect ultraviolet radiation from flames. • Include dual sensitivity adjustment. • C7076A meets NEMA 4 standards with viewing window rated to 20 psi. • C7076D has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Adjustable Sensitivity Application: Gas fired burners; Oil fired burners Electrical Connections: Terminal block Vibration: 0.5 G max Mounting: 1 in. NPT Power Consumption: 7.0 W Ambient Temperature Range: -40°F to +160°F (-40°C to +71°C) Approvals, CSA: Certified: Master Report LR1620 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. FM26980 Comments: Dynamic self-checking flame detector with adjustable sensitivity Used With: Flame Amplifiers: R7476, R7886 Replacement Parts: 190971F/U – 100 Vac Coil and Shutter Assembly for C7076A, D 190998A/U – Aspiration assembly for C7076A 191002R/U – 120 Vac Plug in Electronics less UV Sensing Tube for C7076D 191050/U – Quartz Viewing Window for C7076 191053/U – UV Sensing Tube for C7076 Dimensiions in inches (millimeters) C7076A C7076D M20749A 2-1/4 (57) 2-1/4 (57) 2-9/32 (58) 5-25/32 (147) 5-25/32 (147) 1-27/32 (47) 7-13/16 (198) 15/16 (24) 25/32 (20) 1-9/16 (40) 11-13/16 (300) 3/4 (19) 1-5/8 (19) 2-21/32 (68) 7-19/32 (194) 3/8 INCH NPT 1 (25) 29/32 (22) OPENING FOR 1/2-INCH CONDUIT 7-13/32 (188) 10-1/4 (261) 1-1/16 (27) 4 (102) 4 (102) 4-25/32 (122) 1 INCH NPT POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 1 1 6-23/32 (171) 1-31/32 (50) 3-15/16 (100) 5/16-18 UNC (3 PLCS) X 0.47 (12) DEEP Material Number NEMA Rating Electrical Ratings Frequency Approximate, Dimensions Weight Approvals, Underwriters Laboratories Inc. Approvals, Others C7076A1007/U NEMA 4 120 Vac 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep (102 mm high x 102 mm wide x 261 mm deep) 6.6 lb (3 kg) Listed: File No. MP268, Guide No. MCCZ C7076A1015/U NEMA 4 100 Vac 50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep (102 mm high x 102 mm wide x 261 mm deep) 6.6 lb (3 kg) Listed: File No. MP268, Guide No. MCCZ C7076A1031/U NEMA 4 220 Vac; 240 Vac 50 Hz; 60 Hz 4 in. high x 4 in. wide x 10 1/4 in. deep (102 mm high x 102 mm wide x 261 mm deep) 6.6 lb (3 kg) Listed: File No. MP268, Guide No. MCCZ C7076D1027/U NEMA 7 120 Vac 60 Hz 6 5/8 in. high x 6 3/16 in. wide x 11 3/4 in. deep (168 mm high x 158 mm wide x 300 mm deep) 17.6 lb (8 kg) Listed: File No. E34649, Guide No. ZTSZ Explosion Proof 70-6910 807 Commercial/Industrial Combustion Controls Flame Detectors C7927 Solid State Ultraviolet Flame Detector Dimensiions in inches (millimeters) 8 FT (2.44 M) 1 (25) C7927A1016 M24714 3-3/4 (95) 3-1/4 (82) The Solid State Ultraviolet Flame Detectors, sense ultraviolet radiation emitted by combustion flames. The flame detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil, or combination gas-oil burners. • Properly installed the flame detectors are pressure rated for 5 psi. • Flame detector is used with only the R7851B Flame Amplifier and the 7800 SERIES controls. • Has an integral collar threaded (internal 1/2-14 NPSM) for mounting on a one-half inch sight pipe. Type: Ultraviolet, Minipeeper Application: Gas, Oil, or combination burners-intermittent operation only (burner cycled at least once each 24 hours). NEMA Rating: NEMA 1 Electrical Connections: 2 NEC Class 1 leadwires Mounting: 1/2 in. NPT pipe mounting Approximate, Dimensions: 1 in. diameter x 3 3/4 in. long (25 mm diameter x 95 mm long) Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MP268 Approvals, CSA: Report 158158 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 3011020 Comments: Detects ultraviolet radiation in flames Material Number Lead Length Ambient Temperature Range Used With C7927A1016/U 96 in. (2438 mm) -40°F to +200°F (-40°C to +93°C) Flame Amplifiers: R7851B 808 70-6910 Flame Detectors C7961 Dynamic Self-checking Solid State Ultraviolet Flame Detector A self-checking flame detector using a solid state UV sensor to detect ultraviolet radiation in flames for supervision of gas, oil or combination gas-oil burners. • Designed for use with 7800 series controls with the R7851C flame amp. • Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the solid state UV sensor checking function. • Can be mounted horizontally, vertically or at any angle in between. • The detector requires faceplate alignment and has integral locating reference points to assure proper operation of the shutter mechanism. • Models available with threaded conduit fitting and color-coded leadwires allow rapid electrical installation. • C7961E1022 or E1030 5 pin Brad Harrison type (formally 41307N) mating connector not supplied nor available through Honeywell. • Incorporates UV sensor tube checking feature; used with R7851C1008 Dynamic Self-check Amplifiers. • Protective heat block built into mounting flange. • -40°F (-40°C) rated ultraviolet sensing cell is supplied. • C7961E meets NEMA 4 standards with viewing window rated to 20 psi. • C7961F has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi. Type: Ultraviolet, Self-Checking Application: Gas, Oil or other fuels Electrical Ratings: 120 Vac (-15% +10%) Frequency: 50 Hz; 60 Hz Ambient Temperature Range: -40°F to +175°F (-40°C to +80°C) Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MP268 Comments: Detects ultraviolet radiation generated by combustion of gas, oil, or other fuels Approvals, Swiss RE: Acceptable Used With: R7851C Dynamic Self-Check Amplifier Dimensiions in inches (millimeters) MOUNTING FLANGE 1/2–14 NPSM LEADWIRES FACEPLATE 3/4–14 NPT M10167D 3-3/4 (95) 7-7/32 (183) 5-1/8 (130) 3-7/16 (87) 5-1/4 (133) 1 1 2 2 C7061A1046, C7061A1053: INCH NPT C7061A1038 AND C7061A1046: TYPE CONNECTOR. M1963A FACEPLATE PIPE UNION 8 (203) DIA. 1/2-14 NPT LEADWIRES 9 (229) 2 (51) 5 (127) 1-11 1/2 NPT 2-1/16 1-1/2 (52) (38) 5/16-18 UNC-2B BY 7/16 (11) DEEP MOUNTING HOLES (2) 2 (51) 1 (25) 3 (76) Material Number NEMA Rating Lead Length Electrical Connections Mounting Approximate, Dimensions Weight Approvals, CSA Approvals, Factory Mutual Includes C7961E1006/U NEMA 4 96 in. (2438 mm) NEC Class 1 color-coded 3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961E1014/U NEMA 4 96 in. (2438 mm) NEC Class 1 color-coded 1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961E1022/U NEMA 4 5 pin Brad Harrison Type Connector 1 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961E1030/U NEMA 4 5 pin Brad Harrison Type Connector 3/4 in. NPT 3 3/4 in. diameter (5 1/4 in. diameter including mounting flange) x 7 7/32 in. long (95 mm diameter (133 mm diameter including mounting flange) x 183 mm long) 2.6 lb (1.2 kg) Certified: Pending Pending Quartz Viewing Window rated for 20 psi (138 kPa) C7961F1004/U Explosion Proof 96 in. (2438 mm) NEC Class 1 color-coded 1 in. NPT 8 in. diameter x 12 in. long (203 mm diameter x 305 mm long) 14.5 lb (6.6 kg) Approved: Report No. 14740.01 Quartz Viewing Window rated for 100 psi 70-6910 809 Commercial/Industrial Combustion Controls Flame Detectors C7915 Infrared Flame Detector The C7915 Combination mount Lead Sulfide cell senses infrared radiation from gas, oil, and coal or dual-fuel flames. • Used for combination or dual-fuel applications. • Detects pilot and main flame. • Mounts quickly and easily on a standard 3/4 in. sighting pipe. • Works where flame rod or rectifying photocell mounts are difficult to apply. Type: Infrared (Lead Sulfide) Application: Used for combination or dual-fuel applications Electrical Connections: Two no. 18 AWG wires Mounting: 3/4 in. NPT Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: Master Report LR95329-1 Approvals, Swiss RE: Acceptable Approvals, Factory Mutual: Approved: Report No. 24181.03 Comments: Infrared (Lead Sulfide) Flame Detector Replacement Parts: 32007255-001/U – Lead Sulfide Cell for C7915 50019469-001/U – Magnifying Lens Assembly for C7915A Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With C7915A1010/U 30 in. (762 mm) 1 1/4 in. diameter x 2 1/4 in. long (32 mm diameter x 58 mm long) -20°F to 125°F operating range (-18°C to 52°C operating range) With magnifying lens, 32007255-001 Cell Flame Amplifiers: R7852 C7915A1028/U 48 in. (1219 mm) 1 1/4 in. diameter x 2 1/4 in. long (32 mm diameter x 58 mm long) -20°F to 125°F operating range (-18°C to 52°C operating range) With magnifying lens, 32007255-001 Cell, Orifice, heat block, and reducer bushing Flame Amplifiers: R7852 C7915A1036/U 96 in. (2438 mm) 1 1/4 in. diameter x 2 1/4 in. long (32 mm diameter x 58 mm long) -20°F to 125°F operating range (-18°C to 52°C operating range) With magnifying lens, 32007255-001 Cell Flame Amplifiers: R7852 C7962 Visible Light Flame Detector Dimensiions in inches (millimeters) 4 FOOT (1.2 METER) LEADWIRES (2) M20912 3-1/4 (82) 3-3/4 (95) 1 (25) C7962B The C7962B Visible Light Flame Detector detects the visible light emitted by fuel oil combustion flames. The C7962B Detector is used with Honeywell Flame Safeguard controls to provide fuel oil flame supervision in commercial and industrial burners. • Used with 7800 SERIES Flame Safeguard controls. • Used with R7851B Flame Amplifier. • Has an integral collar threaded (internal 1/2-14 NPSM) for mounting on 1/2 inch sight pipe. Type: Visible Light Flame Detector Application: Commercial, industrial oil burners NEMA Ratings: NEMA 1 Electrical Connections: 2 NEC Class 1 leadwires Vibration: 0.5 G max Mounting: 1/2 in NPT pipe mounting Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MP268 Approvals, CSA: Report 158158 Approvals, Swiss RE: Acceptable Accessories: 32007439-001/U – Mounting Bracket and screws for C7962B (3/8 in. NPT to 1/2 in. NPT) Material Number Lead Length Approximate, Dimensions Ambient Temperature Range Includes Used With C7962B1002/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm diameter x 95 mm long) -40°F to +160°F (-40°C to +71°C) Flame Amplifiers: R7851B C7962B1010/U 96 in. (2438 mm) 1 in. diameter x 3 3/4 in. long (25 mm diameter x 95 mm long) -40°F to +160°F (-40°C to +71°C) 32007439-001 Mounting Bracket and screws Flame Amplifiers: R7851B 810 70-6910 Flame Detectors Optical Flame Detector Accessories or Parts Material Number Description Used With 105172C/U Pressure Seal-off Adapter (3/4 NPT) w/UV Quartz window for C7012, C7024, C7027, C7061 C7012, C7024, C7027, C7061; C7024; C7012; C7061 110634A/U Magnifying Lens Assembly for C7015A C7015 113228/U UV Sensing Tube (-20°F to 175°F) for C7012; C7024 C7012; C7024 114372/U Bulk Pack -20 PSI window for C7012E, F; C7024; C7061 C7024; C7012; C7061 114638/U Rubber Washer (Red) for C7012A, E; C7024A; C7061A; C7961A C7012; C7061; C7024 120739/U Flange Gasket for C7012, C7024, C7061 C7024; C7012; C7061 120930/1662/F Cover for C7012A,G, C7024E, C7061A, C7961E C7012A,G, C7024E, C7061A, C7961E; C7012 120934-520/U Mounting Flange (3/4") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A, C7961E 122748/U 50 PSI Quartz Window for C7012, C7061 C7012; C7061; C7024 124198/U Mounting Flange (1") for C7012A, E; C7024A; C7061A; C7961E C7012A,G, C7024E, C7061A, C7961E 129464M/U UV Power Tube (0°F to 250°F) for C7035 C7035 129464N/U UV Power Tube (-40°F to 250°F) for C7035, C7061 C7061; C7035 129811B/U Socket Assembly w/NPT threads C7035 190971B/U 120 Vac Coil and Shutter Assembly for C7012E, F, C7061A, F C7012E, F; C7061A, F 190971D/F 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E 190971D/U 110 Vac 50 Hz Coil and Shutter Assembly for C7012E1187, 1195 C7012E 190971F/U 100 Vac Coil and Shutter Assembly for C7076A, D C7076A, D 190971G/U 24 Vdc Coil and Shutter Assembly for C7024E, F; C7961 C7024;C7961 190998A/U Aspiration assembly for C7076A C7076A 190999/U Grommet for C7076 Sensors C7076 191002D/U 220/240 Vac Plug in Electronics less UV Sensing Tube for C7076A C7076A 191002R/U 120 Vac Plug in Electronics less UV Sensing Tube for C7076D C7076D 191050/U Quartz Viewing Window for C7076 C7076 191053/U UV Sensing Tube for C7076 C7076 191054/U Housing Gasket for C7076 C7076 191203/0767/U Hinge for C7076A C7076 191284/U Aluminum Shield for C7035 C7035 191702/U Electronics less UV sensing tube for C7012F (120 Vac) C7012F 32004080-001/U 120 Vac Electronics less UV Sensing Tube and Shutter for C7012C C7012C 32004080-002/U 24 Vdc Plug in Electronics less UV Sensing Tube for C7024F C7024F 32007255-001/U Lead Sulfide Cell for C7915 C7915 32007439-001/U Mounting Bracket and screws for C7962B (3/8 in. NPT to 1/2 in. NPT) C7962B 390427B/U Envelope with Reducer bushing (1/2" to 3/8" NPT) C7027; C7015 50019469-001/U Magnifying Lens Assembly for C7915A C7915; C7015 70-6910 811 Commercial/Industrial Combustion Controls Pilot Burners Q179A, B Flame Rectifier Gas Pilots Q179A, B Gas Pilot Burner Assemblies use the flame rectification principle to prove the flame. Q179A, B are used in conjunction with a suitable electronic flame safeguard control on industrial or commercial gas and gas pilot ignited oil burners. • Q179A is a gas pilot assembly (with a flame electrode rod) and ignition electrode, making it suitable for applications requiring an interrupted or intermittent electrically ignited gas pilot burner. • Q179B has only the flame electrode and is suitable for use in continuous pilot applications. • Primary aerated type burner is equipped with stainless steel fins that provide the proper flame rod area to ground area ratio for maximum flame signal and flame stabilization. • Stainless steel electrode(s) are mounted in ceramic insulators, which permit electrode adjustment. • Rajah connectors facilitate disconnecting (A1126 has terminal screws). • Bracket permits side or end mounting. Type of Gas: Natural gas; Gas consumption – 2.0 cfh (0.06 m3/hr) Aeration: Primary Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm compression coupling Mounting: side or end mount Approximate, Dimensions: 4 5/8 in. high x 1 11/16 in. wide x 3 in. deep (118 mm high x 43 mm wide x 76 mm deep) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2 Approvals, Factory Mutual: Approved: Report No. 22961 Material Number Application Orifice Wiring Terminal Type Tip Style Includes Used With Q179A1001/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah I Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1035/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree right hand Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1050/U For Intermittent or Interrupted Ignition 0.028 in. dia. (0.711 mm dia.) Rajah T Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1076/U For Intermittent or Interrupted Ignition 0.028 in. dia. (0.711 mm dia.) Rajah 45 degree Y Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1092/U For Intermittent or Interrupted Ignition 0.028 in. dia. (0.711 mm dia.) Rajah 45 degree T Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1118/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left hand Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Q179A1126/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Screw Terminal I Flame electrode and ignition electrode with screw terminal connections Q624 or other suitable ignition transformer. Q179A1183/U For Intermittent or Interrupted Ignition 0.025 in. dia. (0.635 mm dia.) Rajah I Ignition Electrode Only Q624 or other suitable ignition transformer. Q179B1042/U For Continuous (Standing) pilot 0.025 in. dia. (0.635 mm dia.) Rajah T Flame electrode Q179B1109/U For Continuous (Standing) pilot 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree left hand Flame electrode Q179B1117/U For Continuous (Standing) pilot 0.025 in. dia. (0.635 mm dia.) Rajah 45 degree I Flame electrode 812 70-6910 Pilot Burners Q179C, D Miniature Rectifier Pilots Q179C, D Gas Pilot Burner Assemblies use the flame rectification principle to prove the flame. Q179C, D are used in conjunction with a suitable electronic flame safeguard control on industrial or commercial gas and gas pilot ignited oil burners. • Q179C is a gas pilot assembly (with a flame electrode rod) and ignition electrode, making it suitable for applications requiring an interrupted or intermittent electrically ignited gas pilot burner. • Q179D has only the flame electrode and is suitable for use in continuous pilot applications. • Primary aerated type burner is equipped with stainless steel fins that provide the proper flame rod area to ground area ratio for maximum flame signal and flame stabilization. • Stainless steel electrode(s) are mounted in ceramic insulators, which permit electrode adjustment. • Rajah connectors facilitate disconnecting. Aeration: Primary Compression Fitting Size: 1/4 in. compression coupling, 6.4 mm compression coupling Wiring Terminal Type: Rajah Approvals, Underwriters Laboratories Inc.: Component Recognized: File No. MH9928, Guide No. MCUR2 Approvals, CSA: Certified: Master Report LR95329-1 Material Number Application Mounting Tip Style Orifice Approximate, Dimensions Includes Used With Type of Gas Q179C1009/U For Intermittent or Interrupted Ignition Dual Wing- Rear D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1025/U For Intermittent or Interrupted Ignition Single Wing- Rear L 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1033/U For Intermittent or Interrupted Ignition Dual Wing- Left Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1041/U For Intermittent or Interrupted Ignition Dual Wing- Right Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1058/U For Intermittent or Interrupted Ignition Single Wing- Left Side L 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1066/U For Intermittent or Interrupted Ignition Single Wing- Right Side K 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. Natural Q179C1090/U For Intermittent or Interrupted Ignition Dual Wing- Rear D 0.016 in. dia. (0.40 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and ignition electrode Q624 or other suitable ignition transformer. LP Q179D1008/U For Continuous (Standing) pilot Dual Wing- Rear D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 2 7/16 in. wide x 1 in. deep (79 mm high x 62 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural Q179D1016/U For Continuous (Standing) pilot Dual Wing- Left Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural Q179D1024/U For Continuous (Standing) pilot Dual Wing- Right Side D 0.026 in. dia. (0.66 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural Q179D1057/U For Continuous (Standing) pilot Single Wing- Left Side L 0.024 in. dia. (0.60 mm dia.) 3 1/8 in. high x 3 1/32 in. wide x 1 in. deep (79 mm high x 77 mm wide x 25 mm deep) Flame electrode and thermocouple adapter Q340 Thermocouple or Q313A Thermopile Generator. Natural 70-6910 813 Commercial/Industrial Combustion Controls Pilot Burners C7005 Flame Rectifier Pilots Gas Pilot Burner Assemblies include a flame rod to prove the pilot flame. The assemblies are used with a suitable flame safeguard control on industrial or commercial gas burners or oil burners with gas pilots. • Used with Honeywell controls using the flame rectification principle. • C7005A is for continuous pilot applications. • It includes an insulated flame rod, properly positioned relative to the flame retention type nozzle. C7005B is similar to C7005A, but includes an ignition electrode suitable for automatic, electric-spark ignition, gas pilot applications. • Individually mounted flame rod and ignition electrode in ceramic insulators allow the head assembly to fit inside a 3-inch pipe. • Stainless steel fins on the flame retention type pilot head provide the correct ratio of flame rod area to ground area for maximum flame signal, and are beneficial in stabilizing the pilot flame. • Pilot flame retention nozzle and mixing tube are threaded internally, 1/2-14 NPT and 3/8-18 NPT, respectively, and can be assembled with standard pipe fittings. • Pilot can be installed in vertical, horizontal, or inclined position. • Rajah connectors facilitate electrical connections. Connection Type: 1/2 in. NPT male thread Gas Fitting Wiring Terminal Type: Rajah Approximate, Dimensions: 3 in. diameter x 3 1/2 in. deep (76 mm diameter x 343 mm deep) Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2 Approvals, Factory Mutual: Approved: Report No. 24181.04 Approvals, Swiss RE: Acceptable Material Number Application Orifice Includes Used With Type of Gas C7005A1037/U For Continuous (Standing) pilot 0.052 in. dia. Natural C7005B1035/U For automatic electrically ignited pilot 0.052 in. dia. Ignition electrode Q624 or other suitable ignition transformer. Natural C7005B1050/U For automatic electrically ignited pilot 0.028 in. dia. (0.711 mm dia.) Ignition electrode Q624 or other suitable ignition transformer. LP Commercial Pilot Burners Parts or Accessories Material Number Description Used With 100204B/U This Natural Gas Venturi Mixing Tube is used for C7005A and B C7005A, C7005B 101738/U This Insulator for Flame rod or Igniter is used with C7005A and B C7005A, C7005B 101738A/U This Ignition Assembly, including; electrode, bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B 101738B/U This Flame Rod Assembly, including; Kanthal Electrode, Bracket and Rajah Connector, is used for C7005A and B C7005A, C7005B 101739/U This 4 in. Kanthal Ignition Electrode is used for C7005A and B C7005A, C7005B 101741/0020/U This 7/8 in. long Rajah Connector, with plug end, is used for C7005A and B C7005A, C7005B 101742/0021/U This Electrode Mounting Clip is used for C7005A and B C7005A, C7005B 101743/U This Mounting Bracket is used for C7005A and B C7005A, C7005B 103534/U This 8 in. Kanthal flame electrode is used with C7005A and C7005B C7005A, C7005B 104312/U This Rajah Connector for Flame Electrode is used with Q179A and B Q179A, Q179B 131065/U 131065 Adapts Q340 Thermal Couple to Q179B with 102462. Sold in custom packs Q179A, Q179B 133451A/U This T Port or LH 90 degree Flame Rod and Insulator, is used for Q179A and B Q179A, Q179B 37356/520/U This Rajah connector for ignition electrodes is used with Q179A, Q179B, Q179C, or Q179D Q179A, Q179B, Q179C, Q179D 388146KD/U This 0.016 in. diameter, LP Gas Spud Orifice, is used for Q179C and D. Sold in bulk packs Q179C, Q179D 395390-13/U This LP gas, 0.013 in. diameter Orifice, is used for Q179A and B Q179A, Q179B 395390-28/U This Natural gas, 0.028 in. diameter Orifice, is used for Q179A and B Q179A, Q179B R1061012/U This Ignition cable or Flame Rod Cable is rated at 350°F, 20,000 volts R.M.S. and used with C7005B, Q179A and Q179C C7005B, Q179A, Q179C R1298020/U This Cable Flame Rod Lead, is rated at 400°F, 600 volts R.M.S., and used with Q179 Q179 814 70-6910 Ignition Transformers Q624 Solid State Ignition Transformer Used to ignite pilots on commercial or industrial gas burners. • Ignite gas pilots with spark gaps up to 1/4 in. (6.5 mm). • Reliable light off with 15,000 peak voltage. • Prevent detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector. • For use only in interrupted ignition applications. • Mount in same space used by conventional ignition transformer. • Light weight, 3 lbs. (1.4 kg) versus 8-1/2 lbs. (3.9 kg) for standard transformers. Temperature Range: -40°F to +125°F Approximate, Dimensions: 6 3/4 in. high x 4 1/4 in. wide x 3 in. deep (171.5 mm high x 108 mm wide x 76 mm deep) Weight lb. (kg): 3 lb (1.4 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized Approvals, CSA: Certified: File No. LR95329 Operating Humidity Range (% RH): 95% RH Accessories: 32004766-001/U – 24 inch Ignition Cable for Q624 and Q652 32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652 32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 32004766-004/U – 60 inch Ignition Cable with straight boots 32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot 32004766-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-001/U – 24 inch Ignition Cable for Q624 and Q652 50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652 50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 50060793-004/U – 60 inch Ignition Cable with straight boots 50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot 50060793-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-007/U – 36 inch ignition cable w/90 degree boot on one end only 50060793-008/U – Ignition Cable w/90 degree boot on one end only 50060793-009/U – Ignition Cable w/90 degree boot on one end only 50060793-010/U – Ignition Cable w/90 degree boot on one end only 50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 50060793-012/U – 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Dimensions in inches (millimeters) TERMINAL BOARD MOUNTING PLATE HIGH VOLTAGE ELECTRODE COVER SCREW KNOCKOUT FOR 1/2 INCH CONDUIT 1-1/4 (32) 13/16 (20.5) 5-1/4 (133.5) 19/64 (7) 4-1/4 (108) 1-1/4 (32) 3 (76) M20858 5-15/16 (151) 6-3/4 (171.5) Material Number Application Voltage Frequency Q624A1014/U Gas Ignition Transformer 120 Vac 50 Hz; 60 Hz 70-6910 815 Commercial/Industrial Combustion Controls Ignition Transformers Q652 Solid State Spark Generator Used to ignite gas burners in commercial and industrial applications. • Lightweight, 1 lb. (0.4 kg). • Include single high voltage electrode for gas applications. • For use with gas pilots with electrode spacings between 0.029 and 0.125 in. • Secondary Peak Voltage: 14Kv rms at 21Khz. • Mount in same space used by conventional ignition transformer. • For use only in interrupted ignition applications. • Prevent detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector. Temperature Range: 14°F to 113°F Approximate, Dimensions: 4 15/32 in. high x 2 15/16 in. wide x 2 9/32 in. deep (101.6 mm high x 77.5 mm wide x 58.4 mm deep) Weight lb. (kg): 1 lb (0.45 kg) Approvals, Underwriters Laboratories Inc.: Component Recognized File MH14381 Approvals, CSA: LA66894 Operating Humidity Range (% RH): 90% RH Accessories: 32004766-001/U – 24 inch Ignition Cable for Q624 and Q652 32004766-002/U – 120 inch Ignition Cable used with Q624 and Q652 32004766-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 32004766-004/U – 60 inch Ignition Cable with straight boots 32004766-005/U – 8 inch Ignition Cable w/90 degree and straight boot 32004766-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-001/U – 24 inch Ignition Cable for Q624 and Q652 50060793-002/U – 120 inch Ignition Cable used with Q624 and Q652 50060793-003/U – Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) 50060793-004/U – 60 inch Ignition Cable with straight boots 50060793-005/U – 8 inch Ignition Cable w/90 degree and straight boot 50060793-006/U – 36 inch Ignition Cable w/90 degree and straight boot 50060793-007/U – 36 inch ignition cable w/90 degree boot on one end only 50060793-008/U – Ignition Cable w/90 degree boot on one end only 50060793-009/U – Ignition Cable w/90 degree boot on one end only 50060793-010/U – Ignition Cable w/90 degree boot on one end only 50060793-011/U – 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 50060793-012/U – 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Dimensions in inches (millimeters) M20870B 2-25/32 (71) 2-7/8 (73) 2-9/32 (59) 19 IN. (483 MM) LEAD WIRES HIGH VOLTAGE ELECTRODE 3-17/64 (83) 3-21/32 (95) 4-5/32 (106) 2-15/16 (78) Material Number Application Voltage Frequency Q652B1006/U Gas Ignition Transformer 120 Vac 60 Hz Q652B1014/U Solid State Ignitor Spark Generator-Gas Applications; 220V 60 Hz 220 Vac 60 Hz 816 70-6910 Ignition Transformers Ignition Transformer Accessories or Parts Material Number Description Used With 134666/510/U High voltage terminal insulator for Q652 and Q624 Q652; Q624 32004766-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624 32004766-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624 32004766-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624 32004766-004/U 60 inch Ignition Cable with straight boots Q652; Q624 32004766-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624 32004766-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624 32004766-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624 32004766-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624 32004766-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624 32004766-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624 32004766-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624 32004766-012/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624 4074BTN/U Bag assembly consisting of washer (103218), cap terminal (135793) and ferrule (37356) for Q624 Q624A 50060793-001/U 24 inch Ignition Cable for Q624 and Q652 Q652; Q624 50060793-002/U 120 inch Ignition Cable used with Q624 and Q652 Q652; Q624 50060793-003/U Ignition Cable for Q624 and Q652 (order by foot – enter the number of feet in the Quantity box) Q652; Q624 50060793-004/U 60 inch Ignition Cable with straight boots Q652; Q624 50060793-005/U 8 inch Ignition Cable w/90 degree and straight boot Q652; Q624 50060793-006/U 36 inch Ignition Cable w/90 degree and straight boot Q652; Q624 50060793-007/U 36 inch ignition cable w/90 degree boot on one end only Q652; Q624 50060793-008/U Ignition Cable w/90 degree boot on one end only Q652; Q624 50060793-009/U Ignition Cable w/90 degree boot on one end only Q652; Q624 50060793-010/U Ignition Cable w/90 degree boot on one end only Q652; Q624 50060793-011/U 19 inch Ignition Cable w/90 degree and ring end used with Q624 and Q652 Q652; Q624 50060793-012/U 36 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624 50060793-013/U 48 inch Ignition Cable with 90 degree boot and 1/4 in. spad terminal used with Q624 and Q652 Q652; Q624 70-6910 817 Commercial/Industrial Combustion Controls Firing Rate Motors and Linkages M9484D, E, F; M9494D, F Modutrol® IV Motors Reversing, proportional motors used to drive burner firing rate valves, dampers or auxiliary equipment. Replaces M941A, C, D motors. • Designed for flame safeguard applications in commercial/industrial oil or gas burner system. • Vibration resistant electronic drive circuit. • Regulated by three-wire proportional controller. • Stroke is field-adjustable to 90 or 160 degrees. Frequency: 50 Hz; 60 Hz Stroke: Adjustable; 90 to 160 degrees, Symmetrical Power Consumption: 15 W Input Signal: 135 ohm Shaft Dimensions: double-ended, 3/8 in. square (double-ended, 9.5 mm square) Deadweight Load on Shaft: Either End – 200 lb (300 lb combined power and auxiliary shafts); 90.8 kg (136 kg combined power and auxiliary shafts) Approximate, Dimensions: 6.45 in high x 5.5 in wide x 7.3 in deep (164 mm high x 140 mm wide x 185 mm deep) Ambient Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. E4436, Guide No. XAPX for USA and Canada Supply Voltage: 24 Vac Accessories: Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly Valve. Includes 10 3/4 inch Linkage Rod. Material Number Torque Rating (lb-in.) Torque Rating (Nm) Additional Torque Ratings (lb-in.) Additional Torque Ratings (Nm) Internal Auxiliary Switch Auxiliary Switch Setting Auxiliary Switch Ratings Switch Ratings Timing Factory Stroke Setting M9484D1010/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 160 degrees M9484E1009/U 75 lb-in. 8.5 Nm Breakaway – 150 lb-in. Breakaway – 17.0 Nm 1 11 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 15 seconds, 160 degree stroke – 30 seconds 90 degrees M9484E1017/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 1 1 degree 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484E1033/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 1 7 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484F1007/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 7 and 80 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484F1023/U 75 lb-in. 8.5 Nm Breakaway – 150 lb-in. Breakaway – 17.0 Nm 2 At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 15 seconds, 160 degree stroke – 30 seconds 90 degrees 818 70-6910 Firing Rate Motors and Linkages Material Number Torque Rating (lb-in.) Torque Rating (Nm) Additional Torque Ratings (lb-in.) Additional Torque Ratings (Nm) Internal Auxiliary Switch Auxiliary Switch Setting Auxiliary Switch Ratings Switch Ratings Timing Factory Stroke Setting M9484F1031/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 7 and 80 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 90 degrees M9484F1049/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 35 and 120 degrees 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 60 seconds 160 degrees M9484F1057/U 150 lb-in. 17 Nm Breakaway – 300 lb-in. Breakaway – 34.0 Nm 2 At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 30 seconds, 160 degree stroke – 53 seconds M9494D1000/U 300 lb-in. 34 Nm Breakaway – 600 lb-in. Breakaway – 68.0 Nm At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 60 seconds, 160 degree stroke – 120 seconds 90 degrees M9494F1003/U 300 lb-in. 34 Nm Breakaway – 600 lb-in. Breakaway – 68.0 Nm 2 At 120 Vac – 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite contact; At 240 Vac – 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite contact 90 degree stroke – 60 seconds, 160 degree stroke – 107 seconds 90 degrees Q100 Butterfly Valve Linkages Connects V51E valve to M9484 and M9494 Modutrol IV Motors with adapter plate. • Fits all sizes of V51E Valves. Mounts easily. Material Number Linkage Type Used with Actuator Includes Used With Q100B1006/U Butterfly Gas Valve Modutrol Motor 10 3/4 in. Linkage Rod all sizes V51E Gas Valve 70-6910 819 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V48A; V88A Diaphragm Gas Valves Dimensions in inches (millimeters) 1 2 1 2 BLEED TAPPING: 1/8-27 NPT. PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT FOR 2 THROUGH 3 IN. SIZES. M8487A E C A B D F APPROXIMATE DIMENSIONS VALVE SIZE (IN.) A B C D E F IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4-11/16 5-1/16 5-9/16 5-9/16 6-15/16 6-15/16 6-15/16 119.1 128.6 141.3 141.3 176.2 176.2 176.2 3/4 1 1-1/4 1-1/4 2-1/4 2-1/4 2-1/4 19.1 25.4 31.8 31.8 57.2 57.2 57.2 4-5/8 5 5-7/8 5-7/8 9-1/2 9-1/2 9-1/2 117.5 127.0 149.2 149.2 241.3 241.3 241.3 3-1/2 3-11/16 5-5/16 5-5/16 8-3/8 8-3/8 8-3/8 88.9 93.7 134.9 134.9 212.7 212.7 212.7 1-5/8 2-1/16 2-3/8 2-3/8 3-9/16 3-9/16 3-9/16 41.3 52.4 60.3 60.3 90.5 90.5 90.5 3-13/16 4-5/16 5-5/16 5-5/16 5-5/16 9-5/16 9-5/16 96.8 109.5 134.9 134.9 236.5 236.5 236.5 1-13/16 (46) 3-11/16 (94) Solenoid-operated diaphragm valves provide slow opening and fast closing suitable for controlling natural, LP or manufactured gases. They are normally used on atmospheric boilers, commercial water heaters, and rooftop heaters. • V48 for line voltage service; V88 for 24 Vac service. • Close firmly with diaphragm that is both weight and spring loaded. • Two second maximum closing time. • Valve closes on power failure; recommended for final shutoff service. • Set opening time with various sized bleed orifices or adjustable bleed valve. • Use with LP, natural or manufactured gases. • Made with cast aluminum in straight-through valve pattern. • Valve position indicator available for 1-1/4 in. V48A2227. Type of Fuel: Natural; LP; Manufactured Bleed Tapping: 1/8-27 NPT Body Pattern: Straight-through Valve Opening Time: 5 sec max Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Power Consumption: 9 W; 15 VA max Electrical Connections: 6 in. Leadwires Operating Temperature Range: 32°F to 125°F (0°C to 52°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5) Material Number Pipe Size (inch) Pipe Size (DN) Pilot Tapping Voltage Approximate, Dimensions Pressure Rating (psi) Pressure Rating (kPa) Current Ratings Comments Includes V48A2151/U 3/4 in. DN20 1/8-27 NPT 120 Vac 5 7/16 in. high x 3 13/16 in. wide x 4 5/8 in. deep (138 mm high x 97 mm wide x 118 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2169/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2177/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2185/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2227/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Includes position indicator Ground terminal V48A2243/U 2 in. DN50 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2250/U 2 1/2 in. DN65 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal 820 70-6910 Diaphragm Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Pilot Tapping Voltage Approximate, Dimensions Pressure Rating (psi) Pressure Rating (kPa) Current Ratings Comments Includes V48A2268/U 3 in. DN80 1/4-18 NPT 120 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2276/U 1 1/2 in. DN40 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2334/U 1 in. DN25 1/8-27 NPT 120 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V48A2342/U 1 1/4 in. DN32 1/8-27 NPT 120 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.13 max amps at rated Vac/Hz Ground terminal V88A1618/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1626/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1634/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1659/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide x 4 5/8 in. deep (138 mm high x 97 mm wide x 118 mm deep) 1/2 psi 3.4 kPa 0.62 max amps at rated Vac/Hz V88A1667/U 3/4 in. DN20 1/8-27 NPT 24 Vac 5 7/16 in. high x 3 13/16 in. wide x 4 5/8 in. deep (138 mm high x 97 mm wide x 118 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1675/U 1 in. DN25 1/8-27 NPT 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1683/U 1 1/4 in. DN32 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1691/U 1 1/2 in. DN40 1/8-27 NPT 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1709/U 2 in. DN50 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz V88A1717/U 2 1/2 in. DN65 1/4-18 NPT 24 Vac 9 3/16 in. high x 9 5/16 in. wide x 9 1/2 in. deep (233 mm high x 237 mm wide x 241 mm deep) 1 psi 6.9 kPa 0.62 max amps at rated Vac/Hz 70-6910 821 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V48J; V88J High Temperature Diaphragm Gas Valves Dimensions in inches (millimeters) 1 2 1 2 BLEED TAPPING: 1/8-27 NPT. PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES, 1/4-18 NPT FOR 2 THROUGH 3 IN. SIZES. M8487A E C A B D F APPROXIMATE DIMENSIONS VALVE SIZE (IN.) A B C D E F IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4-11/16 5-1/16 5-9/16 5-9/16 6-15/16 6-15/16 6-15/16 119.1 128.6 141.3 141.3 176.2 176.2 176.2 3/4 1 1-1/4 1-1/4 2-1/4 2-1/4 2-1/4 19.1 25.4 31.8 31.8 57.2 57.2 57.2 4-5/8 5 5-7/8 5-7/8 9-1/2 9-1/2 9-1/2 117.5 127.0 149.2 149.2 241.3 241.3 241.3 3-1/2 3-11/16 5-5/16 5-5/16 8-3/8 8-3/8 8-3/8 88.9 93.7 134.9 134.9 212.7 212.7 212.7 1-5/8 2-1/16 2-3/8 2-3/8 3-9/16 3-9/16 3-9/16 41.3 52.4 60.3 60.3 90.5 90.5 90.5 3-13/16 4-5/16 5-5/16 5-5/16 5-5/16 9-5/16 9-5/16 96.8 109.5 134.9 134.9 236.5 236.5 236.5 1-13/16 (46) 3-11/16 (94) Solenoid-operated diaphragm valves provide slow opening and fast closing suitable for controlling natural, LP or manufactured gases. They are normally used on atmospheric boilers, commercial water heaters, and rooftop heaters. • Rated for 150°F (66°C) maximum temperature applications. • V48 for line voltage service; V88 for 24 Vac service. • Close firmly with diaphragm that is both weight and spring loaded. • Two second maximum closing time. • Valve closes on power failure; recommended for final shutoff service. • Set opening time with various sized bleed orifices or adjustable bleed valve. • Use with LP, natural or manufactured gases. • Made with cast aluminum in straight-through valve pattern. Type of Fuel: Natural; LP; Manufactured Bleed Tapping: 1/8-27 NPT Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through Valve Opening Time: 5 sec max Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Electrical Connections: 6 in. Leadwires Operating Temperature Range: 32°F to 150°F (0°C to 66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ Approvals, CSA: Certificate No. 158158-2500005576 (Z21.21-CSA 6.5) Pressure Ratings (psi): 1 psi Pressure Ratings (kPa): 6.9 kPa Current Ratings: 0.62 max amps at rated Vac/Hz Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption V88J1006/U 1 in. DN25 24 Vac 6 1/16 in. high x 4 5/16 in. wide x 5 in. deep (154 mm high x 127 mm wide x 109 mm deep) 9 W; 15 VA max V88J1022/U 1 1/4 in. DN32 24 Vac 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep (173 mm high x 135 mm wide x 149 mm deep) 9 W; 15 VA max 822 70-6910 Diaphragm Gas Valves V4943/V8943A On/Off Diaphragm Gas Valves V4943A/V8943A are on/off diaphragm gas valve used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters. • Designed for replacement for V4843A/V8843A Gas Valves. • Suitable for use on atmospheric boilers, commercial water heaters, and rooftop heaters. • V8943A/V4943A models are solenoid-operated diaphragm valves for on/off flow control of natural or LP gas. • Valve body of die-cast aluminum with a straight-through pattern. • V4943 are used with line voltage, on/off controllers; V8943A are used with 24 Vac thermostats or controllers. • Valve closes on power failure; recommended for final shutoff service. Type of Fuel: Natural; LP Bleed Tapping: Internal Bleed Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through, non-offset Opening Characteristics: Rapid Opening On-Off Valve Opening Time: 6 sec max Valve Closing Time: 3 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Electrical Connections: 1/4 in. (6 mm) spade terminals (quick connects). 30 in. (762 mm) leadwires and cover for electrical conduit connection provided. Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ (60 Hz only) Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3371-03, 83 (Z21.21, Z21.78) Pressure Ratings (psi): 1/2 psi Pressure Ratings (kPa): 3.4 kPa Comments: (2) 30" leadwires Current Ratings: 0.055 max amps at rated Vac/Hz Dimensions in inches (millimeters) 6-9/16 (167) FOR 1, 1-1/4 OR 7-3/8 (187) FOR 1-1/2, 2 SIDE VIEW 6 (152) 6 (152) TOP VIEW M23232 VENT CONNECTIONS (V4944/V8944 HAVE TWO) Material Number Pipe Size (inch) Pipe Size (DN) Voltage Approximate, Dimensions Power Consumption V4943A1011/U 1 in. DN25 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 VA max V4943A1029/U 1 1/4 in. DN32 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 VA max V4943A1037/U 1 1/2 in. DN40 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 VA max V4943A1045/U 2 in. DN50 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 VA max V8943A1012/U 1 in. DN25 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 8 VA max V8943A1020/U 1 1/4 in. DN32 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 8 VA max V8943A1038/U 1 1/2 in. DN40 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 8 VA max V8943A1046/U 2 in. DN50 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 8 VA max 70-6910 823 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V4943/V8943B, C, N Single Stage Pressure Regulating Valves V4943B, N/8943B, C, N are Single-stage Pressure Regulating Valves. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters. • Designed for replacement for V4843/V8843 Gas Valves. • Suitable for use on atmospheric boilers, commercial water heaters, and rooftop heaters. • V4943/V8943B, C, N models are solenoid-operated diaphragm valves that combine the functions of safety shutoff and pressure regulation in a single unit. • V4943/V8943B, N are for use with natural gas. • V4943/V8943C are for use with LP gas. • Valve body of die-cast aluminum with a straight-through pattern. • V4943 are used with line voltage, on/off controllers; V8943 are used with 24 Vac thermostats or controllers. • Valve closes on power failure; recommended for final shutoff service. Bleed Tapping: 5/16-24 UNF Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through, non-offset Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Frequency: 60 Hz Electrical Connections: 1/4 in. (6 mm) spade terminals (quick connects). 30 in. (762 mm) leadwires and cover for electrical conduit connection provided. Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ (60 Hz only) Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01, 81 (Z21.21, Z21.78) Pressure Ratings (psi): 1/2 psi Pressure Ratings (kPa): 3.4 kPa Comments: (2) 30" leadwires Dimensions in inches (millimeter) 6-9/16 (167) FOR 1, 1-1/4 OR 7-3/8 (187) FOR 1-1/2, 2 SIDE VIEW 6 (152) 6 (152) TOP VIEW M23232 VENT CONNECTIONS (V4944/V8944 HAVE TWO) Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Voltage Approximate, Dimensions Valve Opening Time Current Ratings Pressure Regulator Setpoint (in. wc) Power Consumption V4943B1019/U Natural 1 in. DN25 Slow Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max; 6.6 VA V4943B1027/U Natural 1 1/4 in. DN32 Slow Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943B1035/U Natural 1 1/2 in. DN40 Slow Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943B1043/U Natural 2 in. DN50 Slow Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943N1012/U Natural 1 in. DN25 Rapid Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943N1020/U Natural 1 1/4 in. DN32 Rapid Opening 1-stage 120 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max 824 70-6910 Diaphragm Gas Valves Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Voltage Approximate, Dimensions Valve Opening Time Current Ratings Pressure Regulator Setpoint (in. wc) Power Consumption V4943N1038/U Natural 1 1/2 in. DN40 Rapid Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V4943N1046/U Natural 2 in. DN50 Rapid Opening 1-stage 120 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.055 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 6.6 VA max V8943B1010/U Natural 1 in. DN25 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943B1028/U Natural 1 1/4 in. DN32 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943B1036/U Natural 1 1/2 in. DN40 Slow Opening 1-stage 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943B1044/U Natural 2 in. DN50 Slow Opening 1-stage 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943C1018/U LP 1 in. DN25 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, High Fire – 10.0 in. wc 9 VA max V8943C1026/U LP 1 1/4 in. DN32 Slow Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 3 to 25 sec 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, High Fire – 10.0 in. wc 9 VA max V8943N1013/U Natural 1 in. DN25 Rapid Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943N1021/U Natural 1 1/4 in. DN32 Rapid Opening 1-stage 24 Vac 6 9/16 in. high x 6 in. wide x 6 in. deep (167 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max V8943N1039/U Natural 1 1/2 in. DN40 Rapid Opening 1-stage 24 Vac 7 3/8 in. high x 6 in. wide x 6 in. deep (187 mm high x 152 mm wide x 152 mm deep) 6 sec max 0.363 max amps at rated Vac/Hz Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, High Fire – 3.5 in. wc 9 VA max 70-6910 825 Commercial/Industrial Combustion Controls Diaphragm Gas Valves V4944/V8944B, C, L, N Two Stage Pressure Regulating Gas Valves V4944B, L, N/8944B, C, L, N are Two-stage Pressure Regulating Gas Valves. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters. • Designed for replacement for V4844/V8844 Gas Valves. • Suitable for use on atmospheric boilers, commercial water heaters, and rooftop heaters. • V4944/V8944B, C, L, N models are solenoid-operated diaphragm valves that combine the functions of safety shutoff and pressure regulation in a single unit. • V4944/V8944B, N are for use with natural gas. • V4944/V8944C, L are for use with LP gas. • Valve body of die-cast aluminum with a straight-through pattern. • V4944 are used with line voltage, dual-stage controllers; V8944 are used with 24 Vac dual-stage thermostats or controllers. • Valve closes on power failure; recommended for final shutoff service. Bleed Tapping: Two 5/16-24 UNF Pilot Tapping: 1/8-27 NPT Body Pattern: Straight-through, non-offset Valve Closing Time: 2 sec max Mounting: Upright (horizontal) Materials: Body – Aluminum Voltage: V4944-120 Vac; V8944-24 Vac Frequency: 60 Hz Power Consumption: V4944-9 VA max; V8944-12.4 VA max Electrical Connections: 1/4 in. (6 mm) spade terminals (quick connects), leadwires and cover for electrical conduit connection provided. Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: File No. MH1639, Guide No. YIOZ (60 Hz only) Approvals, CSA: Certificate No. 158158-1042930, Guide No. 3302-01, 81 (Z21.21, Z21.78) Pressure Ratings (psi): 1/2 psi Pressure Ratings (kPa): 3.4 kPa Current Ratings: V4944-0.077 max amps at rated Vac/Hz; V8944-0.516 max amps at rated Vac/Hz Dimensions in inches (millimeter) 6-9/16 (167) FOR 1, 1-1/4 OR 7-3/8 (187) FOR 1-1/2, 2 SIDE VIEW 6 (152) 6 (152) TOP VIEW M23232 VENT CONNECTIONS (V4944/V8944 HAVE TWO) Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Valve Opening Time Pressure Regulator Setpoint (in. wc) Comments V4944B1018/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944B1026/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944B1059/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.7 in. wc; Factory Setting, High Fire – 3.0 in. wc (3) 30" leadwires V4944B1075/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.6 in. wc; Factory Setting, High Fire – 3.5 in. wc V4944B1091/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.6 in. wc to 4. in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.6 in. wc; Factory Setting, High Fire – 3.5 in. wc V4944L1024/U LP 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires 826 70-6910 Diaphragm Gas Valves Material Number Type of Fuel Pipe Size (inch) Pipe Size (DN) Opening Characteristics Valve Opening Time Pressure Regulator Setpoint (in. wc) Comments V4944N1011/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1029/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1037/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1045/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V4944N1060/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.0 in. wc; Factory Setting, High Fire – 3.0 in. wc (3) 85" leadwires V8944B1019/U Natural 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944B1027/U Natural 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944B1035/U Natural 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944B1043/U Natural 2 in. DN50 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944C1017/U LP 1 in. DN25 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires V8944C1025/U LP 1 1/4 in. DN32 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires V8944C1033/U LP 1 1/2 in. DN40 Slow Opening 2-stage 3 to 25 sec Adj. Range, Low Fire – 1.4 in. wc to 4.2 in. wc; Adj. Range, High Fire – 8.8 in. wc to 11.5 in. wc; Factory Setting, Low Fire – 1.4 in. wc; Factory Setting, High Fire – 10.0 in. wc (3) 30" leadwires V8944N1012/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1020/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1038/U Natural 1 1/2 in. DN40 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1046/U Natural 2 in. DN50 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 0.8 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1053/U Natural 1 in. DN25 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.2 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires V8944N1061/U Natural 1 1/4 in. DN32 Rapid Opening 2-stage 6 sec max Adj. Range, Low Fire – 0.8 in. wc to 2 in. wc; Adj. Range, High Fire – 3 in. wc to 4.5 in. wc; Factory Setting, Low Fire – 1.2 in. wc; Factory Setting, High Fire – 3.5 in. wc (3) 30" leadwires 70-6910 827 Commercial/Industrial Combustion Controls Diaphragm Gas Valves Diaphragm Gas Valve Replacement Parts or Accessories Material Number Description Used With 116930/U 24 Vac, 60 Hz Replacement Coil for V88A Solenoid Operated Valve V88A 116931/U 120 V/60 Hz Replacement Coil for V48A Solenoid Operated Valve V48; V48A 116932/U 220-240 V/50-60 Hz Replacement Coil for V48A Solenoid Operated Valve V48A 118888/U 24V 60 Hz Replacement Coil for V88J V88J 122160/U Orifice - .018" for V48, V88 V48, V88 124674/U Orifice - .011" for V48, V88 V48, V88 126590/U Adjustable Bleed Valve Assembly for V48, V88, V4004. V8004. 1/8 in. NPT to 1/4 in. compression fitting V48, V88 204480/U Regulator vent pipe fitting to be used with V4843/V8843B, C, L, N and V4844/ V8844B, C, L, N and V4943/V8943, V4944/V8944 V4843B; V4843C; V4843L; V4843N; V8843B; V8843C; V8843L; V8843N; V4844B; V4844C; V4844L; V4844N; V8844B; V8844C; V8844L; V8844N; V4943; V8943; V4944; V8944 828 70-6910 Butterfly Gas Valves V51 Butterfly Gas/Air Valve Provides modulating control of natural, manufactured, LP gases or air. • Use in commercial and industrial installations where large amounts of gas must be closely controlled. • NOT for use as safety shutoff valve. • Adaptable to most modulating jobs. • Modutrol motor, such as the M9484 or M9494, may be mounted directly on valve or close to it. • Valve mechanism has strain release. • Adjustable stroke over low fire-high fire range. • Straight-through valve pattern. • Rugged cast aluminum body provides durability and maintenancefree operation. Type of Fuel: Air; natural; manufactured; LP Body Pattern: Straight-through Mounting: Motor shaft horizontal Materials: Body – Aluminum Operating Temperature Range: 32°F to 140°F (0°C to 60°C) Approvals, Underwriters Laboratories Inc.: File No. MH5968 Vol. 1 Sec. 1, Guide no. MHKZ Pressure Ratings (psi): 5 psi Pressure Ratings (kPa): 34.5 kPa Used With: Mod Motor with Q100 Linkage Accessories: 32003396-001/U – V51E mounting kit for 1-1/2 and 2 in. valve actuators includes brackets and hardware 32003396-002/U – V51E mounting kit for 2-1/2, 3 and 4 in. valve actuators includes brackets and hardware Q100B1006/U – Linkage to connect Modutrol motor to V51E Butterfly Valve. Includes 10 3/4 inch Linkage Rod. Dimensions in inches (millimeter) VALVE SIZE (in.) 1 1/2 2 2 1/2 3 4 2 21/32 3 5/32 3 27/32 4 1/32 5 21/64 67.5 80.2 97.6 102.4 135.3 A A 1 in. mm 1 9/16 1 13/16 2 5/16 2 25/64 3 5/32 39.7 46.0 58.7 60.7 80.2 B B in. mm 4 1/4 4 1/4 4 13/16 5 5 3/8 108.0 108.0 122.2 127.0 136.5 C C in. mm 3 1/32 3 17/32 4 23/32 4 23/32 5 17/64 77.0 89.7 119.9 119.9 133.8 D D in. mm M9532A 1 2 1 1 MAXIMUM DIMENSIONS. 2 NOMINAL DIMENSIONS. V51E DIMENSIONS Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Pressure Tapping Approximate, Dimensions V51E1000/U 1 1/2 in. DN40 4200 cfh 118.9 m3/hr Inlet and outlet pressure taps – Two downstream 1/4 in. NPT taps 2 11/16 in. high x 3 1/16 in. wide x 5 13/16 in. deep (68 mm high x 77 mm wide x 148 mm deep) V51E1018/U 2 in. DN50 9210 cfh 260.7 m3/hr 3 3/16 in. high x 3 9/16 in. wide x 6 1/16 in. deep (80 mm high x 90 mm wide x 154 mm deep) V51E1034/U 2 1/2 in. DN65 8390 cfh 199.8 m3/hr 3 7/8 in. high x 4 3/4 in. wide x 7 1/8 in. deep (98 mm high x 120 mm wide x 181 mm deep) V51E1059/U 3 in. DN80 14640 cfh 414.5 m3/hr 4 1/16 in. high x 4 3/4 in. wide x 7 3/8 in. deep (102 mm high x 120 mm wide x 188 mm deep) V51E1075/U 4 in. DN100 33000 cfh 934.2 m3/hr 5 3/8 in. high x 5 1/4 in. wide x 8 9/16 in. deep (135 mm high x 134 mm wide x 217 mm deep) 70-6910 829 Commercial/Industrial Combustion Controls Butterfly Gas Valves V5197 Integrated Valve Train Butterfly Gas Valve Dimensions in inches (millimeters) 10-5/16 (277) 4-27/32 (123) 6-7/16 (165) 2-1/2 (64) 7-1/8 (181) 3-25/32 (96) M17528 The V5197A valve provides flow control of air, natural gas, liquid petroleum, & manufactured gases which require a high turn down ratio. The adjustment screw controls the maximum flow of gas, but keeps the linear modulating characteristics & stroke. • Used with air, natural, manufactured or liquefied petroleum (LP) gases. • For modulating applications that do not require final shutoff service of firing rate valve. • Two valve body types (small and large) applicable to seven pipe sizes: Small body type for 3/4 in. (19 mm), 1 in. (25 mm), 1-1/4 in. (32 mm), 1-1/2 in. (38 mm) and 2 in. (51 mm) pipes, NPT or ISO 7 threads. Large body type for 2 in. (51 mm), 2-1/2 in. (64 mm) and 3 in. (76 mm) pipes, NPT or ISO 7 threads. • Two downstream 1/4 in. NPT threaded pressure taps available. • Accepts C6097 Pressure Switch mounted directly to flange (downstream pressure tap only). • Unpainted cast aluminum body. • Suitable for electric or pneumatic operators with the appropriate linkage. • May be used with manufacturers own linkage and drive motor. • Flow adjustment screw on bottom of valve controls maximum flow. • Visual position indicator. Type of Fuel: Air; natural; manufactured; LP Pressure Tapping: Inlet and outlet pressure taps – Two downstream 1/4 in. NPT taps Mounting: Directly bolted to Integrated Valve Train (IVT) components or IVT adapters Materials: Body – Die-cast aluminum Operating Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, Underwriters Laboratories Inc.: Component Listed Approvals, CSA: Design Certified Approvals, Swiss RE: Acceptable Pressure Ratings (psi): 15 psi max Pressure Ratings (kPa): 1 Bar Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions V5197A1003 3/4 in.; 1 in.; 1 1/4 in.; 1 1/2 in.; 2 in. DN20; DN25; DN32; DN40; DN50 2450 cfh for 3/4 in.; 3080 cfh for 1 in.; 4430 cfh for 1 1/4 in.; 5010 cfh for 1 1/2 in.; 5480 cfh for 2 in. 51 mm is 155/ 38 mm is 142/ 32 mm is 125/ 25 mm is 87/ 19 mm is 69 10 5/16 in. high x 6 7/16 in. wide x 7 11/32 in. deep (277 mm high x 165 mm wide x 187 mm deep) V5197A1011 2 in.; 2 1/2 in.; 3 in. DN65; DN80; DN50 12,600 cfh for 2 in.; 14,800 cfh for 2 1/2 in.; 16,900 cfh for 3 in. 76 mm is 478/ 64 mm is 419/ 51 mm is 356 12 11/16 in. high x 9 1/4 in. wide x 8 13/16 in. deep (322 mm high x 235 mm wide x 224 mm deep) Firing Rate Gas Valve Parts Material Number Description Used With 49084/0021/U Adjusting arm for V51E. V51E 49085B/U Strain Release Assembly V51E 830 70-6910 Gas Valve Actuators Selection Chart: V5055 and V5097 Industrial Gas Valves with V4055, V4062 or V9055 Fluid Power Actuators The chart below describes every model of V5055 or V5097 Valve in the left column, and every model of Fluid Power Actuator across the top. While it’s possible to combine any valve with any actuator, we’ve marked the recommended valve/actuator combinations which cover most applications with a •. Each valve described in the left column is available: • In these sizes: 3/4 to 3 in. (NPT or parallel BSP). V5055A, B, C are also available in 4 in. size (flange connection only). • With upstream and/or downstream tap. Options available on some Fluid Power Actuators include: • Damper arm shaft, with or without spring return. • NEMA 4 enclosure. • Fast or slow open time (13 or 26 seconds). • Auxiliary switch. • Valve seal overtravel interlock switch. For complete specifications and ordering information on V5055 and V5097 Valves and V4055, V4062 and V9055 Fluid Power Actuators, refer to Index for specific page numbers. Fluid Power Actuators/ Industrial Gas Valves Standard pressurea High Pressurea V5055A, Fb, V5097A V5055B, V5097B V5055C, V5097C V5055D, V5097D V5055E, V5097E Type Model Pressure Ratinga On-Off Characterized Guidec VSOId On-Off VSOId V4055 On-Off A, Ge Standard • • • B High • f • f • Dd Fd e Standard • • Ed High • f • V4062 Hi-Lo-Off A Standard • • B High • f • f • Dd Standard • V9055 Modulating A Standard • Dd Standard • a Refer to the table below for actual pressure ratings of the various combinations of valves and actuators. b V5055F models meet EN161 leakage requirements. c Characterized guide provides a more linear relationship between stem travel and gas flow. Check Honeywell form 70-8311 to verify that flow curve characteristics match application requirements. d Valve Seal Overtravel Interlock. Valve has two shutoff seals, actuator has a proof-of-closure switch. e V4055F, G models include switch for manual control. f These combinations have higher pressure ratings; see the table below. The following combinations of V5055 and V5097 Valves, and V4055, V4062 and V9055 Fluid Power Actuators are approved by these agencies. Underwriters Laboratories, Inc: Listed: MH1639 V4055A/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055B/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055E/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055F/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.). V4055G/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.). V4062A, D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V9055A, D/V5055A, B, C, E (3/4-4 in.) or V5097A-E (3/4-3 in.). Factory Mutual Approved: Report No. 20698, 20835, 21172 and 24061: Valve Actuator Approvals: V4055A/V5055A and V5097A. V4055D/V5055C and V5097C. V4055A/V5055B and V5097B. V4055B/V5055D and V5097D. V4055E/V5055E and V5097E. V4055F/V5055Ca and V5097C. V4055G/V5055A, Ba and V5097A, B. V9055A/V5055B, C and V5097B, C. a Manual reset safety shut-off valves. Pressure Ratings of Valve-Actuator Combinations Model Pipe Size Standard Pressure Actuators V4055A, D, F, G, V4062A, D, V9055A, D High Pressure Actuators V4O55B, E, V4062B M.O.P.D. a Max. Rated Pressure b M.O.P.D. a Max. Rated Pressure b Standard Pressure Valves V5055A, B, C, F, V5097A, B, C 3/4" to 1-1/2" c 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar 2" to 3" d 5 PSI 340 mbar 15 PSI 1.0 Bar 15 PSI 1030 mbar 15 PSI 1.0 Bar 4" flanged e 3 PSI 207 mbar 15 PSI 1.0 Bar 5 PSI 340 mbar 15 PSI 1.0 Bar High Pressure Valves V5055D, E, V5097D, E 3/4" to 1-1/2" c 5 PSI 340 mbar 75 PSI 5.0 Bar 25 PSI 1720 mbar 75 PSI 5.0 Bar 2" to 3" d 5 PSI 340 mbar 45 PSI 3.0 Bar 15 PSI 1030 mbar 45 PSI 3.0 Bar a Max Operating Pressure Differential (UL) or Max Operating Pressure (CSA); maximum allowable pressure drop from inlet to outlet for proper operation. b Max Rated Pressure (UL) or Max Close-off Pressure (CSA); maximum pressure that the valve can be exposed to without leakage or damage to the valve. c Applies for small-body V5097 valves 3/4” up to 2” pipe size. d Applies for large-body V5097 valves 2” up to 3” pipe size. e V5055A, B, C only. 70-6910 831 Commercial/Industrial Combustion Controls Gas Valve Actuators V4055A, B, D, E On-Off Fluid Power Gas Valve Actuator Use in combination with V5055 or V5097 Gas Valves to control gas supply to commercial and industrial burners. • Use where smooth light off is important. • One-second maximum closing time. • Continuously displays the valve position with a red indicator when open and a yellow indicator when closed. • Mount in any position directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Operating Temperature Ratings: 60 Hz Models: -40°F to +150°F (-40°C to +66°C). 50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to +70°C). Contact Ratings: V4055D, E ONLY-Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp Used With: V5055; V5097 Gas Valves Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ Approvals, Factory Mutual: V4055A-When used with the V5055A, B or V5097A, B: Approved, Report Nos. 20698, 20835, 21172, and 24061; V4055B, D, E-When used with the V5055D or V5097D: Approved, Report Nos. 20698, 20835, 21172, and 24061 Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Dimensions in inches (millimeters) B A 1 1 (32.5) KNOCKOUT FOR 1/2 INCH CONDUIT (4) 5 (127.0) 1-9/32 27/32 (21.4) 3-23/32 (94.5) 6-3/4 (171.5) ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL. M10981A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 — 283 283 283 283 298 298 298 — 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 — 70 70 70 70 86 86 86 — DIM A V5055 V5097 IN. MM DIM B IN. MM DIM A IN. MM DIM B IN. MM VALVE VALVE Material Number Electrical Ratings Frequency Timing Internal Auxiliary Switch Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Auxiliary Switch Ratings Comments Includes V4055A1007/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa V4055A1031/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa V4055A1064/U 120 Vac 50 Hz; 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1080/U 240 Vac 50 Hz; 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1098/U 120 Vac 50 Hz; 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1114/U 240 Vac 50 Hz; 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055A1296/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec Yes - adjusted to 90% stroke 5 psi 34 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp V4055A1304/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft with return spring installed V4055A1312/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Nema 4 Enclosure V4055B1021/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Damper Shaft V4055B1039/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Damper Shaft 832 70-6910 Gas Valve Actuators Material Number Electrical Ratings Frequency Timing Internal Auxiliary Switch Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Auxiliary Switch Ratings Comments Includes V4055B1088/U 220 Vac 50 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa V4055D1001/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055D1019/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa Damper Shaft V4055D1027/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec Yes 5 psi 34 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Nema 4 Enclosure V4055D1035/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec Yes 5 psi 34 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp V4055D1043/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 5 psi 34 kPa V4055E1016/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Damper Shaft V4055E1024/U 120 Vac 60 Hz Opening – 26 sec; Closing – < 1 sec Yes 15 or 25 psi 103 or 172 kPa 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Nema 4 Enclosure Damper Shaft V4055E1040/U 120 Vac 60 Hz Opening – 13 sec; Closing – < 1 sec No 15 or 25 psi 103 or 172 kPa Nema 4 Enclosure Damper Shaft 70-6910 833 Commercial/Industrial Combustion Controls Gas Valve Actuators V4055F, G Manual Reset Safety Shut-off Gas Valve Actuators Provide manual reset, safety shut-off functions as required on FM, IHEA-IRI and NFPA 86A,B,C industrial furnaces, ovens and kilns. Use with V5055 or V5097 Gas Valves to control gas supply. • Close in one second maximum. • Continuously displays the valve position with a red indicator when closed. • Mount directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Frequency: 60 Hz Temperature Range: -40°F to +150°F (-40°C to +66°C) Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Dimensions in inches (millimeters) B A 1 1 (32.5) KNOCKOUT FOR 1/2 INCH CONDUIT (4) 5 (127.0) 1-9/32 27/32 (21.4) 3-23/32 (94.5) 6-3/4 (171.5) ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL. M10981A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 — 283 283 283 283 298 298 298 — 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 — 70 70 70 70 86 86 86 — DIM A V5055 V5097 IN. MM DIM B IN. MM DIM A IN. MM DIM B IN. MM VALVE VALVE Material Number Electrical Ratings Internal Auxiliary Switch Timing Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Contact Ratings Description Approvals, Factory Mutual Used With V4055F1006/U 120 Vac No Opening – 13 sec; Closing – < 1 sec 5 psi 34 kPa Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp Manual reset safety shutoff valve with proof of closure switch. When used with the V5055D or V5097D: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 V4055G1004/U 120 Vac No Opening – 13 sec; Closing – < 1 sec 5 psi 34 kPa Manual ON-OFF actuator normally used with V5055/V5907A, B valve bodies. Low pressure. When used with the V5055A, B or V5097A, B: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 834 70-6910 Gas Valve Actuators V4062 Off-Lo-Hi Fluid Power Gas Valve Actuators Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand. • Provide final safety shutoff service when used with V5055 or V5097 gas valve. • One-second maximum closing time. • Continuously displays the valve position with a red indicator when open and a yellow indicator when closed. • Mount in any position directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Electrical Ratings: 120 Vac Frequency: 60 Hz Maximum Safe Operating Pressure (psi): 5 psi Maximum Safe Operating Pressure (kPa): 34 kPa Temperature Range: -40°F to +150°F (-40°C to +66°C) Used With: V5034; V5055; V5097; VE5000 Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZ Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Dimensions in inches (millimeters) B A 1 1 (32.5) KNOCKOUT FOR 1/2 INCH CONDUIT (4) 5 (127.0) 1-9/32 27/32 (21.4) 3-23/32 (94.5) 6-3/4 (171.5) ALLOW 4 IN. (101.6 MM) CLEARANCE FOR ACTUATOR REMOVAL. M10981A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 — 283 283 283 283 298 298 298 — 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 — 70 70 70 70 86 86 86 — DIM A V5055 V5097 IN. MM DIM B IN. MM DIM A IN. MM DIM B IN. MM VALVE VALVE Material Number Internal Auxiliary Switch Timing Contact Ratings Auxiliary Switch Range Description Comments Includes V4062A1008/U No Opening – 26 sec; Closing – < 1 sec Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft V4062A1123/U Yes Opening – 26 sec; Closing – < 1 sec 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft with return spring installed V4062A1131/U No Opening – 13 sec; Closing – < 1 sec Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft V4062A1156/U No Opening – 26 sec; Closing – < 1 sec Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies For Series 60 Floating Control V4062A1198/U Yes - adjusted to 90 degree stroke Opening – 13 sec; Closing – < 1 sec 120 Vac – 9.8 AFL, 58.8 ALR, 1/2 hp; 240 Vac – 4.9 AFL, 29.4 ALR, 1/2 hp Low pressure HI-LO-OFF actuator for use with V5055B and V5097B valve bodies Damper Shaft with return spring installed V4062D1002/U No Opening – 26 sec; Closing – < 1 sec Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp HI-LO-OFF actuator with Proof of Closure normally used on V5055C, E/V5907C, E valve bodies (Low Pressure) Damper Shaft V4062D1010/U No Opening – 13 sec; Closing – < 1 sec Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp HI-LO-OFF actuator with Proof of Closure normally used on V5055C, E/V5907C, E valve bodies (Low Pressure) Damper Shaft 70-6910 835 Commercial/Industrial Combustion Controls Gas Valve Actuators V9055 Modulating Fluid Power Gas Valve Actuators Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand. • Include integral shaft to drive combustion air damper in unison with valve. • One-second maximum closing time. • Continuously displays the valve position with a red indicator when open and a yellow indicator when closed. • Mount in any position directly to valve bonnet with three setscrews. • Provide final safety shutoff service when used with V5055 or V5097 Gas Valves. Frequency: 60 Hz Temperature Range: -40°F to +125°F (-40°C to +52°C) Internal Auxiliary Switch: No Includes: Damper Shaft Approvals, CSA: When used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Underwriters Laboratories Inc.: When used with V5055A, B, C, E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.) Listed MH1696 Approvals, Swiss RE: When used with V5055 or V5097: Acceptable Accessories: 203422C/U – 4-20 ma Adapter for V9055 Material Number Electrical Ratings Comments Timing Maximum Safe Operating Pressure (psi) Maximum Safe Operating Pressure (kPa) Contact Ratings Description Approvals, Factory Mutual Used With V9055A1055/U 120 Vac Opening – 26 sec; Closing – < 1 sec 5 psi 34 kPa Low pressure Modulating-OFF actuator for use with V5055B valve bodies When used with the V5055B, C or V5097B, C: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 V9055A1063/U 120 Vac Nema 4 Enclosure Opening – 26 sec; Closing – < 1 sec 5 psi 34 kPa Low pressure Modulating-OFF actuator for use with V5055B valve bodies When used with the V5055B, C or V5097B, C: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5034; V5055; V5097; VE5000 V9055D1000/U 120 Vac Opening – 26 sec; Closing – < 1 sec 5 psi 34 kPa Proof of Closure (Factory Mutual) Switch – 9.8 AFL, 58.8 ALR, 1/2 hp; 4.9 AFL, 29.4 ALR, 1/2 hp Low pressure Modulating-OFF actuator with Proof of Closure normally used on V5055C, E/V5907C, E valve bodies. V5034; V5055; V5097; VE5000 836 70-6910 Gas Valve Actuators Dimensions in inches (millimeters) B E F C D G A 1 3 D 1/4 INCH NPT DOWNSTREAM TAP AND PLUG 1/4 INCH NPT UPSTREAM TAP AND PLUG (1/4 BSP ON INTERNATIONAL MODELS) 2 1 2 3 \[32.5\] KNOCKOUT FOR1/2 INCH CONDUIT (4) OCTAGON 3/4 \[19.1\] BOLT HOLES (8) ON 3-3/4 (95) RADIUS 1 9 32 1 3 16 \[30\] 9 3 16 \[233\] 27 32 \[21.5\] 3 23 32 5 \[94.5\] 3 \[127.0\] 19 32 \[91\] 6 3 4 \[171.5\] 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 14-1/8 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 5-13/16 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-13/16 8-13/16 11-7/32 5-3/4 5-3/4 5-3/4 5-3/4 8-3/8 9-1/4 9-1/4 12-1/2 13-1/8 13-1/8 13-1/8 13-1/8 13-1/4 13-3/4 13-3/4 16-3/16 2-13/16 2-13/16 2-13/16 2-13/16 3-1/2 4-1/2 4-1/2 — 333.4 333.4 333.4 333.4 336.5 349.3 349.3 411.0 DIM A IN. MM DIM B IN. MM DIM C IN. MM DIM D IN. MM DIM E IN. MM DIM F IN. MM DIM G OCTAGON IN. MM IN. MM ALLOW 4 INCHES CLEARANCE FOR ACTUATOR REMOVAL. ADD 1/8 INCH TO DIMENSION FOR MODELS WITH NEMA 4 ENCLOSURE. ADD 1/4 INCH TO DIMENSION A FOR MODELS WITH NEMA 4 ENCLOSURE. M7321 282.6 282.6 282.6 282.6 285.8 298.5 298.5 358.8 69.9 69.9 69.9 69.9 73.0 85.7 85.7 147.6 208.0 208.0 208.0 208.0 211.1 223.8 223.8 285.0 146.1 146.1 146.1 146.1 212.7 235.0 235.0 317.5 2-1/4 2-1/4 2-1/4 2-1/4 2-3/4 2-3/4 2-3/4 4-5/8 57.2 57.2 57.2 57.2 69.9 69.9 69.9 117.5 4-13/16 4-13/16 4-13/16 4-13/16 7-19/32 7-19/32 7-19/32 — 122.2 122.2 122.2 122.2 192.9 192.9 192.9 — 71.4 71.4 71.4 71.4 88.9 114.3 114.3 — Fluid Actuator Accessories and Parts Material Number Description Used With 133568/U Auxiliary Switch (Adjustable Valve Position) for V4055, V4062 or V9055 V4055; V4062; V9055 133569/U Replacement Pre-ignition Interlock (Proof of Closure) Switch for V4055D, E; V4062D or V9055D V4055; V4062; V9055 203422C/U 4-20 ma Adapter for V9055 V9055 7616BR/U Crank Arm assembly with clip for Damper Arm of V4055, V4062 or V9055 V4055; V4062; V9055 70-6910 837 Commercial/Industrial Combustion Controls Industrial Gas Valves V5055 Industrial Gas Valves Safety shutoff valves used with V4055, V4062 and V9055 fluid power actuators to control gas flow to commercial and industrial burners. • Use with natural or LP gases. • Mount directly in gas supply line. • Include 1/4 in. NPT upstream and downstream taps and plug. • 4 in. models have only flanged connections. • V5055 normally closed valves are rated for final shutoff service safety shutoff. • V5055A, C, D, E Valves are for On-Off service. • V5055B Valve has a characterized guide and in combination with the V4055, V4062, and V9055 Fluid Power Actuators, provides slowopening, hi-lo-off, and modulating functions respectively. • V5055C, E, F Valves have a double seal and are used with V4055D, E Actuators to provide proof-of-closure switch and valve seal overtravel interlock. • V5055D, E, F Valves are for high pressure applications. Operating Temperature Range: -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C) Approvals, Underwriters Laboratories Inc.: When used with V4055A, B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ Approvals, CSA: When used with V4055, V4062, and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Swiss RE: When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 Used With: V9055; V4055; V4062 Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055A1004/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1012/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055A1020/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055A1038/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1046/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1053/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1228/U 4 in. DN100 10200 cfh 288.8 m3/hr Flanged With V4055A, D or V4062 – 3 psi (20.7 kPa); With V4055B or E – 5 psi (340 mbar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055A1343/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug 838 70-6910 Industrial Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055B1002/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1010/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055B1028/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055B1069/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1077/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1085/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055B1150/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062 – 3 psi (20.7 kPa); With V4055B or E – 5 psi (340 mbar) When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1000/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1018/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1026/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055C1034/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1042/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug 70-6910 839 Commercial/Industrial Combustion Controls Industrial Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055C1059/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1109/U 4 in. DN100 9180 cfh 259.9 m3/hr Flanged With V4055A, D or V4062 – 3 psi (20.7 kPa); With V4055B or E – 5 psi (340 mbar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055C1182/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055D1008/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1016/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1024/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1032/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1040/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1057/U 3 in. DN80 5230 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055D1065/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055E1005/U 2 in. DN50 3620 cfh 102.5 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055E1013/U 2 1/2 in. DN65 4250 cfh 120 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055E1021/U 3 in. DN80 5230 cfh 148 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055E1039/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug 840 70-6910 Industrial Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Connection Type Maximum Operating Differential Pressure Approvals, Factory Mutual Comments Includes V5055E1047/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055E1054/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055E1062/U 3/4 in. DN20 665 cfh NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18 NPT downstream tap and plug V5055F1003/U 1 in. DN25 960 cfh 27.2 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Meets Intent of DIN Seat Leakage Requirements 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055F1011/U 1 1/2 in. DN40 1717 cfh 48.6 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Meets Intent of DIN Seat Leakage Requirements 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug V5055F1037/U 1 1/4 in. DN32 1406 cfh 39.8 m3/hr NPT With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Meets Intent of DIN Seat Leakage Requirements 1/4 in. -18 NPT downstream tap and plug, 1/4 in. -18 NPT upstream tap and plug Dimensions in inches (millimeters) B E F C D A 1 1/4 INCH NPT DOWNSTREAM TAP AND PLUG 1 KNOCKOUT FOR1/2 INCH CONDUIT (4) OCTAGON 5 (127) 27/32 (21) 3-23/32 (95) 6-3/4 (172) ALLOW 2 IN. (51 mm) CLEARANCE FOR ACTUATOR REMOVAL. M27268A 3/4 1 1-1/4 1-1/2 2 2-1/2 3 VALVE SIZE INCH 11-1/8 11-1/8 11-1/8 11-1/8 11-1/4 11-3/4 11-3/4 283 283 283 283 286 299 299 2-3/4 2-3/4 2-3/4 2-3/4 2-7/8 3-3/8 3-3/8 70 70 70 70 73 86 86 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-13/16 8-13/16 208 208 208 208 211 224 224 5-3/4 5-3/4 5-3/4 5-3/4 8-3/8 9-1/4 9-1/4 146 146 146 146 213 235 235 2-1/4 2-1/4 2-1/4 2-1/4 2-3/4 2-3/4 2-3/4 57 57 57 57 70 70 70 4-7/8 4-7/8 4-7/8 4-7/8 7-19/32 7-19/32 7-19/32 124 124 124 124 193 193 193 2-13/16 2-13/16 2-13/16 2-13/16 3-1/2 4-1/2 4-1/2 71 71 71 71 89 114 114 DIM A IN. MM DIM B IN. MM DIM C IN. MM DIM D IN. MM DIM E IN. MM DIM F IN. MM OCTAGON IN. MM 1-9/32 (33) 1/4 INCH NPT UPSTREAM TAP AND PLUG 70-6910 841 Commercial/Industrial Combustion Controls Industrial Gas Valves OCTAGON H 6-3/4 (171) 1-9/32 (33) A B C D DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J E G F J OCTAGON 5 (127) VALVE SIZE (IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 283 283 283 283 298 298 298 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 70 70 70 70 86 86 86 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-5/16 8-5/16 208 208 208 208 211 211 211 8-1/4 8-1/4 8-1/4 8-1/4 11-3/4 11-3/4 11-3/4 210 210 210 210 298 298 298 IN. MM IN. MM IN. MM 62 62 62 62 91 91 91 5 5 5 5 8 8 8 127 127 127 127 203 203 203 58 58 58 58 113 113 113 23 23 23 23 38 38 38 100 100 100 100 165 165 165 71 71 71 71 114 114 114 3/4 1 1-1/4 1-1/2 2 2-1/2 3 M27581 1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL. 1 2-7/16 2-7/16 2-7/16 2-7/16 3-5/8 3-5/8 3-5/8 2-5/16 2-5/16 2-5/16 2-5/16 4-7/16 4-7/16 4-7/16 7/8 7/8 7/8 7/8 1-1/2 1-1/2 1-1/2 3-15/16 3-15/16 3-15/16 3-15/16 6-1/2 6-1/2 6-1/2 2-13/16 2-13/16 2-13/16 2-13/16 4-1/2 4-1/2 4-1/2 842 70-6910 Industrial Gas Valves V5097 Integrated Valve Train Safety shutoff valves used with V4055, V4062 and V9055 fluid power actuators to control gas flow to commercial and industrial burners. • Use with natural or LP gases. • Mount directly in gas supply line. • Two Valve body types. Small body type for 3/4 in., 1 in., 1-1/4 in., 1-1/2 in., 2 in. pipes. Large body types for 2 in., 2-1/2 in. and 3 in. pipes. • Seven pipe adapter sizes from 3/4 in. to 3 in. have NPT or BSP threaded connections. • Provides three 1/4 in. upstream and two 1/4 in. downstream tap and plug. • CE version provides an additional downstream tap and plug. • Yellow SHUT indicator attached to the valve stem provides an indication of the valve closed position. • V5097A, C, D, E Valves are for on-off service. • V5097B Valve has a characterized guide and in combination with the V4055, V4062 and V9055 Fluid Power Actuators, provides slowopening, HI-LO-OFF, and modulating functions, respectively. • V5097C, E Valves have a double seal and are used with V4055D, E Actuators to provide proof-of-closure switch and valve seal overtravel interlock. • Actuators to provide proof-of-closure switch and valve seal overtravel interlock. • V5097D, E Valves are for high pressure applications. • Two valve body types (small and large) applicable to server pipe size. Operating Temperature Range: -40°F to +150°F; When used with V9055 – -40°F to +125°F (-40°C to +66°C; When used with V9055 – -40°C to +52°C) Approvals, Underwriters Laboratories Inc.: When used with V4055A, B, D, E, V4062, V9055: Listed, File No. MH1639 Guide No. YIOZ Approvals, CSA: When used with V4055, V4062, and V5097: Certified General listed File No. 158158, Class 3371 for USA and Canada Approvals, Swiss RE: When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061 Approvals, CE: CE #E3070 (Gastec) Comments: Select Proper Pipe Adapter Includes: Three 1/4 in. -18 NPT upstream and two 1/4 in. -18 NPT downstream taps Used With: V9055; V4055; V4062 Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Maximum Operating Differential Pressure Integrated Valve Train Body Size Approvals, Factory Mutual V5097A1004/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Small body When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097A1012/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055A, G: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097B1002/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Small body When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097B1010/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055A, G and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24061 V5097C1000/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Small body When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24066 V5097C1018/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055D, F and V9055A: Approved, Report Nos. 20698, 20835, 21172, and 24066 V5097D1008/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Small body When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 V5097D1016/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055B: Approved, Report Nos. 20698, 20835, 21172, and 24068 V5097E1005/U 3/4 in. or 1 in. or 1 1/4 in. or 2 in. DN20 or DN25 or DN32 or DN50 665 cfh to 3620 cfh 18.8 to 102.5 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 25 psi (1.6 bar) Small body When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 V5097E1013/U 2 in. or 2 1/2 in. or 3 in. DN50 or DN65 or DN80 3620 cfh to 5230 cfh 102.5 to 148.0 m3/hr With V4055A, D or V4062 – 5 psi (340 mbar); With V4055B or E – 15 psi (1 bar) Large body When used with the V4055E: Approved, Report Nos. 20698, 20835, 21172, and 24068 70-6910 843 Commercial/Industrial Combustion Controls Industrial Gas Valves Dimensions in inches (millimeters) 6-3/4 (171) 1-9/32 (33) A B C D DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J E G H F J OCTAGON OCTAGON 5 (127) VALVE SIZE (IN.) IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM 11-1/8 11-1/8 11-1/8 11-1/8 11-3/4 11-3/4 11-3/4 283 283 283 283 298 298 298 2-3/4 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 70 70 70 70 86 86 86 8-3/16 8-3/16 8-3/16 8-3/16 8-5/16 8-5/16 8-5/16 208 208 208 208 211 211 211 8-1/4 8-1/4 8-1/4 8-1/4 11-3/4 11-3/4 11-3/4 210 210 210 210 298 298 298 IN. MM IN. MM IN. MM 62 62 62 62 91 91 91 5 5 5 5 8 8 8 127 127 127 127 203 203 203 58 58 58 58 113 113 113 23 23 23 23 38 38 38 100 100 100 100 165 165 165 71 71 71 71 114 114 114 3/4 1 1-1/4 1-1/2 2 2-1/2 3 M11682B 1 ALLOW 2 IN. (51 MM) CLEARANCE FOR ACTUATOR REMOVAL. 1 2-7/16 2-7/16 2-7/16 2-7/16 3-5/8 3-5/8 3-5/8 2-5/16 2-5/16 2-5/16 2-5/16 4-7/16 4-7/16 4-7/16 7/8 7/8 7/8 7/8 1-1/2 1-1/2 1-1/2 3-15/16 3-15/16 3-15/16 3-15/16 6-1/2 6-1/2 6-1/2 2-13/16 2-13/16 2-13/16 2-13/16 4-1/2 4-1/2 4-1/2 844 70-6910 Industrial Gas Valves Integrated Valve Train Pipe Adapters Material Number Pipe Size (inch) Pipe Size (DN) Connection Type Integrated Valve Train Body Size Description Used With 32000109-001/U 3/4 in. DN20 NPT Small body 3/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-002/U 1 in. DN25 NPT Small body 1 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-003/U 1 1/4 in. DN32 NPT Small body 1 1/4 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-004/U 1 1/2 in. DN40 NPT Small body 1 1/2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-005/U 2 in. DN50 NPT Small body 2 in. NPT Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-006/U 3/4 in. DN20 BSP Small body 3/4 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32000109-007/U 1 in. DN25 BSP Small body 1 in. BSP Pipe Adapter Small Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-001/U 2 in. DN50 NPT Large body 2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-002/U 2 1/2 in. DN65 NPT Large body 2 1/2 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-003/U 3 in. DN80 NPT Large body 3 in. NPT Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-004/U 2 in. DN50 BSP Large body 2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-005/U 2 1/2 in. DN65 BSP Large body 2 1/2 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 32001605-006/U 3 in. DN80 BSP Large body 3 in. BSP Pipe Adapter Large Body Integrated Valve Train. Required for Valve Train Assembly. V5097; V4297; V5197 V5055/5097 Replacement Parts or Accessories Material Number Description Used With 133392A/U O-Ring Assembly for 2 in., 2 1/2 in., and 3 in. V5055 valves V5055/V5097 valves 133393A/U O-Ring Assembly for 1 in., 1 1/4 in., and 1 1/2 in. V5055 valves V5055/V5097 valves 133398AA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055A valves V5055/V5097 valves 133398BA/U Replacement Bonnet Assembly with 133393A Seal Assembly for 3/4, 1, 1-1/4, 1-1/2 in. V5055B valves V5055/V5097 valves 133398CA/U Replacement Bonnet Assembly, with 137253A replacement Seal Assembly for small body (3/4, 1, 1 1/2 in.) V5055/V5097C. V5055/V5097 valves 133417AA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055A valves V5055/V5097 valves 133417BA/U Replacement Bonnet Assembly with 133392A Seal Assembly for 2, 2 1/2, and 3 in. V5055B valves V5055/V5097 valves 133417CA/U Bonnet Assembly for 2, 2 1/2, or 3 in. V5055C or V5097C valves V5055C/V5097C valves 137253A/U Replacement seal assembly. For 4 inch V5055. V5055 4074EYE/U Bag assembly for V5097 (large body) includes 6 ea bolts, nuts and washers. Large Body V5097 4074EYF/U Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. Small Body V5097 4074EYK/U Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. Small Body V5097 4074EYL/U Bag assembly for V5097 (large body) includes (2) O-rings, (1) grease capsule. Large Body V5097 70-6910 845 Commercial/Industrial Combustion Controls Pilot Gas Valves V4046C; V8046C Pilot Gas Valves Dimensions in inches (millimeters) 1-3/16 (30) DIM. A 1-3/8 (35) 1-5/8 (41) 1-3/4 (45) 2-5/8 (67) 1-3/4 (45) DIM. B 1-1/4 (32) BASIC CENTER 45 BASIC CENTER 8-32 x 1/4 IN.(6) DEEP (2) 1/2-14 NPSM 36 IN. (915) LEADS (2) THREAD SIZE MODEL V4046C, V8046C BODY SIZE THREAD SIZE SMALL SMALL LARGE LARGE 1/8-27 NPT 1/4-18 NPT 1/4-18 NPT 3/8-18 NPT 5/16 3/8 1/2 1/2 8 10 13 13 2-3/4 3 3-1/4 3-1/4 70 76 83 83 DIM. A DIM. B IN MM IN MM M16595A Provide on-off control of natural, LP and manufactured gases to pilot burners in industrial and commercial applications. • Magnetically operated, normally closed. • Provide instantaneous action when energized. • On power failure, valve closes in one second maximum. • Use in any position, directly in pipe line or on support bracket. • Replace the solenoid coil without removing the valve body from the piping connections. • Straight-through valve pattern. • Available in line voltage or low voltage models. Type of Fuel: Air; natural; manufactured; LP Body Pattern: Straight-through Valve Opening Time: 1 sec max Valve Closing Time: 1 sec max Mounting: Directly in pipe or on support bracket Materials: Body – Aluminum Power Consumption: 8 W Operating Temperature Range: -40°F to +125°F (-40°C to +52°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. MH1639, V3, S3 - Guide No. YIOZ Approvals, CSA: Certificate No. 158158-2500006058, Guide No. C3371-03, 83 Approvals, Factory Mutual: Approved: Report No. 17450 Pressure Ratings (psi): 10 psi Pressure Ratings (kPa): 68.9 kPa Material Number Pipe Size (inch) Capacity (cfh) Capacity (m3/hr) Voltage Frequency Electrical Connections Approvals, Swiss RE V4046C1005/U 1/8 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1021/U 1/4 in. 20 cfh 0.57 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1047/U 1/4 in. 55 cfh 1.56 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1054/U 3/8 in. 67 cfh 1.90 m3/hr 110 Vac; 120 Vac 50 Hz; 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing Acceptable V4046C1120/U 3/8 in. 67 cfh 1.90 m3/hr 120 Vac 60 Hz Two 10 ft. leadwires and 1/2 in. conduit bushing Acceptable V8046C1006/U 1/8 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing V8046C1014/U 1/4 in. 20 cfh 0.57 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing V8046C1022/U 1/4 in. 55 cfh 1.56 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing V8046C1030/U 3/8 in. 67 cfh 1.90 m3/hr 24 Vac 60 Hz Two 36-in. leadwires and 1/2 in. conduit bushing 846 70-6910 Solenoid Gas Valves V4295; V8295 Solenoid Gas Valves V4295A/V8295A normally closed and V4295S/V8295S normally open (vent) solenoid gas valves, are suitable for furnaces, ovens, atmospheric burners, commercial water heaters, rooftop make-up air units, power burners, and commercial/industrial boilers. • V8295A, S are used with 24 Vac controllers. • V4295A, S are used with 120 Vac controllers. • Positive close off of gas flow when de-energized. • High valve spring force allows up to 0.7 psi back pressure at valve seat. • No inlet pressure influence at valve seat. • Inlet pressure changes do not affect ability to close valve. • Low operating noise. • Low rush-in current. • Upstream and downstream taps allows tapping and testing pressure points. Type of Fuel: Air; natural; manufactured; mixed; LP Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT Body Pattern: Straight-through, non-offset Valve Opening Time:less than 1 sec Valve Closing Time: less than 1 sec Mounting: Vertical to 90 degrees from vertical Materials: Body – Die-cast aluminum Frequency: 50 Hz; 60 Hz Electrical Connections: Screw terminals Operating Temperature Range: -40°F to +140°F (-40°C to +60°C) Approvals, Swiss RE: Acceptable Approvals, Control Safety Devices: Acceptable Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Voltage Approximate, Dimensions Current Ratings Pressure Ratings (psi) Pressure Ratings (kPa) Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual V4295A1015 1/2 in. DN15 250 cfh 7.1 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1023 3/4 in. DN20 645 cfh 18.3 m3/hr 120 Vac 5 1/4 in. high x 3 7/16 in. wide x 2 3/4 in. deep (133 mm high x 87 mm wide x 70 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1031 1 in. DN25 790 cfh 22.4 m3/hr 120 Vac 5 1/4 in. high x 3 15/16 in. wide x 3 in. deep (133 mm high x 100 mm wide x 76 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1049 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 120 Vac 8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (203 mm high x 151 mm wide x 111 mm deep) 0.34 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1056 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 120 Vac 8 3/8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (213 mm high x 151 mm wide x 111 mm deep) 0.3 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1064 2 in. DN50 3465 cfh 98.1 m3/hr 120 Vac 8 3/8 in. high x 6 11/16 in. wide x 5 3/8 in. deep (213 mm high x 170 mm wide x 137 mm deep) 0.525 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1072 2 1/2 in. DN65 5070 cfh 143.5 m3/ hr 120 Vac 12 3/4 in. high x 9 1/2 in wide x 7 7/8 in. deep (324 mm high x 241 mm wide x 200 mm deep) 0.575 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1080 3 in. DN80 6100 cfh 172.7 m3/ hr 120 Vac 12 3/4 in. high x 9 1/2 in wide x 7 7/8 in. deep (324 mm high x 241 mm wide x 200 mm deep) 0.675 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF 70-6910 847 Commercial/Industrial Combustion Controls Solenoid Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Voltage Approximate, Dimensions Current Ratings Pressure Ratings (psi) Pressure Ratings (kPa) Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual V4295A1098 3/8 in. 210 cfh 5.9 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.16 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1106 1/2 in. DN15 290 cfh 8.2 m3/hr 120 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.16 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1114 3/4 in. DN20 610 cfh 17.3 m3/hr 120 Vac 3 3/16 in. high x 3 7/16 in. wide x 2 3/4 in. deep (81 mm high x 87 mm wide x 70 mm deep) 0.2 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1122 1 in. DN25 825 cfh 23.4 m3/hr 120 Vac 6 5/16 in. high x 3 15/16 in. wide x 3 in. deep (160 mm high x 100 mm wide x 76 mm deep) 0.2 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1130 1 1/4 in. DN32 1950 cfh 55.2 m3/hr 120 Vac 8 9/16 in. high x 5 15/16 in. wide x 4 3/8 in. deep (217 mm high x 151 mm wide x 111 mm deep) 0.55 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1148/U 1 1/2 in. DN40 2270 cfh 64.3 m3/hr 120 Vac 8 9/16 in. high x 5 15/16 in. wide x 4 3/8 in. deep (217 mm high x 151 mm wide x 111 mm deep) 0.55 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295A1155 2 in. DN50 3740 cfh 105.9 m3/ hr 120 Vac 9 3/16 in. high x 6 11/16 in. wide x 5 3/8 in. deep (233 mm high x 170 mm wide x 137 mm deep) 0.54 max amps at rated Vac/Hz 5 psi 34.5 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 04, 83 Approved: Report No. J.I.OD6A2. AF V4295S1005 3/4 in. DN20 350 cfh 9.9 m3/hr 120 Vac 5 1/2 in. high x 3 7/16 in. wide x 2 3/4 in. deep (140 mm high x 87 mm wide x 70 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 83 Approved: Report No. J.I.OD6A2. AF V4295S1013 1 in. DN25 420 cfh 11.9 m3/hr 120 Vac 5 1/2 in. high x 3 15/16 in. wide x 3 in. deep (140 mm high x 100 mm wide x 76 mm deep) 0.16 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 83 Approved: Report No. J.I.OD6A2. AF V4295S1021 1 1/4 in. DN32 1100 cfh 31.1 m3/hr 120 Vac 8 3/4 in. high x 5 15/16 in. wide x 4 3/8 in. deep (222 mm high x 151 mm wide x 111 mm deep) 0.34 max amps at rated Vac/Hz 2 psi 13.8 kPa Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 83 Approved: Report No. J.I.OD6A2. AF V8295A1016 1/2 in. DN15 250 cfh 7.1 m3/hr 24 Vac 4 7/16 in. high x 2 7/8 in. wide x 2 3/16 deep (113 mm high x 73 mm wide x 56 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1024 3/4 in. DN20 645 cfh 18.3 m3/hr 24 Vac 5 1/4 in. high x 3 7/16 in. wide x 2 3/4 in. deep (133 mm high x 87 mm wide x 70 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1032 1 in. DN25 790 cfh 22.4 m3/hr 24 Vac 5 1/4 in. high x 3 15/16 in. wide x 3 in. deep (133 mm high x 100 mm wide x 76 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only 848 70-6910 Solenoid Gas Valves Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Voltage Approximate, Dimensions Current Ratings Pressure Ratings (psi) Pressure Ratings (kPa) Approvals, Underwriters Laboratories Inc. Approvals, CSA Approvals, Factory Mutual V8295A1040 1 1/4 in. DN32 1450 cfh 41.0 m3/hr 24 Vac 8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (203 mm high x 151 mm wide x 111 mm deep) 1.6 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1057 1 1/2 in. DN40 2190 cfh 62.0 m3/hr 24 Vac 8 3/8 in. high x 5 15/16 in. wide x 4 3/8 in. deep (213 mm high x 151 mm wide x 111 mm deep) 1.7 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295A1065 2 in. DN50 3465 cfh 98.1 m3/hr 24 Vac 8 3/8 in. high x 6 11/16 in. wide x 5 3/8 in. deep (213 mm high x 170 mm wide x 137 mm deep) 2.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only V8295S1006 3/4 in. DN20 350 cfh 9.9 m3/hr 24 Vac 5 1/2 in. high x 3 7/16 in. wide x 2 3/4 in. deep (140 mm high x 87 mm wide x 70 mm deep) 0.8 max amps at rated Vac/Hz 2 psi 13.8 kPa Component Recognized; File No. YLOZ Certificate No. 158158- 1154280, Guide No. C3371-03, 85 Approved: 3/8 in., 1/2 in., 3/4 in. only 70-6910 849 Commercial/Industrial Combustion Controls Solenoid Gas Valves V4297A Solenoid Safety Shut-off Valve for IVT V4297A are normally closed solenoid gas valve. Suitable for use on furnaces, ovens, atmospheric burners, commercial water heaters, rooftop make-up air units, power burners, and commercial/industrial boilers. • V4297A are used with 120 Vac controllers. • Positive close off of gas flow when de-energized. • High valve spring force allows up to 0.7 psi back pressure at valve seat. • No inlet pressure influence at valve seat. • Inlet pressure changes do not affect ability to close valve. • Low operating noise. • Low rush-in current. • Upstream and downstream taps allows tapping and testing pressure points. • For use with the Integrated Valve Train. • Accepts C6097 Pressure Switch mounted directly to flange (upstream pressure tap only). Type of Fuel: Air; natural; manufactured; mixed; LP Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT Body Pattern: Straight-through, non-offset Valve Opening Time: less than 1 sec Valve Closing Time: less than 1 sec Flanges: Required, Order Separately Mounting: Directly bolted to Integrated Valve Train Components Materials: Body – Die-cast aluminum Voltage: 110 Vac; 120 Vac Frequency: 50 Hz; 60 Hz Electrical Connections: Screw terminals Operating Temperature Range: -40°F to +130°F (-40°C to +54°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371- 03, 04, 83 Approvals, Swiss RE: Acceptable Pressure Ratings (psi): 5 psi Pressure Ratings (kPa): 34.5 kPa Replacement Parts: 4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. 4074EYK/U – Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. Dimensions in inches (millimeters) 2 (51) 5 (127) 5-1/2 (140) 5-5/8 (143) 3-3/4 (95) 1-1/2 (38) 2-3/4 (70) 1/2 (13) 5-3/4 (147) 6-1/4 (159) 10-1/4 (260) M23226 TOP VIEW Material Number Pipe Size (inch) Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions Integrated Valve Train Body Size Current Ratings V4297A1005 3/4 in. to 1 1/4 in. DN20 or DN25 or DN32 650 cfh; 700 cfh; 780 cfh 19.8 m3/hr 9 in. high x 5 3/4 in. wide x 5 5/8 in. deep (229 mm high x 147 mm wide x 143 mm deep) Small body, small flow 0.2 max amps at rated Vac/Hz V4297A1013 3/4 in. to 2 in. DN20 or DN25 or DN32 or DN40 or DN50 1190 cfh; 1460 cfh; 2260 cfh; 2735 cfh; 3060 cfh 10 1/4 in. high x 5 3/4 in. wide x 5 5/8 in. deep (260 mm high x 147 mm wide x 143 mm deep) Small body, large flow 0.5 max amps at rated Vac/Hz 850 70-6910 Solenoid Gas Valves V4297S Normally Open Vent Valve for IVT V4297S are normally open (vent) solenoid gas valves. Suitable for use on furnaces, ovens, atmospheric burners, commercial water heaters, rooftop make-up air units, power burners, and commercial/industrial boilers. • V4297S is used with 120 Vac controllers. • Low operating noise. • Low rush-in current. • Upstream and downstream taps allows tapping and testing pressure points. • For use with the Integrated Valve Train. Type of Fuel: Air; natural; manufactured; mixed; LP Pressure Tapping: Inlet and outlet pressure taps – 1/4 in. NPT Body Pattern: Straight-through, non-offset Valve Opening Time: less than 1 sec Valve Closing Time: less than 1 sec Flanges: Required for Stand Alone Mounting: Directly bolted to Integrated Valve Train Components Materials: Body – Die-cast aluminum Voltage: 110 Vac; 120 Vac Frequency: 50 Hz; 60 Hz Electrical Connections: Screw terminals Operating Temperature Range: -40°F to +145°F (-40°C to +63°C) Approvals, Underwriters Laboratories Inc.: Listed: File No. MH18476, V1, S1 - Guide No. YIOZ Approvals, CSA: Certificate No. 158158-1154280, Guide No. C3371- 03, 04, 83 Approvals, Swiss RE: Acceptable Pressure Ratings (psi): 5 psi Pressure Ratings (kPa): 34.5 kPa Replacement Parts: 4074EYF/U – Bag assembly for V5097 (small body) includes 6 ea bolts, nuts and washers. 4074EYK/U – Bag assembly for V5097 (small body) includes (2) O-rings, (1) grease capsule. 4074EYL/U – Bag assembly for V5097 (large body) includes (2) O-rings, (1) grease capsule. Dimensions in inches (millimeters) 2-5/8 3 (69) (76) 1-1/2 (38) 5/16 (8) 3/4 (18) 3/4 (18) 2 (51) 5 (127) 8 (203) 1-1/2 3/16 (5) (32) M23252 2 (51) 12-3/8 (314) 3-1/8 (79) 1/2 (13) 4-1/2 (114) 5/8 (16) 1 (25) 1/2 (13) 1-1/4 IN. NPT 1/2 (13) (3 HOLES) 3/8 (10) (3 HOLES) 2-5/8 (69) 9-1/2 (241) 3-1/8 (79) 3/8 (10) 1/2 (13) 1/2 (13) 7/8 (22) 4-1/8 (105) 3-1/8 (79) 5 (127) 3/8 (10) 1/2 (13) 1-1/4 (32) 2 (51) 1-1/2 (32) 3/16 (5) 1-15/16 (49) 2-3/8 (60) M23251 2 (51) 1 IN. NPT Material Number Pipe Size (DN) Capacity (cfh) Capacity (m3/hr) Approximate, Dimensions Integrated Valve Train Body Size Current Ratings V4297S1003 DN25 714 cfh 20.2 m3/hr 9 1/2 in. high x 3 1/8 in. wide x 5 in. deep (241 mm high x 79 mm wide x 127 mm deep) Small body 0.2 max amps at rated Vac/Hz V4297S1011 DN32 1115 cfh 31.6 m3/hr 12 3/8 in. high x 5 in. wide x 8 in. deep (314 mm high x 127 mm wide x 203 mm deep) Large body 0.34 max amps at rated Vac/Hz 70-6910 851 Commercial/Industrial Combustion Controls Servo Regulated Gas Valves V4730C; V4734C; V8730C Gas/Air Servo Regulated Gas Valves Body Pattern: Straight flange Valve Opening Time: Dead time maximum: 1 second; First valve – < 1 second; Second valve – reaches 50% of the adjustable outlet pressure within 5 seconds Materials: Body: Aluminum alloy, die-cast Frequency: 50 Hz; 60 Hz Ambient Temperature Range: 5°F to 140°F (-15°C to +60°C) Approvals, Underwriters Laboratories Inc.: File No. MH18476 Approvals, CSA: File: Certificate No: 158158-1227192 Approvals, Others: Gas Appliance Directive: 90.396/EEC, PIN: 0063AT1198, Low Voltage Directive: 73/23/EEC, Electro Magnetic Compatibility Directive: 89/336/EEC Maximum Safe Operating Pressure (psi): 0.5 psi (CSA approved), 1.45 psi for 120V; 1 psi for 24V (UL approved) Maximum Operating Pressure (mbar): 200 mbar (UL approved) 100 mbar for 120V; 69 mbar for 24V (UL approved), 35 mbar (CSA approved) Comments: The minimum load for which the system can be used is 14-17% of the reference load, which equals a minimum pressure differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas control. Coil Insulation Solenoid Valves: Class H insulation system Current Ratings: V1 Current Rating – 0.16A; V2 Current Rating – 0.16A; V1 + V2 Current Rating – 0.32A Material Number Pipe Size (inch) Capacity (kW) Capacity (kBtuh) Voltage Electrical Connections Pipe Connection Includes Max. Capacity with Strainer (cfh) V4730C1006-0000 1/2 in. Natural Gas 0.64 sp.gr – 22-150 KW Natural Gas 0.64 sp.gr – 73- 512 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-001 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 221 cfh V4730C1014-0000 3/4 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-002 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V4730C1022-0000 1 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-003 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V4730C1030-0000 1 1/4 in. Natural Gas 0.64 sp.gr – 55-382 KW when used with VMU335, 71-500KW Natural Gas 0.64 sp.gr – 185- 1300 kBtuh when used with VMU335,245- 1710 kBtuh 120 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-004 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1300 cfh 852 70-6910 Servo Regulated Gas Valves Material Number Pipe Size (inch) Capacity (kW) Capacity (kBtuh) Voltage Electrical Connections Pipe Connection Includes Max. Capacity with Strainer (cfh) V4734C1002-0000 1 1/4 in. Natural Gas 0.64 sp.gr – 97-680 KW when used with VMU680 Natural Gas 0.64 sp.gr – 326- 2287 kBtuh when used with VMU680 120 Vac (+10%, -15%) Mesh screen filter and 32006652-004 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) V8730C1007-0000 1/2 in. Natural Gas 0.64 sp.gr – 22-150 KW Natural Gas 0.64 sp.gr – 73- 512 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-001 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 221 cfh V8730C1015-0000 3/4 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-002 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V8730C1023-0000 1 in. Natural Gas 0.64 sp.gr – 43-300 KW Natural Gas 0.64 sp.gr – 146- 1024 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-003 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1024 cfh V8730C1031-0000 1 1/4 in. Natural Gas 0.64 sp.gr – 55-382 KW when used with VMU335, 71-500 KW Natural Gas 0.64 sp.gr – 185- 1300 kBtuh when used with VMU335, 245-1710 kBtuh 24 Vac (+10%, -15%) Standard DIN plug connector with 36 in. (914 mm) leadwires, included. 1/8 in. (3mm) NPT pressure taps at inlet and outlet flanges. Six flange pressure taps connections are provided at the main body to mount either a pressure switch (low or high) or a Valve Proving System (VPS). Mesh screen filter and 32006652-004 Flange kit. (Kit includes 1 pipe adapter, 1 O-ring, 4 mounting screws, 1 DIN connector and wiring harness kit.) Nat. Gas (Delta P= 1 in. w.c.) – 1300 cfh # ECC or Buildings Branch | Flame Safeguard part 3 Servo Regulated Gas Valves Dimensions in inches (millimeters) M22414 6-1/8 (156) 1-27/32 (48) 4-7/32 (107) 5-1/4 (133) 7-5/16 (240) 2 (51) 2-1/32 (52) 1-11/16 3-7/8 (98) (43) PRESSURE SWITCH OPTIONAL VALVE POSITION INDICATOR LAMPS M22415 6-1/8 (156) 1-27/32 (48) 4-7/32 (107) 5-1/4 (133) 6-1/2 (166) 2 (51) 2-1/32 (52) 1-11/16 3-7/8 (98) (43) OPTIONAL PRESSURE SWITCH VALVE POSITION INDICATOR LAMPS M16865 6-9/16 (166) 1-27/32 (48) 4-7/32 (107) 5-1/4 (133) 7-5/16 (190) 2 (51) 2-1/32 (52) 1-11/16 3-7/8 (98) (43) OPTIONAL PRESSURE SWITCH VALVE POSITION INDICATOR LAMPS M16864 6-9/16 (166) 1-7/8 (48) 4-5/16 (109) 5-11/32 (136) 8-15/32 (215) 2-1/4 (57) 3 (76) 1-3/4 4-1/32 (102) (44) OPTIONAL PRESSURE SWITCH V4730C; V4734C; V8730C Accessories and Parts Material Number Description 50002653-001/U Manual Shut-Off Valve Kit (1 in. NPT or smaller valves) 854 70-6910 Venturi Mixing Unit Venturi Mixing Unit Dimensions in inches (millimeters) M22417D 8-19/32 (218) 7-7/8 (200) LG 5-1/2 (140) SM 9-9/32 DIA. (236 DIA.) LG 6-1/4 DIA. (159 DIA.) SM 1 2 1 2 1 LG (LARGE) IS VENTURI MIXING UNIT VMU500. 2 SM (SMALL) ARE VENTURI MIXING UNITS VMU150/300/335. The venturi mixing unit (VMU), combined with the V4730C/ V8730C gas valves and specific direct current (dc) fan, has been developed for modulating premix appliances like gas burners and gas boilers. • All adjustment and test points are accessible from one side. • Has a wide modulation band (14 to 100% of the boiler load). • Flexible mounting positions of gas control to venturi manifold and venturi manifold to fan. • Two stainless steel sensing tubes are provided for use with or without manual safety shutoff valve. Materials: Housing: Aluminum, Venturi: Statically dissipative statcon PF, Seals: Rubber (NBR). Ambient Temperature Range: 32°F to 212°F (0°C to 100°C) Approvals, Underwriters Laboratories Inc.: File No. MH18476 Approvals, CSA: File: Certificate No: 158158-1227192 Pipe Connection: Four M5 screws and a rubber O-ring are provided with the venturi to assemble it to the V4730C/V8730C gas valve. The stainless steel tube provided with the venturi has to be connected between the venturi inlet (connection provided) and the gas valve regulator. Longer sensing tube for use with manual safety shutoff valve (KTTBA002). Shorter sensing tube for use without manual safety shutoff valve (KTTBA001). Current Ratings: V1 Current Rating – 0.16A; V2 Current Rating – 0.16A; V1 + V2 Current Rating – 0.32A Material Number Body Pattern Maximum Safe Operating Pressure (psi) Maximum Operating Pressure (mbar) Comments Reference Load VMU150A1011 Straight flange 2.9 psi (UL approved), 1/2 psi (CSA approved) 200 mbar (UL approved), 35 mbar (CSA approved) Pressure Drop: Approximately 3.2 in. wc (800 Pa) across the venturi at reference load. The minimum load for which the system can be used is 14-17% of the reference load, which equals a minimum pressure differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas control. 150 kW (512,000 Btuh) VMU185A1084 1/2 psi (CSA approved; 2.9 psi (UL approved) 35 mbar (CSA approved), 200 mbar (UL approved) Pressure Drop: Approximately 3.2 in. wc (800 Pa) across the venturi at reference load. The minimum load for which the system can be used is 14-17% of the reference load, which equals a minimum pressure differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas control. 185 kW (632,000 Btuh) VMU300A1046 Straight flange 2.9 psi (UL approved), 1/2 psi (CSA approved) 200 mbar (UL approved), 35 mbar (CSA approved) Pressure Drop: Approximately 3.2 in. wc (800 Pa) across the venturi at reference load. The minimum load for which the system can be used is 14-17% of the reference load, which equals a minimum pressure differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas control. 300 kW (1,024,000 Btuh) VMU335A1018 Straight flange 2.9 psi (UL approved), 1/2 psi (CSA approved) 200 mbar (UL approved), 35 mbar (CSA approved) Pressure Drop: Approximately 3.2 in. wc (800 Pa) across the venturi at reference load. The minimum load for which the system can be used is 14-17% of the reference load, which equals a minimum pressure differential of 0.2 in. wc (50 Pa) of the 1:1 venturi/servo regulator gas control. 335 kW (1,143,000 Btuh) 70-6910 855 Commercial/Industrial Combustion Controls Pressure Switches C437D, E 2000 Series Gas Pressure Switches Dimensions in inches (millimeters) 1-5/16 (33.3) 1 (25.4) 6-1/2 (165.1) 7-3/4 (196.9) 2 (50.8) 45 45 7-3/8 (187.3) 1/8–27 NPT 1/2–14 NPT TAPPED FOR 1/2 IN. CONDUIT 1 2 137755 MOUNTING BRACKET (2), IN 4074BWK BAG ASSEMBLY – OPTIONAL. VENT TAPPING. REMOVE DUST-SEAL LABEL BEFORE MOUNTING. M27582 6-1/4 (159) 5/16 (8) (4) 5/8 (15.9) (4) 7-11/16 DIA. (195.3) 1/8 (3.2) 3-7/16 (87.3) 1 2 C437D, E Series 2000 Gas Pressure Switches are pressureactuated devices used in industrial gas systems for safety shutoff. Series 2000 models have snap acting MicroSwitch™ snap switches to open a circuit on pressure rise or drop. • C437 models have direct- and reverse-acting SPST (non-mercury) switching. • Models intended for lockout applications must be manually reset before resuming operation. • Models with pressure range of 1 to 26 in. wc (0.25 to 6.5 kPa) compensate for momentary surges in gas pressure with a restrictive orifice in inlet pressure channel. • Impede tampering and provide dust-resistant operation with enclosed setting. • Increase strength of control diaphragm with Buna N fiber-reinforced material. • Two Buna-N fiber-reinforced seal-off diaphragms for added reliability. • Clear glass cover allows observation of interior mechanism to aid in setting and checkout. Application: Industrial gas system applications for safety shutoff, pressure control, or differential-pressure control. Switch Operation: Manual Reset Sensor Element: BUNA N Diaphragm Materials: Case: Die-cast aluminum Approximate, Dimensions: 7 3/4 in. high x 6 1/4 in. wide x 3 7/16 in. deep (197 mm high x 159 mm wide x 87 mm deep) Operating Temperature Range: 32°F to 125°F (0°C to 52°C) Temperature Ratings: 125°F - Maximum Ambient (52°C - Maximum Ambient) Electrical Connections: Screw terminals Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive Pipe Connection: Main or High Pressure – 1/2 in. NPT internal thread; Vent or Low pressure – 1/8 in. NPT internal thread Approvals, Underwriters Laboratories Inc.: Listed: File No. MP2168, Guide No. MFHX Approvals, CSA: Certified: File No. LR1620, Guide No. 380-W-1.16 Approvals, Factory Mutual: Approved: Report No. 22018, 24127, J.I.IF4A3.AF Approvals, Swiss RE: Acceptable Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Differential Type Switching Action C437D2003/U 1 to 26 in. wc; 5.0 psi - Maximum Sustained 0.5 to 7.0 kPa; 34.5 kPa \- Maximum Sustained 1 3/4 in. wc 0.44 kPa Subtractive SPST, break on rise, non-mercury C437D2011/U 1/2 to 5 psi; 15.0 psi - Maximum Sustained 3.0 to 35 kPa; 103.4 kPa \- Maximum Sustained 1/2 psi 3.45 kPa Subtractive SPST, break on rise, non-mercury C437D2029/U 1 to 10 psi; 30.0 psi - Maximum Sustained 5.0 to 70.0 kPa; 206.8 kPa - Maximum Sustained 1 psi 6.89 kPa Subtractive SPST, break on rise, non-mercury C437E2002/U 1 to 26 in. wc; 5.0 psi - Maximum Sustained 0.5 to 7.0 kPa; 34.5 kPa \- Maximum Sustained 1 3/4 in. wc 0.44 kPa Additive SPST, Break on Fall, non-mercury C437E2010/U 1/2 to 5 psi; 15.0 psi - Maximum Sustained 3.0 to 35 kPa; 103.4 kPa \- Maximum Sustained 1/2 psi 3.45 kPa Additive SPST, Break on Fall, non-mercury C437E2028/U 1 to 10 psi; 30.0 psi - Maximum Sustained 5.0 to 70.0 kPa; 206.8 kPa - Maximum Sustained 1 psi 6.89 kPa Additive SPST, Break on Fall, non-mercury C437E2036/U 0.5 to 5.5 in. wc; 3.0 psi \- Maximum Sustained 0.1 to 1.4 kPa; 20.7 kPa \- Maximum Sustained 0.25 in. wc 0.06 kPa Additive SPST, Break on Fall, non-mercury 856 70-6910 Pressure Switches C6097 Pressure Switch Dimensions in inches (millimeters) 27/32 (22) HOLE HOUSING GAS CONNECTION 1/4 NPT WITH DUST SEAL 2-1/4 (57) 3-3/16 (81) 1-17/32 (90) 2-21/32 (68) 2-21/32 (68) 31/32 (25) 25/32 (21) 1-3/32 (28) 15/32 (12) 13/32 (11) 2-23/32 (69) 2-23/32 (69) 1-3/4 (45) 2-13/32 (61) ATMOSPHERIC PRESSURE REFERENCE PORT OR DIFFERENTIAL CONNECTION 1/8 NPT INDICATOR M29773 1 2 3 P NO NC COM TERMINAL DIAGRAM Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure systems. • For use with natural gas, liquid propane (LP) gas, or air. • Diaphragm-actuated safety-limit switch. • Switch can be wired to turn on alarm. • C6097A models break control circuit at setpoint on pressure fall. • C6097B models break control circuit at setpoint on pressure rise. • Lockout with manual reset and recycle options. • Lockout models have external manual reset button. • Removable transparent cover protects scaleplate and adjusting knob. • Pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only). • 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train. • Optional switch position indicator lamp available. • IP54 enclosure standard. • Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in. wc or 1.5 to 7 psi. • Surge orifice. • Integral vent limiter on all models. Application: Safety devices used in positive-pressure or differentialpressure systems to sense gas or air pressure changes Operating Temperature Range: -40°F to +140°F (-40°C to +60°C) Electrical Connections: Screw terminals Electrical Ratings: Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main Valve: 400 VA with 2-1/2 times inrush Contact Ratings: 120 Vac Switch Contact – 3.0 AFL, 18.0 ALR, 5.0 A resistive; 240 Vac Switch Contact – 3.0 AFL, 18.0 ALR, 5.0 A resistive Approvals, Underwriters Laboratories Inc.: Component Listed, MP 2168-8-1 Approvals, CSA: File # 95329 Certificate 2632-01 Approvals, Factory Mutual: JI 2D4A1.AF Approvals, Swiss RE: Acceptable Approvals, Others: CSD-1 AFB: Acceptable Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Differential Type Switch Operation Switching Action Approximate, Dimensions Pipe Connection Mounting C6097A1004/U 0.4 to 5 in. wc 0.10 to 1.25 kPa 0.16 in. wc Nominal; 0.24 in. wc Maximum 0.04 kPa Nominal; 0.06 kPa Maximum Additive Auto recycle Break on pressure fall 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097A1012/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint max. 0.60 kPa @ min. setpoint; max. 1.05 kPa @ max. setpoint Additive Manual Reset Break on pressure fall 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (90 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097A1020/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint max. 0.60 kPa @ min. setpoint; max. 1.05 kPa @ max. setpoint Additive Manual Reset Break on pressure fall 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (66 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097A1038/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint max. 2.5 kPa @ min. setpoint; max. 3.0 kPa @ max. setpoint Additive Manual Reset Break on pressure fall 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (90 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread 70-6910 857 Commercial/Industrial Combustion Controls Pressure Switches Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Differential Type Switch Operation Switching Action Approximate, Dimensions Pipe Connection Mounting C6097A1046/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint max. 2.5 kPa @ min. setpoint; max. 3.0 kPa @ max. setpoint: Additive Manual Reset Break on pressure fall 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (66 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097A1053/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc Nominal; 0.48 in. wc Maximum 0.06 kPa Nominal; 0.12 kPa Maximum Additive Auto recycle Break on pressure fall 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097A1061/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc Nominal; 0.48 in. wc Maximum 0.06 kPa Nominal; 0.12 kPa Maximum Additive Auto recycle Break on pressure fall 2 1/4 in. high x 2 23/32 in. wide x 2 23/32 in. deep (57 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097A1079/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc Nominal; 2.4 in. wc Maximum 0.27 kPa Nominal; 0.60 kPa Maximum Additive Auto recycle Break on pressure fall 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097A1087/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc Nominal; 2.4 in. wc Maximum 0.27 kPa Nominal; 0.60 kPa Maximum Additive Auto recycle Break on pressure fall 2 1/4 in. high x 2 23/32 in. wide x 2 23/32 in. deep (57 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097A1095/U 0.4 to 5 in. wc 0.10 to 1.25 kPa max. 0.6 in. wc @ min. setpoint; max. 0.25 in. wc @ max. setpoint max. 0.15 kPa @ min. setpoint; max. 0.25 kPa @ max. setpoint Additive Manual Reset Break on pressure fall 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (90 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097A1103/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 psi @ min. setpoint; max. 1.4 psi @ max. setpoint max. 7.6 kPa @ min. setpoint; max. 9.6 kPa @ max. setpoint Additive Manual Reset Break on pressure fall 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (66 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097A1111/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 psi @ min. setpoint; max. 1.4 psi @ max. setpoint max. 7.6 kPa @ min. setpoint; max. 9.6 kPa @ max. setpoint Additive Manual Reset Break on pressure fall 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (90 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097A1129/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal; 0.3 psi Maximum 0.69 kPa Nominal; 2.07 kPa Maximum Additive Auto recycle Break on pressure fall 2 1/4 in. high x 2 23/32 in. wide x 2 23/32 in. deep (57 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097A1137/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal; 0.3 psi Maximum 0.69 kPa Nominal; 2.07 kPa Maximum Additive Auto recycle Break on pressure fall 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097A1210/U 0.4 to 5 in. wc 0.10 to 1.25 kPa 0.16 in. wc Nominal; 0.24 in. wc Maximum 0.04 kPa Nominal; 0.06 kPa Maximum Additive Auto recycle Break on pressure fall 2 1/4 in. high x 2 23/32 in. wide x 2 23/32 in. deep (57 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097A1228/U 0.4 to 5 in. wc 0.10 to 1.25 kPa max. 0.6 in. wc @ min. setpoint; max. 0.25 in. wc @ max. setpoint max. 0.15 kPa @ min. setpoint; max. 0.25 kPa @ max. setpoint Additive Manual Reset Break on pressure fall 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (90 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread Flange Mount 858 70-6910 Pressure Switches Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Differential Type Switch Operation Switching Action Approximate, Dimensions Pipe Connection Mounting C6097B1002/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint max. 2.5 kPa @ min. setpoint; max. 3.0 kPa @ max. setpoint Subtractive Manual Reset Break on pressure rise 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (90 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097B1010/U 12 to 60 in. wc 3.0 to 15 kPa max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint max. 2.5 kPa @ min. setpoint; max. 3.0 kPa @ max. setpoint Subtractive Manual Reset Break on pressure rise 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (66 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097B1028/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint max. 0.60 kPa @ min. setpoint; max. 1.05 kPa @ max. setpoint Subtractive Manual Reset Break on pressure rise 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (90 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097B1036/U 3 to 21 in. wc 0.7 to 5.2 kPa max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint max. 0.60 kPa @ min. setpoint; max. 1.05 kPa @ max. setpoint Subtractive Manual Reset Break on pressure rise 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (66 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097B1044/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpoint max. 7.6 kPa @ min. setpoint; max. 9.6 kPa @ max. setpoint Subtractive Manual Reset Break on pressure rise 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep (66 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097B1051/U 1.5 to 7 psi 10.3 to 48 kPa max. 1.1 in. wc @ min. setpoint; max. 1.4 in. wc @ max. setpoint max. 7.6 kPa @ min. setpoint; max. 9.6 kPa @ max. setpoint Subtractive Manual Reset Break on pressure rise 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097B1069/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc Nominal; 0.48 in. wc Maximum 0.06 kPa Nominal; 0.12 kPa Maximum Subtractive Auto recycle Break on pressure rise 2 1/4 in. high x 2 23/32 in. wide x 2 23/32 in. deep (57 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097B1077/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc Nominal; 2.4 in. wc Maximum 0.27 kPa Nominal; 0.60 kPa Maximum Subtractive Auto recycle Break on pressure rise 2 1/4 in. high x 2 23/32 in. wide x 2 23/32 in. deep (57 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097B1085/U 12 to 60 in. wc 3.0 to 15 kPa 1.1 in. wc Nominal; 2.4 in. wc Maximum 0.27 kPa Nominal; 0.60 kPa Maximum Subtractive Auto recycle Break on pressure rise 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097B1093/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal; 0.3 psi Maximum 0.69 kPa Nominal; 2.07 kPa Maximum Subtractive Auto recycle Break on pressure rise 2 1/4 in. high x 2 23/32 in. wide x 2 23/32 in. deep (57 mm high x 69 mm wide x 69 mm deep) Flange Mount C6097B1101/U 1.5 to 7 psi 10.3 to 48 kPa 0.1 psi Nominal; 0.3 psi Maximum 0.69 kPa Nominal; 2.07 kPa Maximum Subtractive Auto recycle Break on pressure rise 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread C6097B1119/U 3 to 21 in. wc 0.7 to 5.2 kPa 0.24 in. wc Nominal; 0.48 in. wc Maximum 0.06 kPa Nominal; 0.12 kPa Maximum Subtractive Auto recycle Break on pressure rise 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep (81 mm high x 69 mm wide x 69 mm deep) Vent or Low pressure – 1/8 in. NPT internal thread 1/4 in. NPT internal thread 70-6910 859 Commercial/Industrial Combustion Controls Pressure and Limit Controllers L404F Pressuretrol® Controllers Provide operating control with automatic limit protection for pressure systems up to 300 psi (2068 kPa). • Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element. • Models have snap-acting switching to open or close a circuit on pressure rise. • Have adjustable differentials. • Adjustments are made by screws on top of case. • Mount using 1/4 inch -18 NPT internal pipe threads or surface mount through base of case. • Ground screw terminal. Application: Provide control of steam, air, non-combustible gases or non-corrosive fluids Differential Type: Subtractive Mounting: 1/4 inch-18 NPT internal thread connection on diaphragm assembly, 1/4 -19 BSPT internal thread on models with BSPT ground screw; or surface mount through back of case Switch Operation: Auto recycle Sensor Element: Stainless steel diaphragm standard; Brass Bellows on models with 20 to 300 psi Operating Temperature Range: -35°F to +150°F (-37°C to +66°C) Electrical Connections: Screw terminals Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive Pipe Connection - Main or High Pressure: 1/4 inch-18 NPT internal thread standard; 1/4 -19 BSPT internal thread on models with BSPT ground screw Approvals, Underwriters Laboratories Inc.: Listed: File No. MP466, Guide No. MBPR Approvals, CSA: Certified: File No. LR1620, Guide No. 400-E-O; or Certified: File No. LR95329 for Miss-wiring Compliant models Approvals, Swiss RE: Acceptable Material Number Operating Range (psi) Operating Range (kPa) Maximum Sustained Pressure (psi) Maximum Sustained Pressure (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Switching Action Includes Comments L404F1060/U 2 to 15 psi 14 to 103 kPa 25 psi 172 kPa 2 to 6 psi 14 to 41 kPa SPDT snap action, make R-W, break R-B on pressure rise L404F1078/U 5 to 50 psi 35 to 345 kPa 85 psi 586 kPa 6 to 14 psi 41 to 97 kPa SPDT snap action, make R-W, break R-B on pressure rise L404F1094/U 20 to 300 psi 138 to 2068 kPa 350 psi 2413 kPa 20 to 50 psi 138 to 345 kPa SPDT snap action, make R-W, break R-B on pressure rise L404F1102/U 10 to 150 psi 69 to 1034 kPa 225 psi 1151 kPa 10 to 22 psi 60 to 152 kPa SPDT snap action, make R-W, break R-B on pressure rise L404F1219/U 2 to 15 psi 14 to 103 kPa 25 psi 172 kPa 2 to 6 psi 14 to 41 kPa SPDT snap action, make R-W, break R-B on pressure rise BSPT ground screw and European Enclosure L404F1227/U 10 to 150 psi 69 to 1034 kPa 225 psi 1151 kPa 10 to 22 psi 60 to 152 kPa SPDT snap action, make R-W, break R-B on pressure rise BSPT ground screw and European Enclosure L404F1235/U 20 to 300 psi 138 to 2068 kPa 350 psi 2413 kPa 20 to 50 psi 138 to 345 kPa SPDT snap action, make R-W, break R-B on pressure rise BSPT ground screw and European Enclosure L404F1243/U 5 to 50 psi 35 to 345 kPa 85 psi 586 kPa 6 to 14 psi 41 to 97 kPa SPDT snap action, make R-W, break R-B on pressure rise BSPT ground screw and European Enclosure L404F1367/U 1 to 8 psi 7 to 55 kPa 25 psi 172 kPa 0.75 to 2 psi 5 to 14 kPa Snap switch breaks R-B (closes R-W) on pressure rise. Make-on devices omit terminal B. Range Stop installed at 8 PSI L404F1375/U 5 to 50 psi 35 to 350 kPa 85 psi 586 kPa 6 to 14 psi 40 to 100 kPa Snap switch makes R-W on pressure rise Miss-wiring Compliant (less B terminal) L404F1383/U 10 to 150 psi 70 to 1035 kPa 225 psi 1151 kPa 10 to 22 psi 70 to 150 kPa Snap switch makes R-W on pressure rise Miss-wiring Compliant (less B terminal) L404F1391/U 20 to 300 psi 140 to 2070 kPa 350 psi 2413 kPa 20 to 50 psi 140 to 345 kPa Snap switch makes R-W on pressure rise Miss-wiring Compliant (less B terminal) L404F1409/U 2 to 15 psi 14 to 103 kPa 25 psi 172 kPa 2 to 6 psi 15 to 40 kPa Snap switch makes R-W on pressure rise Miss-wiring Compliant (less B terminal) 860 70-6910 Pressure and Limit Controllers Dimensions in inches (millimeters) 3-3/4 (95) 1-1/16 (27) 13/16 (21) 1-3/16 (30) HOLE FOR 1/2 INCH CONDUIT DIFFERENIAL ADJUSTMENT SCREW 1-1/2 (38) 2-1/8 (54) M19635B 1-13/16 (46) 4-1/2 (115) 4-11/32 (111) 1-61/64 (50) 1-15/16 (49) 3/16 X 11/32 (5 X 9) KNOCKOUT MAIN SCALE ADJUSTMENT SCREW 1/4 –18 NPT CLEAR PLASTIC COVER 3-7/8 (99) 2-3/4 (70) 3-1/4 (83) DIMENSION "A" (SEE TAB) 1 1 1 15 TO 100 kPa (2 TO 15 PSI) SCALE MODELS ONLY. PSI RANGE 2 TO 15 5 TO 50 10 TO 150 20 TO 300 DIMENSION "A" 123 126 126 146 70-6910 861 Commercial/Industrial Combustion Controls Pressure and Limit Controllers L404T, V Oil Pressuretrol® Limit Controllers Oil pressure sensing devices for use on oil burner systems using any type of fuel oil, including heavy pretreated oils. • Clear plastic cover allows observation of the pressure settings. • Models have snap-acting switching to open or close a circuit on pressure rise. • L404T High pressure limit, break a circuit on oil pressure rise above setpoint. • L404V Low Pressure limit, makes a circuit on oil pressure rise above setpoint. • Adjustments are made by screws on top of case. • Mount using 1/4 inch -18 NPT internal pipe threads or surface mount through base of case. • Ground screw terminal. Application: Oil pressure limit switch for fuel oil, including heavy oil applications Differential Type: Subtractive Mounting: 1/4 in. NPT internal thread or surface mount through back of case Switch Operation: Auto recycle Sensor Element: Stainless Steel diaphragm Approximate, Dimensions: 4 31/32 in. high x 4 1/2 in. wide x 2 3/4 in. deep (126 mm high x 114 mm wide x 70 mm deep) Operating Temperature Range: -35°F to +150°F (-37°C to +66°C) Electrical Connections: Screw terminals Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive; Pipe Connection: Main or High Pressure – 1/4 in. NPT internal thread Approvals, Underwriters Laboratories Inc.: Listed: File No. MP2168, Guide No. MFHX Approvals, CSA: Certified: File No. LR95329 Dimensions in inches (millimeters) 3-3/4 (95) 1-1/16 (27) 13/16 (21) 1-3/16 (30) HOLE FOR 1/2 INCH CONDUIT DIFFERENIAL ADJUSTMENT SCREW 1-1/2 (38) 2-1/8 (54) M19635B 1-13/16 (46) 4-1/2 (115) 4-11/32 (111) 1-61/64 (50) 1-15/16 (49) 3/16 X 11/32 (5 X 9) KNOCKOUT MAIN SCALE ADJUSTMENT SCREW 1/4 –18 NPT CLEAR PLASTIC COVER 3-7/8 (99) 2-3/4 (70) 3-1/4 (83) DIMENSION "A" (SEE TAB) 1 1 1 15 TO 100 kPa (2 TO 15 PSI) SCALE MODELS ONLY. PSI RANGE 2 TO 15 5 TO 50 10 TO 150 20 TO 300 DIMENSION "A" 123 126 126 146 Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Switching Action Includes L404T1055/U 5 to 50 psi; 85 psi - Maximum Sustained 35 to 350 kPa; 586 kPa - Maximum Sustained 6 to 14 psi 40 to 100 kPa SPST snap-acting break on pressure rise L404T1063/U 10 to 150 psi; 225 psi - Maximum Sustained 70 to 1035 kPa; 1151 kPa \- Maximum Sustained 10 to 22 psi 70 to 150 kPa SPST snap-acting break on pressure rise L404V1087/U 10 to 150 psi; 225 psi - Maximum Sustained 70 to 1035 kPa; 1151 kPa \- Maximum Sustained 10 to 22 psi 70 to 150 kPa Snap switch makes R-W on pressure rise Miss-wiring Compliant (less B terminal) L404V1095/U 5 to 50 psi; 85 psi - Maximum Sustained 35 to 350 kPa; 586 kPa - Maximum Sustained 6 to 14 psi 40 to 100 kPa Snap switch makes R-W on pressure rise Miss-wiring Compliant (less B terminal) 862 70-6910 Pressure and Limit Controllers L4079 Pressuretrol® Limit Controllers Dimensions in inches (millimeters) 3-7/8 (98) 1/4 (6) (2-15 PSI ONLY) KNOCKOUT FOR 1/2 INCH CONDUIT (2) 6 (1/4) 4-15/16 (125) KNOCKOUT (2) FOR NO. 10 SCREW 1/4 - 18 NPT 1-1/16 (27) M22435 2-1/8 (54) 1-13/16 (46) 1-13/16 (46) 13/16 (21) 13/16 (21) 3-1/2 (89) 1-1/2 (38) 3/16 (5) 1-13/16 (46) 4-1/2 (114) (COVER) 4-3/8 (111) (CASE) 1-15/16 (49) 1-15/16 (49) High pressure limit switches. • Stainless steel diaphragm for use with steam, air, noncombustible gases and fluids non-corrosive to stainless steel. • L4079W is for Oil Applications. • Micro Switch™ snap-acting switches open automatically on pressure rise; must be manually reset. • Mount using 1/4 in. NPT female fitting on diaphragm assembly or surface mount through back of case. Mounting: 1/4 in. NPT internal thread or surface mount through back of case Sensor Element: Stainless Steel diaphragm Approximate, Dimensions: 5 in. high x 4 1/2 in. wide x 3 1/2 in. deep. (127 mm high x 114 mm wide x 89 mm deep.) Temperature Ratings: 150°F - Maximum Ambient (66°C - Maximum Ambient) Electrical Connections: Screw terminals Contact Ratings: 120 Vac Switch Contact – 9.8 AFL, 58.8 ALR; 240 Vac Switch Contact – 4.9 AFL, 29.4 ALR Pipe Connection: Main or High Pressure – 1/4 in. NPT internal thread Approvals, Underwriters Laboratories Inc.: Listed: File No. MP466, Guide No. MBPR Approvals, Swiss RE: Acceptable Material Number Application Operating Range (psi) Operating Range (kPa) Switch Operation Switching Action L4079A1035/U Provide limit control of steam, air, non-combustible gases or non-corrosive fluids 2 to 15 psi; 25 psi - Maximum Sustained 14 to 103 kPa; 172 kPa - Maximum Sustained Manual Reset SPST (two) break simultaneously on pressure rise L4079A1050/U Provide limit control of steam, air, non-combustible gases or non-corrosive fluids 10 to 150 psi; 225 psi - Maximum Sustained 69 to 1034 kPa; 1151 kPa - Maximum Sustained Manual Reset SPST (two) break simultaneously on pressure rise L4079B1033/U Provide limit control of steam, air, non-combustible gases or non-corrosive fluids 2 to 15 psi; 25 psi - Maximum Sustained 14 to 103 kPa; 172 kPa - Maximum Sustained Manual Reset SPST break on pressure rise L4079B1041/U Provide limit control of steam, air, non-combustible gases or non-corrosive fluids 10 to 150 psi; 225 psi - Maximum Sustained 70 to 1035 kPa; 1151 kPa - Maximum Sustained Manual Reset SPST break on pressure rise L4079B1058/U Provide limit control of steam, air, non-combustible gases or non-corrosive fluids 5 to 50 psi; 85 psi - Maximum Sustained 35 to 350 kPa; 586 kPa - Maximum Sustained Manual Reset SPST break on pressure rise L4079B1066/U Provide limit control of steam, air, non-combustible gases or non-corrosive fluids 20 to 300 psi; 350 psi - Maximum Sustained 140 to 2070 kPa; 2413 kPa - Maximum Sustained Manual Reset SPST break on pressure rise L4079W1000/U High oil pressure limit switch for heavy oil applications. 10 to 150 psi; 225 psi - Maximum Sustained 35 to 350 kPa; 1151 kPa - Maximum Sustained Manual Reset SPST break on pressure rise - Oil Applications 70-6910 863 Commercial/Industrial Combustion Controls Pressure and Limit Controllers L408J Vaporstat® Controllers Provide operating control and automatic high limit protection for vapor heating systems with pressures up to 4 psi (8 kPa). All models have Microswitch snap switches to open or close a circuit on a pressure rise. • Stainless steel diaphragm for use with liquids, air, noncombustible gases, ammonia, oxygen, distilled water and similar media. • Provide SPDT switching. • Clear plastic cover allows observation of the pressure settings. • Mount using hexagonal fitting with 1/4 in. NPT internal threads for direct mounting to the 14026 (steel) or 50024585-001 (brass) Steam Trap (siphon loop). • Ground Screw terminal. Application: Provide operating control and automatic limit protection for pressure systems with pressures up to 4 psi (8 kPa) Differential Type: Subtractive Mounting: 1/4 in. NPT internal thread or surface mount through back of case Sensor Element: Stainless Steel diaphragm Approximate, Dimensions: 5 1/8 in. high x 4 1/2 in. wide x 4 1/2 in. deep. (130 mm high x 114 mm wide x 114 mm deep.) Operating Temperature Range: -35°F to +150°F (-37°C to +66°C) Electrical Connections: Screw terminals Contact Ratings: 120 Vac Switch Contact – 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac Switch Contact – 5.1 AFL, 30.6 ALR, 5.0 A resistive Pipe Connection: Main or High Pressure – 1/4 in. NPT internal thread Approvals, Underwriters Laboratories Inc.: Listed: File No. MP466, Guide No. MBPR Approvals, CSA: Certified: File No. LR1620, Guide No. 400-E-O Approvals, Swiss RE: Acceptable Dimensions in inches (millimeters) 1-5/32 (29) 2-1/8 (54) 1/4 – 18 NPT 2-1/4 (57) 1-13/16 (46) 1-15/16 (49) 1-61/64 (50) 4-11/32 (110) CASE 4-1/2 (114) COVER 3-7/8 (98) 2-3/4 (70) 1-1/16 (27) 13/16 (21) 5-1/8 (130) 3-23/32 (95) 1-1/16 (27) 7/8 (22) DIA. 1-3/16 (30) 2-1/4 (57) 4-1/2 (114) M19770 3/16 (9) x 21/64 (8) KNOCKOUT (2) Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Switch Operation Switching Action Comments L408J1009/U 0 to 16 oz/in2 0 to 6.9 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPDT make R-W, break R-B on pressure rise L408J1017/U 0 to 4 psi 0 to 28 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPDT make R-W, break R-B on pressure rise L408J1025/U 0 to 16 oz/in2 0 to 6.9 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPST make on pressure rise Only Miss-wiring Compliant L408J1033/U 0 to 4 psi 0 to 28 kPa 2 to 16 oz/in2 0.9 to 6.9 kPa Auto recycle SPST make on pressure rise Only Miss-wiring Compliant 864 70-6910 Pressure and Limit Controllers L91 Proportional Pressuretrol® Controllers W R B W R B W R B PRESSURE RISE PRESSURE RISE L91A,B L91D M16597 Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases. • Use with steam, air, noncombustible gases, or other fluids noncorrosive to the brass or phos-bronze (300 psi models) bellows. • Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (10-300 psi models) or brass bellows (all other pressure range models). Application: Modulating pressure control for regulation of liquid, air, or other non-corrosive gases. Switch Operation: Modulating Operating Temperature Range: 32°F to 150°F (0°C to 66°C) Electrical Connections: Screw terminals Pipe Connection: Main or High Pressure – 1/4 in. NPT external thread Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Mounting Sensor Element Approximate, Dimensions Modulation Output L91A1037/U 0 to 15 psi; 25 psi - Maximum Sustained 0 to 103 kPa; 172 kPa - Maximum Sustained 0.5 psi 3.4 kPa optional surface mount through back of case Brass bellows 6 7/8 in. high x 4 1/2 in. wide x 2 7/8 in. deep (175 mm high x 114 mm wide x 73 mm deep) Single potentiometer, 140 ohms L91A1052/U 5 to 150 psi; 225 psi - Maximum Sustained 34 to 1034 kPa; 1151 kPa - Maximum Sustained 5 psi 34 kPa optional surface mount through back of case Brass bellows 5 3/4 in. high x 4 1/2 in. wide x 2 3/4 in. deep (146 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 140 ohms L91A1078/U 10 to 300 psi; 325 psi - Maximum Sustained 69 to 2068 kPa; 2241 kPa - Maximum Sustained 12 psi 83 kPa optional surface mount through back of case Phos-bronze bellows 6 1/16 in. high x 4 1/2 in. wide x 2 3/4 in. deep (154 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 140 ohms L91A1136/U 10 to 300 psi; 325 psi - Maximum Sustained 69 to 2068 kPa; 2241 kPa - Maximum Sustained 12 psi 83 kPa optional surface mount through back of case Phos-bronze bellows 6 1/16 in. high x 4 1/2 in. wide x 2 3/4 in. deep (154 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 140 ohms L91B1035/U 0 to 15 psi; 25 psi - Maximum Sustained 0 to 103 kPa; 172 kPa - Maximum Sustained 1.5 to 12 psi 10 to 83 kPa optional surface mount through back of case Brass bellows 6 7/8 in. high x 4 1/2 in. wide x 2 7/8 in. deep (175 mm high x 114 mm wide x 73 mm deep) Single potentiometer, 140 ohms L91B1050/U 5 to 150 psi; 225 psi - Maximum Sustained 34 to 1034 kPa; 1151 kPa - Maximum Sustained 5 to 23 psi 35 to 160 kPa optional surface mount through back of case Brass bellows 5 3/4 in. high x 4 1/2 in. wide x 2 3/4 in. deep (146 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 140 ohms L91B1068/U 10 to 300 psi; 325 psi - Maximum Sustained 69 to 2068 kPa; 2241 kPa - Maximum Sustained 28 to 110 psi 193 to 758 kPa optional surface mount through back of case Phos-bronze bellows 6 1/16 in. high x 4 1/2 in. wide x 2 3/4 in. deep (154 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 140 ohms L91B1100/U 5 to 150 psi; 225 psi - Maximum Sustained 0 - 1 MPa; 1151 kPa - Maximum Sustained 5 to 23 psi 35 to 160 kPa 1/4 in BSP-TR thread Mounting Brass bellows 5 3/4 in. high x 4 1/2 in. wide x 2 3/4 in. deep (146 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 135 ohms L91B1118/U 10 to 300 psi; 325 psi - Maximum Sustained 0 - 2 MPa; 2241 kPa - Maximum Sustained 28 to 110 psi 193 to 758 kPa 1/4 in BSP-TR thread Mounting Phos-bronze bellows 6 1/16 in. high x 4 1/2 in. wide x 2 3/4 in. deep (154 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 140 ohms L91B1241/U 10 to 300 psi; 325 psi - Maximum Sustained 69 to 2068 kPa; 2241 kPa - Maximum Sustained 12 to 48 psi 85 to 330 kPa optional surface mount through back of case Phos-bronze bellows 6 1/16 in. high x 4 1/2 in. wide x 2 3/4 in. deep (154 mm high x 114 mm wide x 70 mm deep) Single potentiometer, 140 ohms L91D1015/U 0 to 15 psi; 25 psi - Maximum Sustained 0 to 103 kPa; 172 kPa - Maximum Sustained 1.5 to 12 psi 10 to 83 kPa optional surface mount through back of case Brass bellows 6 7/8 in. high x 4 1/2 in. wide x 2 7/8 in. deep (175 mm high x 114 mm wide x 73 mm deep) Dual potentiometer, 140 ohms L91D1031/U 5 to 150 psi; 225 psi - Maximum Sustained 34 to 1034 kPa; 1151 kPa - Maximum Sustained 11 to 52 psi 76 to 359 kPa optional surface mount through back of case Brass bellows 5 3/4 in. high x 4 1/2 in. wide x 2 3/4 in. deep (146 mm high x 114 mm wide x 70 mm deep) Dual potentiometer, 140 ohms 70-6910 865 Commercial/Industrial Combustion Controls Pressure and Limit Controllers Dimensions in inches (millimeters) M29781 L91A,B,D ALL OTHER MODELS 10 TO 300 PSI 0 TO 15 PSI 0 TO 16 OZ/IN 2 1/4-18 NPT DIM A (SEE TABULATION TABLE) DIM B (SEE TABULATION TABLE) DIM C (SEE TABULATION TABLE) 1 2 2 3 4 1 2 3 4 4-1/2 (114.3) (COVER) (110.3) (CASE) 3-57/64 (98.8) 3-13/32 (86.5) (29.4) (27.8) (46.0) (53.5) (69.9) (30.2) 1-1/16 1-3/16 (27.0) (98.4) (22.2) 4-11/32 (52.8) (94.5) (2) EXTERNAL THREADS ON 0 TO 15 PSI MODELS; INTERNAL THREADS ON ALL OTHER MODELS. SOME MODELS ARE ALSO AVAILABLE WITH 1/4-19 BSP-TR INTERNAL THREADS; SEE TABLE 1. PROPORTIONING RANGE ADJUSTING SCREW ON L91B,D MODELS ONLY. 33312B KNURLED ADJUSTMENT SCREW KNOB, 7/8 IN. \[22.2 MM\] DIAMETER,. KNOB IS INCLUDED WITH 10 TO 300 PSI \[0.07 TO .07 MPa\] MODELS; OPTIONAL ACCESSORY FOR OTHER MODELS. FOR 10 TO 300 PSI \[0.07 TO 2.07 MPa\] MODELS. DIM C INCLUDES THE KNURLED ADJUSTMENT KNOB. TABULATION OF DIMENSIONS A, B, AND C OPERATING RANGE DIM A DIM B DIM C CUSTOMARY UNITS METRIC UNITS IN. MM IN. MM IN. MM 0 TO 15 PSI 5 TO 150 PSI 10 TO 300 PSI 0 TO 103 kPa 0.03 TO 1.03 MPa 0.07 to 2.07 MPa 2-7/16 1-5/8 1-1/4 61.9 41.3 31.8 1-7/32 13/16 5/8 31.0 20.6 15.9 6-7/8 5-3/4 6-1/16 174.6 146.1 154.0 1-5/32 1-3/32 1-13/16 2-1/8 3-7/8 2-3/4 7/8 2-5/64 3-23/32 13/16 (20.1) 1-1/16 (27.0) 4 4 866 70-6910 Pressure and Limit Controllers P7810 Pressure Control Line voltage pressure controller that provides automatic operating control, automatic limit protection, manual reset limit protection, and 4-20 mA modulating firing rate control for pressure systems up to 300 psi. • May be used with steam, air, non-combustible gases or fluids that will not corrode the pressure sensing element. • Models available in 15, 150, 300 psi maximum setpoints. • LED indicators show limit function/lockout. • Reset function easily accessible under cover. • Clear cover allows setpoint and differentials to be read (but not adjusted) without opening the cover. Application: On-off, Modulate and Limit Control Sensor Element: Stainless Steel, solid state sensor Materials: Case: Plastic Approximate, Dimensions: 5 1/4 in. high x 4 21/32 in. wide x 3 3/8 in. deep (133 mm high x 119 mm wide x 86 mm deep) Voltage: 120 Vac Frequency: 50 Hz; 60 Hz Power Consumption: 3.6 W, 4.7 VA @ 50Hz; 3.3 W, 4.0 VA @ 60 Hz Operating Temperature Range: 32°F to 140°F (0°C to +60°C) Operating Humidity Range (% RH): 5 to 95% RH, non-condensing Electrical Connections: Screw terminals Contact Ratings: 120 Vac Switch Contact – 9.8 AFL, 58.8 ALR, 10.0 A resistive Pipe Connection: Main or High Pressure – 1/2 in. NPT internal thread Approvals, Underwriters Laboratories Inc.: Listed: File No. MP268, Guide No. MCCZ Approvals, CSA: Certified: File No. LR95329-6 Approvals, Factory Mutual: Approved: Report No. J.I.2D3A6AF Modulation Output: 4 mA to 20 mA Dimensions in inches (millimeters) RESET PRESSURETROL¨ 1/4 (6) 2x1-5/8 (41) 1-5/8 (41) 2-5/8 (67) 3-7/32 2x5-1/4 (133) (82) 2-17/32 (64) 3-3/8 (86) 5-1/4 (133) 2x 3-3/16 (81) 2-1/8 (55) 4-23/32 (120) 2x27/32 (22) DIAMETER 5-29/32 (150) 4-21/32 (119) 2-5/8 (67) 4 (102) 4-3/4 (120) 3/8 (10) 7/8 (22) 1 1 1 DIMENSIONS WITH DOOR IN OPEN POSITION. M23225 2 2 PIPE THREAD IS 1/4 INCH NATIONAL PIPE THREAD FOR P7810A,B; 1/2 INCH NATIONAL PIPE THREAD FOR P7810C,D. 3 3 3 WIRING COMPARTMENT ACCESS COVER. Material Number Operating Range (psi) Operating Range (kPa) Differential Pressure Range (psi) Differential Pressure Range (kPa) Switching Action P7810C1000/U 0 to 15 psi; 22.5 psi - Maximum Sustained 0 to 103 kPa; 155 kPa - Maximum Sustained 2 to 10 psi 14 to 69 kPa Break on pressure rise P7810C1018/U 0 to 150 psi; 225 psi - Maximum Sustained 0 to 1034 kPa; 1151 kPa - Maximum Sustained 5 to 20 psi 35 to 135 kPa Break on pressure rise P7810C1026/U 0 to 300 psi; 450 psi - Maximum Sustained 0 to 2068 kPa; 3103 kPa - Maximum Sustained 15 to 50 psi 103 to 340 kPa Break on pressure rise 70-6910 867 Commercial/Industrial Combustion Controls Pressure and Limit Controllers Pressure Controls and Limits Accessories Material Number Description Used With 106729/U C437, C637 Glass Lens, 6" diameter C437, C637 129178E/U Cover Assembly L404, L604 137632/U C437, C637 Paper Lens Gasket C437, C637 139870/U C437, C637 Lens Gasket for Rainproof Models C437, C637 139870A/U Glass lens with rubber gasket for NEMA 3 C437 and C637. C437, C637 14026/U Steam Trap “Black Iron Siphon Loop” for L404, L408, L91 or P7810A, B L404, L91, L604 209731A/U 1/2 in. NPT Brass Siphon Loop for P7810C, D P7810C, P7810D 23176CB/U L91 Potentiometer - 135 ohm L91 23176CF/U L91 Potentiometer - 135 ohm L91 32003039-001/U C6097 Lamp Kit, Position Indication C6097 32003040-001/U C6097 Cover, Recycle Model C6097 32003041-001/U C6097 Cover, Manual Reset Model C6097 4074BWJ/U Pressure Control/Limits, Limit Stop Assembly - to limit setpoint. Includes 129564 Range Stop, 107194 Range Stop Screw and 23466 Wrench. L404, L604, L91, L4079 50024585-001/U Steam Trap “1/4 in. NPT Brass Siphon Loop” for L404, L408, or L91 L404, L91, L604 868 70-6910 Modernization and Replacement RM7895 On-Off Primary Control with Prepurge Microprocessor-based integrated primary burner control for automatically fired gas, oil, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting • Subbase, amplifier, and prepurge timer are required for operation • Options include PC interface using ModBus™, keyboard display module, Data ControlBus™ Module, remote display module and firstout expanded annunciator • Five LEDs provide sequence information • Interchangeable plug-in flame amplifiers • Optional local or remote annunciation of operation and fault information • Nonvolatile memory retains history files and sequencing status after power loss • Optional remote reset capability • Optional report generation using Modbus™ • Selectable relight or lockout on loss of flame • Airflow switch check Honeywell RA890, R4795, R7795 All 120 V models. Fireye M-Series IMPORTANT: For on-off, gas-fired systems, some authorities having jurisdiction prohibit the wiring of any limit or operating contacts in series with the main fuel valve(s). DIRECTIONS: 1\. Disconnect all power to programmer. 2\. Remove old programmer from subbase (trade-in to Honeywell Authorized Flame Safeguard Distributor). 3\. Mark all wires on subbase; i.e., wires connected to terminal “1” should be marked “1.” Disconnect wires as they are marked. 4\. Remove old subbase. 5\. Mount Q7800A Subbase. 6\. Connect wires to subbase per attached cross reference. Pay close attention to footnotes. For example: to convert a Fireye UVM-2 to a RM7895, the wire marked “A” would connect to terminal #9 on the Q7800. The wire marked “8” would connect to Q7800 terminal #8. 7\. A superscript letter, such as “a” designates a footnote. Study these footnotes carefully. 8\. Plug in the RM7895. Make sure you select the proper ST7800A Purge Timer and Detector for the application. 9\. There are 2 wires on the amplifier section of the RM7895, which are used to select the desired trial for ignition timing and mode (lock-out or recycle). Refer to the RM7895 instruction sheet (form 66-1090) for assistance with proper selection. 10\. If a low voltage controller is used on the RA890 or UVM-1, remove it and replace it with a line voltage controller. The line voltage controller should be connected in series with the limits. 11\. If a low voltage airflow switch is used on the RM7895, it must be replaced with a line voltage airflow switch. 12\. The following models are recommended for replacements: Honeywell Device to be Replaced Replace With Amplifier RA890E, F RM7895A R7847A RA890G RM7895A R7849A R4795A, D/W-R7290 AMP RM7895A R4795A, D/W-R7289 AMP RM7895B R7847A R7795A RM7895A R7849 R7795B RM7895A R7847 R7795C RM7895C R7849 R7796D RM7895C R7847 R4140P RM7895C R7847A or R7849A R4140Y RM7895A Fireye Device to be Replaced Replace With Amplifier TFM1, 2, 3H RM7895A R7847A UVM1, 2, 3, 3H R7849A UVM5 RM7895C R7849A CONVERSION CHART FOR RM7895 120 VOLT ONLY Q7800 TERMINAL L1 L2 3 4 6 7 8 9 10 21 F G Programmer to be Converted RA890 (All) 1a 2 c b, d 6 b 3d 5 4 — F G R4795 (All) a 2 c 8, 7 1 6b 3 5 4 — F G R7795A, B L1 L2 9 8 16 3 5 6 18 — F G R7795C, D L1 L2 9 8 16 3 5 6 18 7 F G R4140P L1 L2 A M 3 P 5 7 — 6 S1 S2 R4140Y L1 L2 9 8 4 3 6 7 5 — Fe G Fireye: UVM/TFM (All models)/MII 1 1 A 8 7 6 3 5 4 — S2f S1 UVM-1 (Prior to 1968) a 2 A b, d 1 b 3 5 4 — Sf S UVM-2 (Prior to 1968), All others a 2 A 8 1 6 3 5 4 — Sf S a Connect power to terminal L1. b If no airflow switch is used, jumper Q7800 terminal 6 to 7. c Replace low voltage alarm (if used) with line voltage alarm. Connect alarm directly to Q7800 terminal 3. d On power burners, identify burner motor wire on terminal 3 and connect it to Q7800 terminal 4. e Select amplifier to match detector being used. f On UVM models, the detector must be changed to a Honeywell C7027 or C7035. 70-6910 869 Commercial/Industrial Combustion Controls Electromechanical Burner Controls RA890F Protectorelay™ Primary Control Primary control provides solid state, electronic flame safeguard protection for industrial and commercial single or dual fuel burners for rectification type flame detection. • Uses rectification principle of electronic flame detection. • Replaces RA890E in most applications and mounts on same Q270A1024 Subbase. • Recycles if flame signal lost while in Run. Failure to establish pilot results in a lockout. • Safe-start check prevents start-up if flame-simulating failure occurs in flame detector circuit. • Includes built-in protection against ignition crossover in flame rod systems. • Includes SPDT alarm contacts. • Solid state circuitry. • Mounts and removes easily through use of captive mounting screws. • Mounting base is made of strong thermoplastic. Application: Primary control for rectification application (Flame Rod for example) Frequency: 50 Hz; 60 Hz Temperature Range: 60 Hz models -20°F to +115°F, 50 Hz models -20°F to +105°F (50 Hz Models -29°C to +41°C, 60 Hz Models -29°C to +46°C) Approximate, Dimensions: 5 in. high x 5 in. wide x 4 3/4 in. deep (including subbase) (127 mm high x 127 mm wide x 121 mm deep (including subbase)) Approvals, Underwriters Laboratories Inc.: UL Listed: 120V models only; File No. MP268, Guide No. MCCZ Approvals, CSA: CSA Certified: 120V models only; File No. LR1620 Approvals, Factory Mutual: Approved: Report No. 17678, 19417, 19784 Material Number Voltage Flame Failure Response Time (sec) Alarm Relay Switching Safety Switch Timing Description RA890F1270/U 120 Vac 0.8 sec SPDT 15 seconds Rectification, with alarm contacts RA890F1288/U 120 Vac 3.0 sec SPDT 15 seconds Rectification, with alarm contacts RA890F1296/U 208 Vac 3.0 sec SPDT 15 seconds Rectification, with alarm contacts RA890F1304/U 220 Vac 0.8 sec SPDT 15 seconds Rectification, with alarm contacts RA890F1338/U 120 Vac 0.8 sec SPDT 30 seconds Rectification, with alarm contacts RA890F1346/U 120 Vac 3.0 sec SPDT 30 seconds Rectification, with alarm contacts RA890F1387/U 240 Vac 3.0 sec SPDT 15 seconds Rectification, with alarm contacts RA890F1478/U 120 Vac 0.8 sec SPDT 15 seconds Rectification, with alarm contacts, fast safe start check. RA890G Protectorelay™ Primary Control Primary control provides solid state, electronic flame safeguard protection for industrial and commercial single or dual fuel burners applications using Ultraviolet flame detectors. • Design for interrupted ignition with intermittent pilot on gas burners, and interrupted or intermittent ignition on oil burners. • Use with a C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector for flame sensing. • Recycles if flame signal lost while in Run. Failure to establish pilot results in a lockout. • Safe-start check prevents start-up if flame-simulating failure occurs in flame detector circuit. • Includes SPDT alarm contacts. • Solid state circuitry, eliminates warm-up and increases resistance to vibration. • Mounts and removes easily through use of captive mounting screws. • Mounting base is made of strong thermoplastic. Application: Either a line or low voltage controller can be used Frequency: 50 Hz; 60 Hz Temperature Range: 60 Hz models -20°F to +115°F, 50 Hz models -20°F to +105°F (50 Hz Models -29°C to +41°C, 60 Hz Models -29°C to +46°C) Approximate, Dimensions: 5 in. high x 5 in. wide x 4 3/4 in. deep (including subbase) (127 mm high x 127 mm wide x 121 mm deep (including subbase)) Approvals, Underwriters Laboratories Inc.: UL Listed: 120V models only; File No. MP268, Guide No. MCCZ Approvals, CSA: CSA Certified: 120V models only; File No. LR9S329 Approvals, Factory Mutual: Approved: Report No. 22013 Material Number Voltage Flame Failure Response Time (sec) Alarm Relay Switching Safety Switch Timing Description RA890G1229/U 120 Vac 0.8 sec SPDT 15 seconds Ultraviolet, with alarm contacts RA890G1245/U 220 Vac 0.8 sec SPDT 15 seconds Ultraviolet, with alarm contacts RA890G1260/U 120 Vac 3.0 sec SPDT 15 seconds Ultraviolet, with alarm contacts RA890G1286/U 240 Vac 3.0 sec SPDT 15 seconds Ultraviolet, with alarm contacts Q270 Wiring Mount Base Application: Wiring Mounting Base for RA890, R4795 Material Number Description Used With Q270A1024/U Wiring Mounting Base for RA890, R4795 RA890, R4795 870 70-6910 Testers and Demonstrators A7800 Tester Provides quick operational check of the 7800 SERIES System components. • Allows testing different 7800 SERIES devices using configuration plugs and functional switches to simulate interlocks and control functions. • Indicator lamps represent outputs as activated. Application: Tester Voltage: 120 Vac Frequency: 50 Hz; 60 Hz Temperature Range: -30°F to +150°F (-34.5°C to +65°C) Material Number Required Components Includes Used With A7800A1010/U Configuration Plugs, Included Configuration Plugs 7800 SERIES Relay Modules with Valve Proving System or New Optical Detector Amplifiers A7800 and DSP2672 Replacement Parts Material Number Application Used With Comments 203579A/U Tester; DSP2672 RM7800/40/45 (non VPS side) Configuration Plug RM7800; RM7840 Configures A7800 and DSP2672 203579B/U Tester; DSP2672 RM7838A Configuration Plug Configures A7800 and DSP2672 203579C/U Tester; DSP2672 RM7838B, C Configuration Plug Configures A7800 and DSP2672 203579D/U Tester; DSP2672 RM7885A Configuration Plug Configures A7800 and DSP2672 203579E/U Tester; DSP2672 RM7890 (non VPS models) Configuration Plug Configures A7800 and DSP2672 203579F/U Tester; DSP2672 RM7895, 96, 97, 98 (non VPS side) Configuration Plug Configures A7800 and DSP2672 203579G/U Tester; DSP2672 RM7823 Configuration Plug Configures A7800 and DSP2672 203579H Tester; DSP2672 RM7865 Configuration Plug Configures A7800 and DSP2672 203579J/U Tester; DSP2672 RM7838B, C (VPS) Configuration Plug A7800A1010 Tester Configures A7800 and DSP2672 203579K/U Tester; DSP2672 RM7890 (VPS) Configuration Plug A7800A1010 Tester 203579L/U Tester; DSP2672 RM7800/40G,L (VPS side) Configuration Plug A7800A1010 Tester 203579M/U Tester; DSP2672 RM7898 (VPS Side) Configuration Plug A7800A1010 Tester 70-6910 871 Commercial/Industrial Combustion Controls Testers and Demonstrators Demonstrators or Trainers DSP3452 DSP3981 DSP3956 DSP3564U The DSP3452 is designed for training and demonstration of Honeywell Burner and Boiler Controls with auxiliary devices that are typically used with commercial and industrial burners. It demonstrates the wiring and operation of primary safety controls. • The trainer can be used with Honeywell primary controls or programming controls (not included with the trainer). • The nine trouble switches simulate a range of faults from a burned out pilot valve to a faulty flame detector to an inoperative firing rate motor. • The trainer measures 20 1/2 in. x 32 in. x 12 1/2 in. It weighs approximately 30 lbs. Color: Black Material Number Application Voltage Frequency Approximate, Dimensions Required Components Includes Used With Comments DSP3452/U Primaries, Programmers or 7800 Series Trainer 120 Vac 50 Hz; 60 Hz 20 1/2 in. x 32 in. x 12 1/2 in. Devices for wiring and training jumper wires, propane gas hose with regulator, detector mounting adapters Primaries, Programmers and 7800 SERIES Relay Modules Complete Flame Safeguard Training Package DSP3564/U ControlLink FAR Trainer/Demonstrator 120 Vac 50 Hz; 60 Hz Relay Module, R7999 Control and 3 ML Motors; Relay Module, R7999 Control and 4 ML Motors ControLinks Fuel Air Ratio controls DSP3956/U ControLink FAR Configuration Toolkit ZM Software; USB-485 Converter with cable and Connector for Controlinks ControLinks Fuel Air Ratio controls DSP3981/U For Controlinks Configuration and Monitoring 120 Vac 50 Hz; 60 Hz ControLinks Fuel Air Ratio controls With S7999D Touchscreen for FAR Monitoring or Programming SOLA Demonstrators The DSP3943 is used as a SOLA commissioning or monitoring tool when a System or Local Operator Interface is not required for operation. The DSP contains the S7999B1026 touchscreen display which uses a wizardlike process to assist you through the commissioning process. The DSP3980 contains an S7999D1006 Touchscreen Display to commission or monitor the SOLA system when a System or Local Operator Interface is not required for operation. The DSP3980 includes the power supply for operation and cable with connector for the SOLA system. A USB storage drive is provided to save display screen snapshots or trending information. Voltage: 120 Vac Color: Black Material Number Application Frequency Includes Used With Comments DSP3943/U Demonstrator, SOLA 60 Hz S7910A1001 SOLA HC; S7999 Touchscreen Display; S7910 Keyboard display, system switches and ports DSP3980/U Demonstrator 50 Hz; 60 Hz SOLA Controls Touchscreen for R7910/R7911 SOLA Monitoring or Programming 872 70-6910 Testers and Demonstrators Flame Simulator Flame simulators simplify the troubleshooting of flame safeguard controls by providing a quick method to check the flame detection function. Material Number Application Color Comments Used With 123514A/U Flame Simulator, Rectification Flame Amplifiers Brown Applications with test jack in G circuit R4075B; R4181A; R4138A, B; R7253A; R8169B; R7257A; R7247A; R7847A 203659/U Simulates C7027, C7035, C7044 Flame Simulators for 7800 SERIES Purple Simulates Minipeeper Flame Detectors 7800 SERIES Relay modules FSP1535 Tester Provides quick operational check of Honeywell RA890 or R4795 nonprogramming primary controls. • Includes indicator lights that visually represent functions of ignition, pilot and main valve as unit simulates system operation. • Eliminates need to operate entire system. • Tests units with rated voltage from 100 to 240, 50/60 Hz by connecting line cord to the rated voltage. Voltage: 120 Vacor 240 Vac Frequency: 50 Hz; 60 Hz Material Number Application Used With FSP1535/U Tester RA890; R4795 FSP5004 Tester A Tester that provides quick operational check of most Honeywell BC7000, R4140, R7140 and R4150 programmers and R7795 primary controls (order 198355A adapter separately). • Includes indicator lights that visually represent control functions of programmer as unit simulates system operation. • Works with 120 Vac, 60 Hz controls. • Use to test some Gordon-Piatt programmers. • Cannot be used to test some R4140 and R4150 models due to design or wiring differences. Reference the list at right to see if you have one of the controls that CANNOT be tested. If you do, check these out using the instructions provided in their respective instruction manuals. • R4150/R4140/BC7000/R7795/R7140 Tester (120V only). Provides a quick operational check. Voltage: 120 Vac Frequency: 50 Hz; 60 Hz Material Number Application Comments Used With FSP5004/U Tester DO NOT USE WITH: BC7000L1018, BC7000L1034, BC7000L1063; R4140D1004, R4140E1001, R4140M1079, or non-120 Vac R4140 models BC7000; R4140; R7795; R7140 70-6910 873 Industrial Flame Monitoring Signal Processors P531; P532 3-channel, Signal Processors The P532/P531 supports three separate viewing heads, two S55XBE and one S70X. Independent 2 x SPDT Flame On relay contacts are provided for each viewing head (6 total). 0-20 or 4-20mA scalable analog output also provided for each viewing head. SIL 3 capable. • 3 channels. • Two SPDT flame relay outputs, one SPDT self-check relay output and one N.O. alarm relay output per channel. • FM and CSA approved. • Monitor the UV and IR flame component simultaneously or separately when using the S550B/BE. • Monitor 3 viewing heads simultaneously. • Independent configuration for each viewing head. • 2 sets of configuration data per viewing head. • Viewing head temperature indication. • Automatic set-up functionality. • Automatic viewing head detection. • Modbus and RS422 protocol compatible. • NEMA 1 Enclosure Rated. Output: 4-20mA Communications: ModBus and RS422 Compatible Mounting: Cabinet mounting tabs Connection Type: Removable terminals Dimensions: 4.3 in. wide x 5.8 in. deep x 5.5 in. high (109 mm wide x 147 mm deep x 117 mm high) Approvals, CSA: Approved (Temperature Range -40 to 158°F; -40 to 70°C) Approvals, Factory Mutual: Approved (Temperature Range -40 to 158°F; -40 to 70°C) Used With: S550BE, S552BE, S556BE, S70X, S80X viewing heads Material Number Description Application Keypad Status Monitoring Electrical Ratings Frequency Required Components P531AC AC Signal Processor Signal Processor with 3 channels without keypad Use KP532U keypad LEDs 85-264 Vac + 24 Vdc backup 50 Hz; 60 Hz Appropriate Flame Detector P531DC DC Signal Processor Signal Processor with 3 channels without keypad Use KP532U keypad LEDs 22-26 Vdc+ 24 Vdc backup Appropriate Flame Detector P532AC AC Signal Processor Signal Processor with 3 channels and keypad Integrated tri-color display 85-264 Vac + 24 Vdc backup 50 Hz; 60 Hz Appropriate Flame Detector P532DC DC Signal Processor Signal Processor with 3 channels and keypad Integrated tri-color display 22-26 Vdc+ 24 Vdc backup Appropriate Flame Detector P532UI Program module/keypad used with the P531 Program module/keypad used with the P531 600U Flame Rod Signal Processor Model 600 Ultra Flame Rod is a reliable Flame Detecting system based on the proven principle of measuring rectified current flow through a flame rod when a flame touches it. The Model 600 Flame Detector measures the rectified current and closes the flame relay if the current exceeds the value for the flame-on set-point. Output: 175 Vac for flame rod Mounting: DIN rail, 35mm Connection Type: Removable terminals Dimensions: 2-63/64 in. wide x 3-1/4 in. deep x 5-31/64 in. high (76 mm wide x 83 mm deep x 139 mm high) Used With: Flame Rod Material Number Description Application Keypad Status Monitoring Electrical Ratings Frequency 600U Flame rod signal processor with DPDT flame relay contacts, DPST ignition transformer relay or ignition coil drive Flame rod signal processor Integrated LEDs 85 to 132Vac or 170 to 264Vac 50 Hz; 60 Hz 874 70-6910 Signal Processors P522 Signal Processor with 2 Channels and Keypad The P522 supports two switched (not simultaneously) S55XBE viewing heads. 2 x SPDT Flame On relay contacts and 0-20 or 4-20mA scalable analog output is also provided. SIL 3 capable. • 2 channels. • Integrated keypad. • Two SPDT flame relay outputs and one SPDT self-check relay output. • FM and CSA approved. • Flame failure response and time delay on set-up. • Connect 2 viewing heads, monitoring 1 at a time. • Independent configuration for each viewing head. • 2 sets of configuration data per viewing head. • Viewing head temperature indication. • Modbus and RS422 protocol compatible. • NEMA 1 Enclosure Rating. Application: Signal Processor with 2 channels and keypad Keypad: Integrated Status Monitoring: LEDs Output: 4-20mA Communications: ModBus and RS422 Compatible Mounting: Cabinet mounting tabs Connection Type: Removable terminals Dimensions: 4.3 in. wide x 6.4 in. deep x 6.7 in. high (109 mm wide x 162 mm deep x 170 mm high) Approvals, CSA: Approved Approvals, Factory Mutual: Approved (Temperature Range -32 to +122°F; 0 to +50°C) Material Number Description Electrical Ratings Frequency Used With Required Components P522AC AC Signal Processor 85-264 Vac + 24 Vdc backup 50 Hz; 60 Hz S550B/BE, S552B/BE, S556B/ BE viewing heads Appropriate Flame Detector P522DC DC Signal Processor 22-26 Vdc+ 24 Vdc backup S550B/BE, S552B/BE, S556B/ BE viewing heads Appropriate Flame Detector WATCHDOGIII Flare Stack Signal Processor The P222 is used with S256 viewing head for remote monitoring of flare flame. 2 x SPDT Flame On relay contacts for T1 timer and 1 x SPDT for T2 timer. 0-20 or 4-20mA scalable analog output is also provided. Two timers are included for flame delay off settings one 0 to 60 seconds (T1) and one 0 to 3600 seconds (T2). Application: Flare Stack signal processor with 1 channel and keypad Keypad: Integrated Status Monitoring: LEDs Output: 0/4-20mA Communications: ModBus and RS422 Compatible Mounting: Cabinet mounting tabs Connection Type: Removable terminals Dimensions: 4.3 in. wide x 6.4 in. deep x 6.7 in. high (109 mm wide x 162 mm deep x 170 mm high) Approvals, QPS: Approved Material Number Description Electrical Ratings Frequency Used With Required Components P222 Watchdog Signal Processor 85-264 Vac + 24 VDC backup 50 Hz; 60 Hz S256 WATCHDOGIII flare stack viewing head Appropriate Flame Detector WATCHDOGIII Kit consisting of P222 processor, S256B Viewing Head, 10-ft. C328 cable, quick disconnect plug. 85-264 Vac 50 Hz; 60 Hz 70-6910 875 Industrial Flame Monitoring Signal Processors S256B Flare Stack Viewing Head S256B is a UV flare stack viewing head/flame detector, that detects the presence or absence of flame at the flare stack tip. Used for continuous UV flare stack monitoring to ensure no unburned toxic or waste gas releases into the atmosphere. • Not adversely affected by Gamma Rays or X-Rays. • Solar blind. • Ground mounted, up to 1000 feet away from flare stack tip. • UV gain selection of 0-99. • Digital display. • Quick disconnect plug. • Easy to install with no plant shutdown. • NEMA 4X / IP67 enclosure rating. • Ambient temperature: -40°F to +140°F (-40°C to +70°C). • 22-26 VDC supplied by signal processor. • Used with P222 signal processor. Application: Flame Detector for use with P222 processor NEMA Rating: 4X Electrical Connections: Quick disconnect plug Mounting: 2" Pipe mount Electrical Ratings: 22 to 26Vdc from signal processor Dimensions: 3.7 in. wide x 20.3 in. deep x 13.7 in. high (94 mm wide x 516 mm deep x 348 mm deep) Ambient Temperature Range: -40 to 140°F (-40 to 60°C) Approvals, QPS: QPS to CSA 22.2 Environmental, Electrical, or Ingress Protection Rating: IP67 Comments: One color monitoring Used With: P222 Processor Material Number UV Gain Adjustment IR Gain Adjustment Digital Displays Description S256B 0-99 Yes (1) UV viewing head for use with P222 700 Signal Processor with 1 Channel The 700 supports one UV or IR viewing head model S70X or S80X. 2 x SPDT Flame On relay contacts and 0-20 or 4-20mA scalable analog output is also provided. SIL 3 capable. • 1 channel. • Two SPDT flame relay outputs and one SPDT self-check relay output. • FM and CSA approved. • Status LEDs. • DIN rail mounting. • Modbus and RS422 protocol compatible. • NEMA 1 Enclosure Rating. Application: Signal processor with 1 channel and keypad Status Monitoring: LEDs Output: 4-20mA Communications: ModBus and RS422 Compatible Mounting: DIN rail Connection Type: Removable terminals Dimensions: 2.9 in. wide x 3.3 in. deep x 5.5 in. high (74 mm wide x 84 mm deep x 140 mm high) Approvals, CSA: Approved Approvals, Factory Mutual: Approved (Temperature Range 32 to 140°F; 0 to 60°C) Material Number Description Keypad Electrical Ratings Frequency Used With Required Components 700ACSP AC Signal Processor Integrated 85-264 Vac 50 Hz; 60 Hz All models of S702, S706, S802, S806 viewing heads Appropriate Flame Detector 700DCSP DC Signal Processor Integrated 22-26 Vdc All models of S702, S706, S802, S806 viewing heads Appropriate Flame Detector 876 70-6910 All-in-One Viewing Head and Processor All-in-One Viewing Head and Processor U2-101x and U2-101x PF are integrated viewing head and processor (All in One) with integral touch screen for operator interface. One Normally Open Flame relay contact and one Normally Open Fault relay contact is provided for interlock. 0-20 or 4-20 mA scalable analog output is also provided. Power input is 24 VDC @120 mA. Temperature sensor is included that provides display in degree F and C. System is self checking (no mechanical shutter) fit for use in SIL3 application. Approvals include (IP66), Class I Div 1 (IEC Ex d-ATEX Zone 1) for PF version and Class I, Div 2 (IEC Ex nA) for quick disconnect type models. For remote monitoring and configuration, FLAMETOOL –HMI (support 32 loops) or FLAMETOOL-PC (Supports 248 loops) is available. Available models are UVtron only (clean gases), IR only (oil and coal), UVtron plus IR (for all fuels- all applications including SRU, Kiln etc.). (UVSS is currently disabled). Application: Combination DC signal processor and dual UV/IR Viewing head Keypad: Integrated Electrical Ratings: 22-26 Vdc Output: 4-20mA Communications: ModBus and RS422 Compatible Dimensions: 4.3 in. wide x 5.8 in. deep x 5.5 in. high (109 mm wide x 147 mm deep x 117 mm high) Approvals, CSA: Approved (Temperature Range -40 to 158°F; -40 to 70°C) Approvals, Factory Mutual: Approved (Temperature Range -40 to 158°F; -40 to 70°C) Approvals, Others: SIL3 (Temperature Range -40 to 158°F; -40 to 70°C) Material Number Description Status Monitoring Mounting Connection Type Used With Required Components Combination DC signal processor and dual UV/IR Viewing head U2-1010 Combination DC signal processor and dual UV/IR Viewing head. LED for each sensor, flame relay, and self check. 1" NPT process connection 12 pin connector Cable and connector, PT adapter and purge air coupler sold separately. U2-1010-PF Combination DC signal processor and dual UV/IR Viewing head with 10-ft pigtail. LED for each sensor, flame relay, and self check. 1" NPT process connection pigtail, 10-ft (3m) PT adapter and purge air coupler sold separately. U2-1010-PF-050 Combination DC signal processor and dual UV/IR Viewing head with 50-ft (15m) pigtail. LED for each sensor, flame relay, and self check. 1" NPT process connection pigtail, 50-ft (15m) PT adapter and purge air coupler sold separately. U2-1010-PF-100 Combination DC signal processor and dual UV/IR Viewing head with 100-ft (30m) pigtail. LED for each sensor, flame relay, and self check. 1" NPT process connection pigtail, 100-ft (30m) PT adapter and purge air coupler sold separately. U2-1018-PF Combination DC signal processor and dual UV/ IR Viewing head with 10-ft pigtail. Pipe fitting connection. LED for each sensor, flame relay, and self check. 1" NPT process connection pigtail, 10-ft (3m) PT adapter and purge air coupler sold separately. Combination DC signal processor and IR Viewing head U2-1012 Combination DC signal processor and IR Viewing head. LED for each sensor, flame relay, and self check. 1" NPT process connection 12 pin connector Cable and connector, PT adapter and purge air coupler sold separately. U2-1012-PF Combination DC signal processor and IR Viewing head with 10-ft pigtail. Pipe fitting connection. LED for each sensor, flame relay, and self check. 1" NPT process connection pigtail, 10-ft (3m) PT adapter and purge air coupler sold separately. Combination DC signal processor and UV Viewing head U2-1016 Combination DC signal processor and UV Viewing head. LED for each sensor, flame relay, and self check. 1" NPT process connection 12 pin connector Cable and connector, PT adapter and purge air coupler sold separately. U2-1016-PF Combination DC signal processor and UV Viewing head with 10-ft pigtail. Pipe fitting connection. LED for each sensor, flame relay, and self check. 1" NPT process connection pigtail, 10-ft (3m) PT adapter and purge air coupler sold separately. 70-6910 877 Industrial Flame Monitoring IFM Accessories ISO UNIT Material Number Application Description Used With ISO-OR Replacement O-ring Replacement O‑ring for ISO‑UNIT and ISO‑UNITSS ISO-UNIT and ISO-UNITSS ISO-QW Replacement quartz window Replacement quartz window for ISO‑Unit and ISO‑UnitSS ISO-UNIT and ISO-UNITSS ISO-RR Replacement retainer ring Replacement retainer ring for ISO‑UNIT ISO-UNIT ISO-RRSS Replacement retainer ring Replacement retainer ring for ISO‑UNITSS ISO-UNITSS ISO-UNIT Sealing union with quartz window 1 in. NPTF sealing union with quartz window and 1/2 in. NPTF purge port. ISO-UNITHPGT Sealing Union - Stainless Steel 1" NPTF w/1/2" purge port Sealing Union ‑ Stainless Steel 1" NPTF w/1/2" purge port ISO-UNITSS Sealing union with quartz window 1 in. NPTF stainless steel sealing union with quartz window and 1/2 in. NPTF purge port. Flame Tool Material Number Application Description Used With Comments FLAMETOOLS-HMI/U For all series 700, 500 and U2 Remote programming and logging using touchscreen system. Uses Honeywell S7999 display All 700, 500 and U2 family Supports multiple loops FLAMETOOLS-PC For all series 700, 500 and U2 Remote programming and logging using user PC. Supports Windows 7 and 8, includes RS232 converter cable and manual All 700, 500 and U2 family Supports multiple loops 878 70-6910 IFM Accessories Industrial Flame Monitoring Accessories Material Number Application Description Used With 700-1 Swivel Mount Swivel Mount, 1" NPT to 1/2" NPT S700 and S800 Viewing heads 700-2 Swivel Mount Swivel mount for S700 and S800 series viewing heads. Flanged connection to 1/2 in. NPTM connection. S700 and S800 series viewing heads 700-3 Swivel Mount Swivel mount for S700 and S800 series viewing heads. 1/2 in. NPTF to 1/2 in. NPTM connection. S700 and S800 series viewing heads 700ACC Model S700 viewing head cooling jacket Model S700 viewing head cooling jacket. Use with vortex coolers. Vortex coolers 700CRLT Liquid tight cable restraint Liquid tight cable restraint for S700 and S800 series viewing heads. For S800 viewing head, purchase S800 adapter ring, part 800-ACC-RING, separately. S700 and S800 series viewing heads. For S800 viewing head, purchase S800 adapter ring, part 800-ACC-RING, separately. 700DA Delrin adapter replacement Delrin adapter replacement for S700 series viewing heads. 1/2 in. NPTF process and 1/4 in. NPTF purge connections. S700 series viewing heads 700DA-1 Delrin adapter replacement Delrin adapter replacement for S700 series viewing heads. 1 in. NPTF process and 1/4 in. NPTF purge connections. S700 series viewing heads 700LTA Liquid tight viewing head cable adapter Liquid tight viewing head cable adapter for S700/S800 series viewing heads. S700 and S800 series viewing heads 700RAA Model S700/S800 viewing head right angle adapter Model S700/S800 viewing head right angle adapter. 1/2 in. NPTF to 1/2 in. NPTM connection. 700UA Ultem heat insulating adapter Ultem heat insulating adapter for S700 series viewing heads. 1/2 in. NPTF process and 1/4 in. NPTF purge connections. S700 series viewing heads 800ACC Model S800 viewing head cooling jacket Model S800 viewing head cooling jacket. Use with vortex coolers. Vortex coolers 800ACC-RING Adapter ring Adapter ring to fit 800 viewing head to 700ACC cooling jacket and 700CRLT cable restraint. 800 viewing head to 700ACC cooling jacket and 700CRLT cable restraint 800DA Delrin adapter replacement Delrin adapter replacement for S800 series viewing heads. 1/2 in. NPTF process and 1/4 in. NPTF purge connections. S800 series viewing heads 800UA Ultem heat insulating adapter Ultem heat insulating adapter for S800 series viewing heads. 1/2 in. NPTF process and 1/4 in. NPTF purge connections. S800 series viewing heads ACC55XBE Air cooling canister for Model S55XBE viewing heads Air cooling canister for Model S55XBE viewing heads. 1/4 inch air inlet port. Use with vortex coolers. Model S55XBE viewing heads; Vortex coolers ACC5XX Air cooling canister for Model 5XX viewing heads Air cooling canister for Model 5XX viewing heads. 1/4 inch air inlet port. Use with vortex coolers. Model 5XX viewing heads; Vortex coolers ASY55XBE Model S55xBE viewing head installation. Cable Assembly, 50 foot C330S with overmolded S55xBE connector. Includes 50 foot 4 conductor cable with foil/braid shield and coupling nut tied to shield. Use with Model S55xBE Viewing Heads Model S55xBE Viewing Heads ASY55XBE-50 Model S55xBE viewing head installation. Cable Assembly, 50 foot C330S with overmolded S55xBE connector. Includes 50 foot 4 conductor cable with foil/braid shield and coupling nut tied to shield. Use with Model S55xBE Viewing Heads Model S55xBE Viewing Heads ASY55XBE-100 Model S55xBE viewing head installation Cable Assembly, 100 foot C330S with overmolded S55xBE connector. Includes 200 foot 4 conductor cable with foil/braid shield and coupling nut tied to shield. Use with Model S55xBE Viewing Heads Model S55xBE Viewing Heads 70-6910 879 Industrial Flame Monitoring IFM Accessories Material Number Application Description Used With ASY55XBE-200 Model S55xBE viewing head installation. Cable Assembly, 200 foot C330S with overmolded S55xBE connector. Includes 200 foot 4 conductor cable with foil/braid shield and coupling nut tied to shield. Use with Model S55xBE Viewing Heads Model S55xBE Viewing Heads ASY55XBE-300 Model S55xBE viewing head installation Cable Assembly, 300 foot C330S with overmolded S55xBE connector. Includes 300 foot 4 conductor cable with foil/braid shield and coupling nut tied to shield. Use with Model S55xBE Viewing Heads Model S55xBE Viewing Heads ASY785 Model S70x/S80x viewing head installation. Cable Assembly, 50 foot C330S with pre-wired S70x/ S80x connector. Includes 50 foot 4 conductor, 22g cable with drain, foil/braid shield and connector housing tied to shield. Use with Model S70x/S80x Viewing Heads Model S70x/S80x Viewing Heads ASY785-200 Model S70x/S80x viewing head installation. Cable Assembly, 200 foot C330S with pre-wired S70x/S80x connector. Includes 50 foot 4 conductor, 22g cable with drain, foil/braid shield and connector housing tied to shield. Used with Model S70x/S80x Viewing Heads Model S70x/S80x Viewing Heads ASY786 Model S70x/S80x viewing head installation. Field Wireable Shielded Connector for S70x/S80x Viewing Heads. Used with Model S70x/S80x Viewing Heads Model S70x/S80x Viewing Heads ASY964 15-ft cable with quick disconnect 15-ft cable (12 conductor) with quick disconnect for all U2 non-pipe fitting models. U2-1010, U2-1012, U2-1016, U2-1018 models only. C12S 12 conductor cable with braided shield 12 conductor cable with braided shield for use with all U2 combination DC signal processor and viewing heads. Sold per foot. U2-1010, U2-1012, U2-1016, U2-1018, U2-1010-pf, U2-1012-pf, U2-1016-pf, U2-1018-pf models only. Used with -pf models for cable extension. C330S 4 Conductor Cable with braided shield for S70x, S80x and S55xBE Viewing heads 4 Conductor Cable with braided shield for all Iris viewing heads S55xBE, S70x/S80x viewing heads, P522, and P53x signal processors. M3204 Vortex air cooler, model 3204. Vortex air cooler, model 3204 -4SCFM (113SLPM) for maximum refrigeration 275 BTU/HR (69 Kcal/hr) All cooling jackets M3208 Vortex air cooler, model 3208. Vortex air cooler, model 3208 -8SCFM (227 SLPM) for maximum refrigeration 550 BTU/HR (139 Kcal/hr) All cooling jackets M3210 Vortex air cooler, model 3210. Vortex air cooler, model 3210 -10 SCFM (283SLPM) for maximum refrigeration 650 BTU/HR (164 Kcal/hr) All cooling jackets M4025 Vortex air cooler, model 4025. Vortex air cooler, for cabinet model 4025 - maximum refrigeration 1700 BTU/HR (428 Kcal/hr) For processor cabinet cooling M-701-1 Swivel Mount Swivel mount, 2 in. pipe slip-on to 1 in. NPT connection. All viewing heads- S70x with DA-1 M-701-2 Swivel Mount Swivel Mount, 2" NPT to 1" NPT All viewing heads- S70X with DA-1 M-701-2-FLG Flanged swivel mount Flanged swivel mount, 2 in. flanged to 1 in. NPTF. All viewing heads- S70X with DA-1 M-701-2-SS Swivel Mount Swivel mount, 2 in. NPT female to 1 in. NPT female, Stainless steel construction. All viewing heads- S70X with DA-1 M-701-3 Flanged swivel mount Flanged swivel mount, 3-bolt, 4.5 in. flanged to 1 in. NPTF. All viewing heads- S70X with DA-1 M-701-3P Swivel Mount Swivel mount, 3 in. NPTF to 1 in. NPTF connection. All viewing heads- S70X with DA-1 M-701-4 Swivel Mount Swivel mount, 2-bolt to 1 in. NPTF connection. All viewing heads- S70X with DA-1 M-702-6 Orifice and retaining ring set. Orifice and retaining ring set. Used for all viewing heads. Used for all viewing heads. PT-GA1 High temperature gasket for 1 in. locking coupler. High temperature gasket for 1 in. locking coupler. 1 in. locking coupler PT-QL1 Quartz lens for 1 in. locking coupler. Quartz lens for 1 in. locking coupler. 1 in. locking coupler R-518-08 Viewing Head S256 Quick Disconnect Plug Viewing Head S256 Quick Disconnect Plug WDIII S256 viewing head 880 70-6910 IFM Accessories Material Number Application Description Used With R-518-11 Model S55xBE viewing head installation. S55xBE Field Wireable Cable with 6-8mm cable bushing for use with C330S cable. Includes Field wireable with proper bushing size to provide IP seal with C330S cable. No shield at connector, less robust version. Used with Model S55xBE Viewing Heads Model S55xBE viewing head, and C330S cable. R-518-12 Heat Block-1" NPT All viewing heads with 1" NPTF connection All viewing heads with 1" NPTF connection R-518-13 Heat insulating nipple for S70X/S80X series viewing heads. 1/2 in. NPT Ultem heat insulating nipple for S70X/S80X series viewing heads. S70X/S80X series viewing heads R-518-CL12-HTG Locking coupler 1 in. NPT locking coupler with high temperature gasket. Must be used with R-518-PT12 or R-518- PT12L All viewing head that has 1" NPTF R-518-CL12-PG Locking quick disconnect/cam and groove coupler adapter 1 in. NPT aluminum locking quick disconnect/cam and groove coupler adapter with 1/2 in. NPT purge. Must be used with R-518-PT12 and R-518-PT12L All viewing head that has 1" NPTF R-518-CL13-HTG Locking coupler 1/2 in. NPT locking coupler with high temperature gasket. Must be used with R-518-PT13 or R-518- PT13L All viewing heads that have 1/2" NPTF connection R-518-PT12 Insulating locking coupler adapter 1 in. NPT Ultem insulating locking coupler adapter. Used with U2 processor/viewing head. 1 in. NPT Ultem insulating locking coupler adapter use with R-518-CL12-HTG and R-518-CL12PG R-518-PT12L Locking coupler adapter with quartz lens. 1 in. NPT Ultem locking coupler adapter with quartz lens. 1 in. NPT Ultem insulating locking coupler adapter with quartz lens for use with R-518-CL12-HTG and R-518-CL12PG R-518-PT13 Locking coupler adapter only. 1/2 in. NPT Ultem insulating locking coupler adapter use with R-518-CL13-HTG and R-518-CL13HTG R-518-PT13L Locking coupler adapter with quartz lens. 1/2 in. NPT Ultem locking coupler adapter with quartz lens. UVSOURCE Testing any UV based system Ultraviolet light source battery operated Test for any UV tube based system 70-6910 881 Industrial Flame Monitoring IFM Accessories Fiberoptic System Material Number Application Description Used With FASA-GLASS Glass fiber optics assembly for IR flame detection Glass fiber optics complete assembly for IR flame detection with guide pipes and flex connection. Standard assembly length 5‑feet. Standard 5‑ft fiber optic cable. Use FASA‑GLASS‑FT to add additional fiber optic cable length and inner/outer assemblies FASA-GLASS-FT Glass fiber optics assembly for IR flame detection Glass fiber optics complete assembly per foot adder for FASA‑GLASS, for IR flame detection. Includes fiber optic cable and inner/outer assemblies in 1‑ft segments. FASA-GLASS FASA-INT-GLASS Glass fiber optics assembly for IR flame detection Glass fiber optics inner tube assembly for IR flame detection with flex connector. No guide pipes. Standard assembly length 5‑ft. Use FASA‑INT‑GLS‑FT to add additional fiber optic cable length and inner assembly in 1‑ft length FASA-INT-GLS-FT Glass fiber optics assembly for IR flame detection Glass fiber optics inner assembly per foot adder for FASA‑INT‑GLASS, for IR flame detection. Includes fiber optic cable and inner assembly in 1‑ft increment. FASA-INT-GLASS FASA-INT-QTZ-FT Quartz fiber optics assembly for UV/IR flame detection Quartz fiber optics inner tube assembly per foot adder for FASA‑INT‑QUARTZ, for UV/IR flame detection. Includes fiber optic cable and inner assembly in 1‑ft segments. FASA-INT-QUARTZ FASA-INT-QUARTZ Quartz fiber optics assembly for UV/IR flame detection Quartz fiber optics inner tube assembly for UV/IR flame detection with flex connector. No guide pipes. Standard assembly length 5‑ft. Use FASA‑INT‑QTZ‑FT to add for longer than 5' FASA-QUARTZ Quartz fiber optics assembly for UV/IR flame detection Quartz fiber optics complete assembly for UV/IR flame detection with guide pipes and flex connection. Standard assembly length 5. Use FASA‑QUARTZ‑FT for longer than 5’ by 1’ increment FASA-QUARTZ-FT Quartz fiber optics assembly for UV/IR flame detection Quartz fiber optics complete assembly per foot adder for FASA‑QUARTZ, for UV/IR flame detection. Includes fiber optic cable and inner/outer assemblies in 1‑ft increment FASA-QUARTZ FLEX-HOSE Hose for fiber optics assembly. 1/2 in. NPT x 36 in. long flex hose for fiber optics assembly. FOC-GLASS 5-ft Glass Fiber optic cable for IR viewing heads. 5‑ft Glass Fiber optic cable, for IR viewing heads. Use FOC‑GLASS‑FT adder for each additional foot in length required. IR viewing heads FOC-GLASS-FT Glass fiber optic cable per foot adder for FOC-GLASS, for IR flame detection. Glass fiber optic cable per foot adder for FOC‑GLASS, for IR flame detection. FOC-GLASS, for IR flame detection FOC-QUARTZ 5-ft Fiber optic cable, quartz bundle for UV/IR viewing heads with high temperature epoxy 5‑ft Fiber optic cable, quartz bundle for UV/IR viewing heads with high temperature epoxy. Use FOC‑QUARTZ‑FT adder for each additional foot in length required. FOC-QUARTZ-FT FOC-QUARTZ-FT Quartz fiber optic cable for UV/ IR flame detection Quartz fiber optic cable per foot adder for FOC‑QUARTZ, for UV/IR flame detection. FOC-QUARTZ FOLC-9C Fiber optic lens cartridge and coupler Fiber optic lens cartridge and coupler ‑ 9 degree viewing angle FASA and FASA-INT FOLC-HS Replacement fiber optic lens cartridge mounting hood/lens housing Replacement fiber optic lens cartridge mounting hood/ lens housing with 1/2 inch NPT connection. 882 70-6910 IFM Accessories Material Number Application Description Used With FOLC-SC Fiber optic lens cartridge and coupler Fiber optic lens cartridge and coupler ‑ straight connection. S550FOAD Fiber optics adapter viewing head side Fiber optics adapter for S55XB/S55XBE viewing head and U2 models. S55XB/S55XBE viewing heads, U2 S550FOADY-FT Fiber optics adapter Fiber optics adapter with air purge connection for all viewing heads with 1" NPT connection S55XB/S55XBE viewing heads, U2 S550FOADY-FT-AL Fiber optics adapter Fiber optics adapter with air purge connection for all viewing heads with 1" NPT connection S55XB/S55XBE viewing heads, U2 S592-OR Spare Parts for FOLC-SC and FOLC-9C Metal O‑Ring Spare Parts for FOLC‑SC and FOLC‑9C FOLC-SC and FOLC-9C S592-PC Spare Parts for FOLC-SC and FOLC-9C Fiber assembly quartz lens (plano/convex) for FOLC‑SC and FOLC‑9C FOLC-SC and FOLC-9C S592-PP Spare Parts for FOLC-SC and FOLC-9C Plano/Plano window For FOLC‑SC and FOLC‑9C FOLC-SC and FOLC-9C S592-RR Spare Parts for FOLC-SC and FOLC-9C Retainer clip for FOLC‑SC and FOLC‑9C FOLC-SC and FOLC-9C S700FOAD Fiber optics adapter Fiber optics adapter for S70X viewing heads. Any 1/2" viewing head/ FASA S800FOAD Fiber optics adapter Fiber optics adapter for S80X viewing heads. S80X viewing heads 70-6910 883 Industrial Flame Monitoring IFM Accessories GHE Igniter System The GHE High Energy Ignitor is a non fouling high energy device, designed to directly ignite all liquid and gaseous fuels. The GE High Tension Ignitor is designed to provide reliable ignition and or warm up when and where required. It can be applied to boiler applications from industrial to utility lime and cement kiln heaters, etc. Material Number Application Description Used With Comments GHE1-3 Gas high energy pilot igniter assembly used with gaseous fuels Gas high energy pilot igniter assembly used with liquid and gaseous fuels, 1-3 MBH capacity, 1-7/8 inch OD with 36 inch SS flex hose, 36 inch SS air hose, burner mounting tube, high energy probe, igniter tip 12 in. long x 1/2 in OD. Gaseous fuels 1-3 MMBTU/HR capacity, 1-7/8 inch OD with 36 inch SS flex hose, 36 inch SS air hose, burner mounting tube, high energy probe, igniter tip 12 in. long x 1/2 in OD. Standard assembly length 2-feet. Use IGADD for each 1-ft assembly length addition. Order Powerpack-12-CS, IGN-CPC-10 HT cable, IGN-CPC-ADD for longer than 10' cable and Power pack cabinet. Integral optical flame scanner option is available. GHE2-5 Gas high energy pilot igniter assembly used with gaseous fuels Gas high energy pilot igniter assembly used with liquid and gaseous fuels, 1-3 MBH capacity, 1-7/8 inch OD with 36 inch SS flex hose, 36 inch SS air hose, burner mounting tube, high energy probe, igniter tip 12 in. long x 1/2 in OD. Gaseous fuels 2-5 MMBTU/HR capacity, 2-7/8 inch OD with 36 inch SS flex hose, 36 inch SS air hose, burner mounting tube, high energy probe, igniter tip 12 in. long x 1/2 in OD. Standard assembly length 2-feet. Use IGADD for each 1-ft assembly length addition. Order Powerpack-12-CS, IGN-CPC-10 HT cable, IGN-CPC-ADD for longer than 10' cable and Power pack cabinet. Integral optical flame scanner and quick disconnect options are available. GT-LITE Ignitor Spark tip / probe Ignitor Spark tip / probe, 12 inch long x 1/2 inch OD. 12 inch long x 1/2 inch OD. HEPADD High energy probe High energy probe per foot adder for lengths over 2-feet. Use to add length to IPASS, gas high energy replacement pilot igniter probe assembly, in 1-foot increments. IPASS Use to add length to IPASS, gas high energy replacement igniter probe assembly, in 1-foot increments. HV-HT Replacement internal GHE ignitor cable with contact Replacement internal GHE ignitor cable with contact, 2-feet length standard. Internal cable from igniter tip to junction box. Use HV-HT-FT cable adder for each additional foot in length required. GHE ignitor cable Internal cable from igniter tip to junction box. Use HV-HT-FT cable adder for each additional foot in length required. HV-HT-FT Replacement internal GHE ignitor cable Replacement internal GHE ignitor cable per foot adder for lengths over 2-feet. Use to add length to HV-HT in 1-foot increments. GHE ignitor cable Use to add length to HV-HT in 1-foot increments. IGADD Ignitor assembly per foot adder Ignitor assembly per foot adder for igniter length over 2-ft. Use to add length to GHE1-3 or GHE2-5, gas high energy pilot igniter assembly in 1-foot increments. Add length to GHE1-3 or GHE2-5, gas high energy pilot igniter assembly in 1-foot increments Foot adder for igniter length over 2-ft IGN-CPC-10 Ignitor cable 10 ft with canon plug Ignitor cable 10 ft with canon plug for POWERPACK-12-CS. From power pack to igniter. To add length, use IGN-CPC-ADD. POWERPACK-12-CS From power pack to igniter. To add length, use IGN-CPC-ADD. IGN-CPC-ADD Cannon plug cable Cannon plug cable adder for length over 10-ft. Per foot adder for IGNCPC- 10\. IGN-CPC-10. For length over 10-ft IGN-CPC-LB Replacement ignitor probe junction box with canon plug receptacle Replacement ignitor probe junction box with canon plug receptacle for GHE ignitors. GHE ignitors IPASS GHE pilot igniter probe assembly without burner mounting tube, flange, gas insert or air/gas flex hoses. GHE pilot igniter probe assembly includes igniter tip, junction box. Standard assembly is 2'. Use HEPADD for longer length. Order 12- Jule PowerPack,-12-CS and IGN-CPC-10/ IGN-CPC-ADD Gaseous fuels Includes high energy probe, igniter tip 12 in. long x 1/2 in OD and junction box with receptacle. Standard assembly length 2-feet. Use HEPADD for each 1-ft assembly length addition. Order 12-Joule POWERPACK-12-CS and associated cabling with canon plug NEMA-12-ADD NEMA 12 enclosure for igniter powerpack. NEMA 12 enclosure for igniter powerpack. Igniter powerpack 884 70-6910 IFM Accessories Material Number Application Description Used With Comments NEMA-4-ADD NEMA 4 enclosure for igniter powerpack. NEMA 4 enclosure for igniter powerpack. Igniter powerpack NEMA-4X-ADD NEMA 4X enclosure for igniter powerpack. NEMA 4X enclosure for igniter powerpack. Igniter powerpack POWERPACK-12-CS Ignitor 12 Joule Power pack for GHE and IPASS Ignitor 12 Joule Power Pack GHE and IPASS 120V/220V/50-60Hz, output energy 2,500Vdc, 12 Joule pulses @ 6 sparks/second. QDADD Quick disconnect/cam and groove coupler Add quick disconnect/cam and groove coupler on GHE2-5 in place of the standard flange connection to the burner mounting tube. GHE2-5 70-6910 885 Industrial Flame Monitoring Viewing Heads 700 and 800 System Available in single sensor only, UVTron or IR. Options include quick disconnect with two LEDs or factory installed cable. Application: Flame Detector for Oil Fired burners Mounting: 1/2" NPTF or 1" NPTF with 1/4" NPT Purge connection Electrical Ratings: 22 to 26Vdc from signal processor Sight Pipe (NPT): 1/2 in. Purge Air Pipe (NPT): 1/4 in. Ambient Temperature Range: -40 to 149°F (-40 to 65°C) Approvals, CSA: Approved CSA, FM IEC, SIL3 (Temp rating -40 to 149°F/-40 to 65°C) Approvals, Factory Mutual: Approved Environmental, Electrical, or Ingress Protection Rating: IP64 Required Components: Order ASY785 (50foot) or ASY785-200 (200ft) for molded, shielded cable assemblies. ASY785 or ASY785-200 are recommended for new installations. Material Number Type Electrical Connections Shutter UV Gain Adjustment IR Gain Adjustment Dimensions Comments Used With S702 IR Compact viewing head with 15-foot cable Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep x 2.0 in. high (51 mm wide x 246 mm deep x 51 mm high) Removable connector cover for diagnostic LED viewing during installation. Use with 700 AC SP or 700DC SP S702PF IR Compact viewing head with 10-foot cable Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep x 2.0 in. high (51 mm wide x 246 mm deep x 51 mm high) S706 UV Compact viewing head with 15-foot cable Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep x 2.0 in. high (51 mm wide x 246 mm deep x 51 mm high) Removable connector cover for diagnostic LED viewing during installation. Use with 700 AC SP or 700DC SP S706PF UV Compact viewing head with 15-foot cable Quick disconnect plug Electronic 1-9 2.0 in. wide x 9.7 in. deep x 2.0 in. high (51 mm wide x 246 mm deep x 51 mm high) Use with 700 AC SP or 700DC SP S802 IR Compact viewing head with 15-foot cable Quick disconnect plug Electronic 1-9 1.8 in. wide x 9.2 in. deep x 1.8 in. high (46 mm wide x 234 mm deep x 46 mm high) Removable connector cover for diagnostic LED viewing during installation. Use with 700 AC SP or 700DC SP S806 UV Compact viewing head with 15-foot cable Quick disconnect plug Electronic 1-9 1.8 in. wide x 9.2 in. deep x 1.8 in. high (46 mm wide x 234 mm deep x 46 mm high) Removable connector cover for diagnostic LED viewing during installation. Use with 700 AC SP or 700DC SP 886 70-6910 Viewing Heads S55xBE Viewing head The S550BE is provided with UVTron and IR sensors. System is self checking, no mechanical shutters, not adversely affected by X or Gamma rays generated by pipe check welding. Suitable for all fuel flames, single or multiple fuels. Optional pipe fitting (PF) versions provided with factory installed cable. Suitable for hazardous location duty. SIL 3 capable. • Not adversely affected by Gamma Rays or X-Rays. • Mount in any orientation. • IR gain selection of 0-699. • UV gain selection of 0-99. • 2 digital displays. • Quick disconnect plug. • Parameters stored in signal processor EEPROM. • Ultraviolet and infrared with electronic shutter. • Ambient Temperature: -40°F to +149°F (-40°C to +65°C) • 22-26 VDC supplied by signal processor. • CSA Rated IP64 Enclosure. • Used with P532, P532, P531, P531, P522, P522 signal processors. Application: Flame Detector for All fuels multiple burners Mounting: 1" NPTF burner front with 1/2" purge connection Electrical Ratings: 22 to 26Vdc from signal processor Sight Pipe (NPT): 1 in. Purge Air Pipe (NPT): 1/2 in. Dimensions: 4.1 in. wide x 8.1 in. deep x 5.4 in. high (104 mm wide x 206 mm deep x 137 mm high) Ambient Temperature Range: -40 to 158°F (-40 to 70°C) Approvals, CSA: Approved CSA Approvals, Others: SIL3 (Temp rating -40 to 149°F/ -40 to 65°C) IECEx IEC: Approved Approvals, Factory Mutual: Approved Environmental, Electrical, or Ingress Protection Rating: IP64 Used With: P522, P531 and P532 Processors Material Number Type Electrical Connections Shutter UV Gain Adjustment IR Gain Adjustment Digital Displays Comments Required Components Flame Detector for All fuels multiple burners S550BE Quick disconnect plug Electronic of IR only 0-99 0-699 Yes (2) 2 digit display for UV and IR Use with molded cable ASY55XBE or ASY55XBE-200. P522 or P532 signal processor. S550BE-PF UV/IR Viewing Head 10 foot pigtail Electronic of IR only 0-99 0-699 Yes (2) 2 digit display for UV and IR Factory installed 10' cable. P522 or P532 signal processor. Flame Detector for Gas multiple Burners S556BE UV Viewing Head with Digital Display Quick disconnect plug 0-99 Yes (1) 2 digit display for UV Use with molded cable ASY55XBE or ASY55XBE-200. P522 or P532 signal processor. S556BE-PF UV Viewing Head with Digital Display 10 foot pigtail 0-99 Yes (1) 2 digit display for UV and IR P522 or P532 signal processor. Flame Detector for Oil and Coal multiple burners S552BE Quick disconnect plug Electronic 0-699 Yes (1) 2 digit display for IR Use with molded cable ASY55XBE or ASY55XBE-200. P522 or P532 signal processor. S552BE-PF IR Viewing Head 10 foot pigtail Electronic 0-699 Yes (1) 2 digit display for IR P522 or P532 signal processor.